9 Troubleshooting and Maintenance
Event name
Command Error
Meaning
A command error occurred.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The constant in the expected receive
message that is set in the protocol
macro is different from the constant in
the message that was received.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
Event name
Sequence Abort Completed
Meaning
The sequence was ended by an Abort setting for the next processing or error processing.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The protocol macro data is not set
correctly.
The baud rate, frame format, or other
system setting does not agree with
the remote node.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
9-40
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Correct the expected receive mes-
sage that is set in the protocol macro
or the message that is sent by the
remote node so that the constant in
the message is the same.
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Check if the protocol data and system
settings are set correctly with a trans-
mission line trace from the CX-Proto-
col.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event code
54A8 0000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Set the system so that the expected
receive messages that are set in the
protocol macros agree with the mes-
sages that are sent by the remote
nodes.
Event code
54A9 0000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Correctly set the protocol macro data.
Make sure that the baud rate, frame
format, and other system settings are
the same as for the remote nodes.
After serial com-
munications start
System
At protocol macro
execution
System