Omron CJ1W-SCU32 Operation Manual page 260

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

7 Using Modbus-RTU Slave Mode
Device variable for CJ-series Unit
Port 1
*_P1_StopBitSta
*_P1_ParityYNSta
*_P1_ParityBitSta
*_P1_HwSetSta
*_P2_HwSetSta
*_P1_Ser485Sta
*_P1_Ser232Sta
*_P1_TermSta
*_P1_SysSetupErr
*_P1_OperatingSta
*_P1_TransCtlSta
*_P2_TransCtlSta
*_P1_RmtBusySta
*_P1_LclBusySta
*_P1_SigERSta
*_P1_SigDRSta
*_P1_SigCSSta
*_P1_SigRSSta
7-10
Type
Port 2
*_P2_StopBitSta
BOOL
*_P2_ParityYNSta
BOOL
*_P2_ParityBitSta
BOOL
WORD
*_P2_Ser485Sta
BOOL
*_P2_Ser232Sta
BOOL
*_P2_TermSta
BOOL
*_P2_SysSetupErr
BOOL
*_P2_OperatingSta
BOOL
WORD
*_P2_RmtBusySta
BOOL
*_P2_LclBusySta
BOOL
*_P2_SigERSta
BOOL
*_P2_SigDRSta
BOOL
*_P2_SigCSSta
BOOL
*_P2_SigRSSta
BOOL
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
R/W
Name
R
Stop Bits (2
FALSE: 2 bits
bits/1 bit)
TRUE: 1 bit
R
Parity
FALSE: Yes
(Yes/No)
TRUE: No
R
Parity
FALSE: Even
(Even/Odd)
TRUE: Odd
R
Hardware
Bit 15: RS-422/485 setting status
Settings
Bit 14: RS-232C setting status
Bit 13: Terminating resistance set-
ting status
Bit 01: System Setup error
Bit 0: Port operating status
R
RS-422/485
Port types of each port
Setting Sta-
*_P_Ser485Sta/*_P_Ser232Sta:
tus
00: No port
R
RS-232C
01: RS232C
Setting Sta-
10: RS422A/485
tus
11: This status does not exist.
R
Terminating
TRUE: Terminating resistance ON
Resistance
FALSE: Terminating resistance
Setting Sta-
OFF
tus
R
System
TRUE: System Setup error
Setup error
FALSE: System Setup normal
R
Port Operat-
TRUE: Port operating
ing Status
FALSE: Port stopped
R
Communica-
Bit 10: Remote Unit busy (*2)
tions Status
Bit 08: Local Unit busy (*3)
Bit 07: DTR (ER) signal
Bit 06: DSR (DR) signal
Bit 04: CTS (CS) signal
Bit 03: RTS (RS) signal
R
Remote Unit
TRUE: Remote Unit busy (Flow
Busy (*2)
control)
FALSE: Remote Unit ready to
receive
R
Local Unit
TRUE: Local Unit busy (Flow con-
Busy (*3)
trol)
FALSE: Local Unit ready to receive
R
ER signal
TRUE: High
FALSE: Low
R
DR signal
TRUE: High
FALSE: Low
R
CS signal
TRUE: High
FALSE: Low
Rl
RS signal
TRUE: High
FALSE: Low
Function

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu22Cj1w-scu42

Table of Contents