Siemens SIMOCODE pro Programming And Operating Manual page 236

Industrial controls, function block library simocode pro
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Parameter
A.1 MMDiag block parameter
Parameter
Data format
PA_Diag
DWORD
Slv_Typ
BOOL
Diag_Sts
SMCSTATUS
(Page 237)
Diag_Evt
SMCEVNT
(Page 238)
Diag_Wrn
SMCWRNG
(Page 240)
Diag_Trp
SMCTRP
(Page 242)
ST_Worst
BYTE
OMode
DWORD
ErrorNum
INT
MsgErr1
BOOL
MsgStat1
WORD
MsgAckn1
WORD
ReserveOut
WORD
Structure of OMODE
Table A- 3
Byte
Byte 3
Byte 2
Byte 1; 0
236
Default setting
Meaning
16#00
Diagnostic information for maintenance
FALSE
0 = PROFIBUS
1 = PROFINET
SIMOCODE diagnostic status information
SIMOCODE diagnostic event information
SIMOCODE diagnostic warning information
SIMOCODE diagnostic trip information
16#80
Worst Signal Status
16#00
Status MODE
-1
Error number
FALSE
1 = Messaging error occurs
16#00
ALARM_8P: Status Output
16#00
ALARM_8P: ACK_STATE Output
16#00
Reserved
Structure of OMODE – MMDiag
Value
16#80:
Valid data
16#40:
Invalid data
16#20:
Redundancy error
16#01:
Warm restart (OB100)
16#0000
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Meaning
Irrelevant
Irrelevant
SIMOCODE pro PCS 7 Library V9.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simocode pro pcs 7