4.3.2
Parameterizable functions via the Feature connection MMOprtn
The modules of the library have an input named
responses of the block via this input.
The Feature Bits are assigned in the following order:
Table 4- 11
Feature.Bit
Feature.Bit0
Feature.Bit1
Feature.Bit2
Feature.Bit4
Feature.Bit10
Feature.Bit22
Feature.Bit23
Feature.Bit24
Feature.Bit25
Feature.Bit26
Feature.Bit27
The default setting is 0 in each case.
Note
Feature bit 26 will suppress the reading of DS132.
Feature bit 27 will suppress the reading of DS134.
The feature bits for suppressing reading extended device parameters through datasets 132
and 134 are used only when there is no measurement data (MMMeas block) required for the
particular SIMOCODE pro configuration, as the data relevant to external modules will not be
available.
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Meaning of Feature.Bits
Meaning
Set startup characteristics (Page 80)
Response for Out of Service mode (Page 81)
Resets the commands for switching between modes (Page 81)
Set switch mode or pushbutton mode (Page 82)
Exit local mode (Page 84)
Update acknowledgment and error status of the alarm call (Page 87)
0 = All messages are forwarded via the Event16Ts block to the APL motor
block Alarm view.
1 = All messages are shown in the Alarm view of the MMOprtn block.
Activate local operator permission (Page 87)
Suppression of all messages (Page 88)
Suppress reading of extended device parameters1
Suppress reading of extended plus device parameters1
Description of the blocks
. You can influence various
Feature
4.3 MMOprtn block
101