Omron CJ1W-SCU32 Operation Manual page 92

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

2 Initial Settings and Allocations of Device Variable for CJ-series Unit
Protocol Macro Mode
Device variable for CJ-series Unit
Port 1
*_P1_SendDelayCfg
*_P1_SendDelaySetCfg
There is no specific
device variable for
CJ-series Unit to set
the send delay setting
range.
When you reference
this setting, set to bits
00 to 14 of
*_P1_SendDelayCfg.
*_P1_HlkCTSCtlCfg
*_P1_PmrSgwTimeoutCfg *_P2_PmrSgwTimeoutCfg WORD
*_P1_PmrSgwResp
TimeoutCfg
*_P1_PmrSgwSend
TimeoutCfg
*_P1_PmrTransCfg
*_P1_PmrTransTypCfg
2-18
Port 2
*_P2_SendDelayCfg
*_P2_SendDelaySetCfg
There is no specific
device variable for
CJ-series Unit to set
the send delay setting
range.
When you reference
this setting, set to bits
00 to 14 of
*_P2_SendDelayCfg.
*_P2_HlkCTSCtlCfg
*_P2_PmrSgwResp
TimeoutCfg
*_P2_PmrSgwSend
TimeoutCfg
*_P2_PmrTransCfg
*_P2_PmrTransTypCfg
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Type
R/W
Name
WORD
RW
Send Delay
Settings
BOOL
RW
Send Delay
Time
Bit
RW
Send Delay
string
Time (user-
specified)
BOOL
RW
CTS Control
(*1)
RW
Serial Gateway
Timeout Moni-
toring Time
Setting
USINT
RW
Serial Gateway
Response Tim-
eout Monitor-
ing Time
USINT
RW
Serial Gateway
Send Start Tim-
eout Monitor-
ing Time
WORD
RW
Protocol macro
Transmission
Settings
BOOL
RW
Protocol macro
Transmission
method
Function
Bit 15: Send delay time
Bits 00 to 14: Send delay
time (user-specified)
FALSE: Default (0 ms)
TRUE: User settings
0 to 300 s (0 to 300,000
ms)
(0000 to 7530 hex; 0 to
30,000 decimal) [Unit: 10
ms]
FALSE: No
TRUE: Yes
Default: FALSE
08 to 15: Serial Gateway
response timeout monitor-
ing time
00 to 07: Serial Gateway
send start timeout moni-
toring time
0: 5 s (default)
Range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]
0: 5 s (default)
Range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]
Bit 15: Protocol macro
transmission method
Bit 03: Clearing/holding
the contents of the recep-
tion buffer in full-duplex
mode
Bit 02: Link word specifi-
cation data exchange
method
FALSE: Half-duplex
(default)
TRUE: Full-duplex