DNP V3.00 Device Profile
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Name
278
>Door open
279
>CB wait
280
52 Breaker
281
52 Breaker status
282
Disconnect switch
Disconnect switch
283
status
284
Gnd switch
285
Gnd switch status
286
Switch 1
287
switch 1 status
288
Switch 2
289
switch 2 status
290
Switch 3
291
switch 3 status
292
Switch 4
293
switch 4 status
294
Switch 5
295
switch 5 status
296
Switch 6
297
switch 6 status
298
auto-recl.ac.
299
protection act.
3-16

Extension

>Door open; ON = 1, OFF = 0
>Circuit breaker wait; ON = 1, OFF = 0
Control switches return position indication(double
point commands)
input state of switch breaker; 0=open, 1=close
switch breaker failure status; 0=switch breaker position is
open or close, 1= switch breaker is in an intermediate position
or position state is incorrect.
input state of disconnect switch; 0=open, 1=close
disconnect switch failure status; 0= disconnect switch position
is open or close, 1= disconnect switch is in an intermediate
position or position state is incorrect.
input state of ground switch; 0=open, 1=close
ground switch failure status; 0= ground switch position is
open or close, 1= ground switch is in an intermediate position
or position state is incorrect.
input state of switch 1; 0=open, 1=close
switch 1 failure status; 0= switch 1 position is open or close,
1= switch 1 is in an intermediate position or position state is
incorrect.
input state of switch 2; 0=open, 1=close
switch 2 failure status; 0= switch 2 position is open or close,
1= switch 2 is in an intermediate position or position state is
incorrect.
input state of switch 3; 0=open, 1=close
switch 3 failure status; 0= switch 3 position is open or close,
1= switch 3 is in an intermediate position or position state is
incorrect.
input state of switch 4; 0=open, 1=close
switch 4 failure status; 0= switch 4 position is open or close,
1= switch 4 is in an intermediate position or position state is
incorrect.
input state of switch 5; 0=open, 1=close
switch 5 failure status; 0= switch 5 position is open or close,
1= switch 5 is in an intermediate position or position state is
incorrect.
input state of switch 6; 0=open, 1=close
switch 6 failure status; 0= switch 6 position is open or close,
1= switch 6 is in an intermediate position or position state is
incorrect.

Internal controls

Protection activation
Description
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
3
3
1
1
1
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
126
1
C53000-L1840-A001-01