Description of the blocks
4.1 Functions for all blocks
Bit = 1: The control commands are reset by the block. This, for example, ensures that if a
control command is sent from the SFC, the command is reset automatically after a step is
exited.
4.1.10.4

Enabling resetting of commands for the control settings

Number of the
Feature
Feature bit purpose
With this Feature bit, you select how the block handles commands for the control settings
(for example motor on) via the interconnected input parameters.
The default setting is 0.
Bit = 0: The control commands are not reset by the block. If there are two commands relating
to the control settings at the same time, the status of the control settings is retained. In this
case, the "Invalid signal" message is displayed in the standard view of the faceplate.
Bit = 1: The control commands are reset by the block. This, for example, ensures that if a
control command is sent from the SFC, the command is reset automatically after a step is
exited.
4.1.10.5

Setting switch or button mode

Number of the
Feature
Feature bit purpose
Determine whether a separate interconnectable 1-active control input has to be used for
every automatic command of the block or two automatic commands are assigned to a
control input (input signal as pulse signal or as static signal).
The Feature bit affects the following control inputs:
● starting and stopping a motor
● opening and closing a valve
● switching modes (parameters
Setpoint specification internal and external is given in the form of a pulse (pushbutton
operation) or a static signal (switching mode).
You can find the commands for controlling the block in the relevant section on block
operating modes. These are the parameters that are always used for the automatic
operation of a block.
Bit = 0: Button mode: Each automatic command is assigned to a control input. This has a
latching reaction and is 1-active.
82
bit: 3
bit: 4
and
AutModLi
ManModLi
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
)
SIMOCODE pro PCS 7 Library V9.0