Motor Protection; Interlocking - Siemens SIMOCODE pro Programming And Operating Manual

Industrial controls, function block library simocode pro
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Reference
MMRevDhl - Maintenance (Page 225)
4.7.12

Motor Protection

The motor protection function is used to switch off the motor on a thermal overload
(
Trip = 0
If the motor is switched off via the motor protection function, a message is generated
(process control message). This is displayed in the faceplate with the text "Motor protection."
You can influence the reset via various Feature.Bits. For more details, refer to the section
5.6.3 "Resetting the block in case of interlocks or errors" .
4.7.13

Interlocking

Interlocks
This block provides the following interlocks:
Feature 2 bit 16 = 0:
● Activation enable
● Interlock without reset ("Interlock")
● Interlock with reset ("Protection")
Feature 2 bit 16 = 1:
● Activation enable forward
● Activation enable reverse
● Interlock forward without reset ("Interlock forward")
● Interlock reverse without reset ("Interlock reverse")
● Interlock forward with reset ("Protection interlock forward")
● Interlock reverse with reset ("Protection interlock reverse")
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
, interconnectable input parameters).
Description of the blocks
4.7 MMRevDhl motor block
209