Omron CJ1W-SCU32 Operation Manual page 198

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

5 Serial Gateway
Device variable for CJ-series Unit
Port 1
*_P1_ParityYNCfg
*_P1_ParityBitCfg
*_P1_BaudrateCfg
*_P1_SendDelayCfg
*_P1_SendDelaySetCfg
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you set this set-
ting, set to bits 00 to 14
of *_P1_SendDelayCfg.
*_P1_HlkCTSCtlCfg
*_P1_PmrSgwTimeoutCfg *_P2_PmrSgwTimeoutCfg WORD
*_P1_PmrSgwRespTi
meoutCfg
*_P1_PmrSgwSendTi
meoutCfg
5-6
Port 2
*_P2_ParityYNCfg
*_P2_ParityBitCfg
*_P2_BaudrateCfg
*_P2_SendDelayCfg
*_P2_SendDelaySetCfg BOOL
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you set this set-
ting, set to bits 00 to 14
of *_P2_SendDelayCfg.
*_P2_HlkCTSCtlCfg
*_P2_PmrSgwRespTi
meoutCfg
*_P2_PmrSgwSendTi
meoutCfg
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Type
R/W
Name
BOOL
RW
Parity
BOOL
RW
Parity
Even/Odd
USINT
RW
Baud Rate
(unit: bps)
WORD
RW
Send Delay
Settings
RW
Send Delay
Time
Bit
RW
Send Delay
string
(User-speci-
fied)
BOOL
RW
CTS Control
(*2)
RW
Serial Gateway
Timeout Moni-
toring Time
Settings
USINT
RW
Serial Gateway
Response Tim-
eout Monitor-
ing Time
USINT
RW
Serial Gateway
Send Start Tim-
eout Monitor-
ing Time
Function
FALSE: Yes
TRUE: No
Default: FALSE
FALSE: Even
TRUE: Odd
Default: FALSE
0: 9600, 3: 1200, 4: 2400
5: 4800, 6: 9600, 7: 19200
8: 38400, 9: 57600
10: 115200, 11: 230400
Default: 0
The bits serve the func-
tions described below.
Bit 15: Send delay time
Bits 00 to 14: Send delay
(user-specified)
0: Default (0 ms)
1: User settings
0 to 300 s (0 to 300,000
ms)
(0000 to 7530 hex; 0 to
30,000 decimal) [Unit: 10
ms]
FALSE: No
TRUE: Yes
The bits serve the func-
tions described below.
08 to 15: Serial Gateway
response timeout monitor-
ing time
00 to 07: Serial Gateway
send start timeout moni-
toring time
0: 5 s (default)
Data range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]
0: 5 s (default)
Range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu22Cj1w-scu42

Table of Contents