Device variable for CJ-series Unit
Port 1
*_P1_NopCRLFCfg
*_P1_NopEndCodeYN
Cfg
*_P1_NopRcvDatSzCf
g
*1 When the default settings are used, the Baud Rate, Start Bits, Data Length, Stop Bits, Parity Yes/No and Parity
Even/Odd settings are disabled. To specify settings for these items to the settings other than the default, select
User settings.
Default settings are Baud Rate: 9,600 bps, Start Bits: 1 bit, Data Length: 7 bits, Parity: Even parity and Stop
Bits: 2 bits.
*2 When CTS control is enabled, the request to send signal (RTS) turns ON and the transmission starts after the
clear to send signal (CTS) turns ON. When CTS control is disabled, the request to send signal (RTS) turns ON
and the transmission starts without checking whether the clear to send signal (CTS) is ON.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Type
Port 2
*_P2_NopCRLFCfg
BOOL
*_P2_NopEndCodeYN
BOOL
Cfg
*_P2_NopRcvDatSzCf
USINT
g
6 No-protocol Mode
R/W
Name
RW
No-Protocol CR
+ LF Specifica-
tion Setting
RW
No-protocol
End Code
Inclusion Set-
ting
RW
Number of
Received Data
Bytes in No-
protocol Mode
Function
End code
P*_NopCRLFCfg/
P*_NopEndCodeYNCfg
00: No (specify number of
receive data bytes)
01: Yes
10: CR + LF specified
11: Prohibited
0: 256 bytes (default)
Range: 1 to 255 bytes
6-7