• Sending Device Read/Write Commands Common to AnA/AnU CPU
Sequence
Communications
No. (HEX)
sequence name
810
Device memory
(032A)
batch read as word
data (all device
types except T/C)
811
Device memory
(032B)
batch read as word
data (T/C device
type)
812
Device memory fill
(032C)
as word data (all
device types
except T/C)
813
Device memory fill
(032D)
as word data (T/C
device type)
814
Device memory
(032E)
batch read as bit
data (all device
types except T/C)
815
Device memory
(032F)
batch read as bit
data (T/C device
type)
816
Device memory fill
(0330)
as bit data (all
device types
except T/C)
817
Device memory fill
(0331)
as bit data (T/C
device type)
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Computer Link
Device type
command
QR (Device
Device other
memory batch
than
read as word
Timer/Counter
data)
Timer/Counter
(T, C)
QW (Device
Device other
memory fill as
than
word data)
Timer/Counter
Timer/Counter
(T, C)
JR (Device
Device other
memory batch
than
read as bit data)
Timer/Counter
Timer/Counter
(T, C)
JW (Device
Device other
memory fill as bit
than
data)
Timer/Counter
Timer/Counter
(T, C)
A Standard System Protocol
Function
Reads the word data for the number of device
points starting from the specified device address
for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the spec-
ified station number (and the PLC number that
follows), converts the data into hexadecimal,
and stores it starting from the specified word + 2
in the CS/CJ-series CPU Unit.
Reads the word (PV) data for the number of
device points starting from the specified device
address for the specified device type (T, C) in
the Mitsubishi Computer Link Module with the
specified station number (and the PLC number
that follows), converts the data into hexadeci-
mal, and stores it starting from the specified
word + 2 in the CS/CJ-series CPU Unit.
Writes the word data starting from the specified
word + 7 in the CS/CJ-series CPU Unit to the
number of device points starting from the speci-
fied device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and
the PLC number that follows).
Writes the word (PV) data starting from the
specified word + 7 in the CS/CJ-series CPU Unit
to the number of device points starting from the
specified device address for the specified device
type (T, C) in the Mitsubishi Computer Link Mod-
ule with the specified station number (and the
PLC number that follows).
Reads the bit data for the number of device
points starting from the specified device address
for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the spec-
ified station number (and the PLC number that
follows), converts the data into hexadecimal,
and stores it starting from the specified word + 2
in the CS/CJ-series CPU Unit.
Reads the bit (PV) data for the number of device
points starting from the specified device address
for the specified device type (T, C) in the Mitsub-
ishi Computer Link Module with the specified
station number (and the PLC number that fol-
lows), converts the data into hexadecimal, and
stores it starting from the specified word + 2 in
the CS/CJ-series CPU Unit.
Writes the bit data starting from the specified
word + 7 in the CS/CJ-series CPU Unit to the
number of device points starting from the speci-
fied device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and
the PLC number that follows).
Writes the bit (PV) data starting from the speci-
fied word + 7 in the CS/CJ-series CPU Unit to
the number of device points starting from the
specified device address for the specified device
type (T, C) in the Mitsubishi Computer Link Mod-
ule with the specified station number (and the
PLC number that follows).