8.3.3.11

Resetting, testing and parameterizing via commands

The "Commands" menu item contains all commands relating to SIMOCODE pro, e.g. for
testing the feeder, resetting after tripping and/or transferring parameters into the memory
module or into SIMOCODE pro.
Program memory module
Parameters are transferred to memory module. The memory module must be plugged into
the system interface for this purpose.
Clear memory module
Parameters in memory module are reset. The memory module must be plugged into the
system interface for this purpose.
Read memory module
Acceptance of the parameters from the memory module into the basic unit. The memory
module must be plugged into the system interface for this purpose.
Memory module write protection on
All contents of the memory module are write-protected. This prevents any inadvertent
changes to the contents of the memory module and any parameter changes to the
connected SIMOCODE pro V basic unit.
An inadvertent change of parameters for a motor feeder is prevented.
SIMOCODE pro signals the successful execution of the command with the event
"Memory module write-protected".
Memory module write protection off
With this command you can cancel the write protection of the memory module.
Restart
Initialization of SIMOCODE pro. New start.
Factory settings
All parameters assume their factory settings again.
Set time (= PC time)
If no NTP server address has been configured or no server has been found in the network,
you can set the time of day here, that is, the real-time clock of SIMOCODE pro is set to the
system time of the computer.
Test
Execute the test function. Same function as "TEST/RESET" button on the basic unit and
operator panel
Reset
Execute a reset operation. Same function at "TEST/RESET" button on the basic unit and
operator panel.
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Description of system components
8.3 Operator panel with display
129