4
C CONTROLLER SETTING UTILITY
4
- 14
4.5 Module Monitoring Tab
(d) Monitored or tested module
The monitoring from this screen and the following tests are performed for the
module selected by "Slot No.".
• Forced output of Output (Y)
• Forced write to buffer memory
• Forced write to CPU shared memory
The setting in the "Type" field of Parameter settings (I/O assignment settings)
does not affect the target.
Note that tests can be performed for only the modules that are controlled by the C
Controller module.
(e) Monitoring of CC-Link module
When monitoring or forced write to buffer memory has been performed to the CC-
Link module where the block data assurance per station function is enabled, cyclic
data will be automatically refreshed.
However, data are automatically refreshed only when monitoring or forced write to
buffer memory has been performed within the range set in "Station information
settings" for the master station.
The range set in "Station information settings" can be confirmed by "Slave station
offset, size information" (buffer memory address: 3E0
module.
For details of the block data assurance per station function, refer to the C
Controller Module User's Manual (Hardware Design, Function Explanation).
The following area will not be refreshed when monitoring or forced write to buffer
memory has been performed.
• The write (send) area of link refresh devices (buffer memory) will not be
refreshed when monitoring has been performed.
• The read (receive) area of link refresh devices (buffer memory) will not be
refreshed when forced write to buffer memory has been performed.
(f) Precautions for changing module configuration
When module configuration is changed after starting C Controller setting utility,
any of the following operation updates the module configuration information.
• Set the Connection settings.
Start monitoring
• Click the
System info
• Click the
button in the <<Module monitoring >> tab.
button in the <<Module monitoring >> tab.