Event name
CTS Check Error
Meaning
An error was found during the CTS check.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Loopback test jig failure.
Noise
The communications circuits in the
Serial Communications Unit are
faulty.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Correct any mistakes in wiring the
loopback test jig.
Implement noise countermeasures.
Replace the Unit.
9 Troubleshooting and Maintenance
Event code
04760000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Check the wiring of the loopback test
jig.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
None
During loopback
test
System
9
9-39