Description of the blocks
4.1 Functions for all blocks
Bit = 1: Direct changeover is enabled.
You can reverse the motor direction directly. The motor block reverses the direction
automatically. The motor is stopped and is started in the other direction when the time set in
the
4.1.10.8

Resetting via input signals in the event of interlocking (Protection) or errors

Number of the
Feature
Feature bit purpose
Define how automatic control is to be re-enabled after an active interlock.
The default setting is 0.
Bit = 0: After an interlock (only Protection: Input parameter
only be restarted using a reset command. Reset is initiated either by operator input in the
faceplate or via the interconnectable input parameter (
currently pending command takes effect in automatic mode.
Bit = 1: It is also possible to reset with a 0-1 edge change in the control signal in automatic
mode.
4.1.10.9

Exit local mode

Number of the
Feature
Feature bit purpose
Define how "Local mode" is either exited or will be exited with LocalSetting = 1 or
LocalSetting = 2 and if the mode is not specified by
The default setting is 0.
Bit = 0: Exiting local mode in manual mode (bumpless because the control signals are
continuously adjusted).
Bit = 1: When local mode is exited, the mode changes back to the last mode that was active
prior to local mode (not bumpless).
4.1.10.10

Enable runtime for feedback signals

Number of the
Feature
Feature bit purpose
To activate the runtime of feedback signals.
The default setting is 0.
Bit = 0: Deactivated: Tracking of feedback for simulation immediately after the trigger signal.
84
parameter has elapsed.
IdleTime
bit: 9
bit: 10
bit: 11
AutModLi
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
) or errors, the system can
Protect
= 1) in the block. Thereafter, the
RstLi
or
.
ManModLi
SIMOCODE pro PCS 7 Library V9.0