Omron CJ1W-SCU32 Operation Manual page 317

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

Event name
CTS Check Error
Meaning
An error was found during the CTS check.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Loopback test jig failure.
Noise
The communications circuits in the
Serial Communications Unit are
faulty.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Correct any mistakes in wiring the
loopback test jig.
Implement noise countermeasures.
Replace the Unit.
9 Troubleshooting and Maintenance
Event code
04760000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Check the wiring of the loopback test
jig.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
None
During loopback
test
System
9
9-39