Quality Code - Siemens SIMOCODE pro Programming And Operating Manual

Industrial controls, function block library simocode pro
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

4.1.4

Quality code

The process values of the function blocks are generated and transferred along with a signal
status as a structured variable. This contains a statement about the signal quality. The
function blocks determine the appropriate signal status for their process outputs depending
on the signal status of the process inputs. The signal status is formed from the input
parameters according to the priority table below (highest priority is 0). This group status is
displayed in the status bar of the faceplate and of the block icon. The signal status is
displayed for each individual parameter in the faceplate next to the process values.
Table 4- 3
Quality Code
Quality
Priority
Occurs when...
1
Code
16#80
6
No error
SimOn
16#60
16#00
0
RackF_Act
1
ModF_Act
BusFlt
16#28
1
Subnet error
Rack1Err
Rack2Err
OB not load-
ed.
16#28
2
From preceding
blocks
16#68
3
General warning
16#A4
16#FF
Default setting
highest priority is 0
1
"X"= The Quality Code occurs in this block, "–" = The quality code does not occur in this block.
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Meaning
MMDiag
Good
Simulated
value
Bad, device-
specific, value
not valid
Bad, device-
specific
or
Bad, process-
specific
Uncertain,
device-specific
Maintenance
demand
MMMeas
MMLog
MMStat
X
X
X
X
X
X
X
X
Description of the blocks
4.1 Functions for all blocks
MMRevDhl MMOprtn
X
X
X
X
X
X
X
X
X
X
X