4.3.19

Status information

The status information is communicated to WinCC for display in the faceplates.
Table 4- 40
Status1
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Status information – MMOprtn
Description
Occupied
BatchEn
0 = PROFIBUS
1 = PROFINET
OosAct.Value
OosLi active
0 = Man Active
1 = Auto Active
1 = Local Active
1 = Command fast forward / closed / reverse
1 = Motor stop
1 = Forward/Open Command
1 = Fast reverse Command
1 = Reverse Command
1 = Mode selector S1 on
1 = Reset on
0 = Test function inactive, (PIO)
1 = Test function active
0 = Emergency start inactive (PIO)
1 = Emergency start active
0 = Trip Reset inactive, (PIO)
1 = Trip Reset active
1 = Feedback fast forward / reverse on / close positioner
1 = Status – Motor OFF
1= Feedback forward ON / motor ON / positioner open
1 = Event – overload
1 = Status – change-over pause active
Status – Remote:
0 = Local Operation
1 = REMOTE Operation
1 = Status – General fault
1 = Status – General warning
1 = Feedback fast reverse / open positioner
1 = Feedback reverse on / close positioner
1 = Status – Interlocking time active
1 = Group error
0 = No error
MsgLock enabled