Conversion Successful but Transmission Failed
Unit status
Serial
communica-
tions mode
The Unit con-
Serial commu-
verted the
nications
received (via
mode is set to
CPU bus)
Protocol
command, but
Macro Mode.
could not send
the command
to the remote
device after
conversion.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Error conditions
Indicator
Command end
display
code sent to
command
source
The SD@ indi-
0204 hex
cators do not
(Remote node
flash at all.
busy)
2607 hex
(transmission
command error
(no right to exe-
cute service))
0205 hex
(response time-
out), etc.
9 Troubleshooting and Maintenance
Cause
Confirmation of
device variable
for CJ-series
Unit, etc.
*_P1(orP2)_Time
A Serial Gateway
outErr (Timeout
send start timeout
Error) is set to
occurred.
TRUE.
(The converted
command will be
discarded without
being sent).
The command
was received by
the Unit, but the
step transition in
the communica-
tions sequence of
the protocol
macro is sus-
pended for either
of the following
reasons.
• The next step is
a Receive com-
mand.
• The Wait com-
mand is being
executed.
*_P1(orP2)_Pmr
The Serial Gate-
SgwProhSta
way is prohibited.
(Serial Gateway
Prohibited Flag
(Protocol Mac-
ros)) is TRUE
(Prohibited sta-
tus).
*_P1(orP2)_HlkC
CTS control is set
TSCtlCfg (CTS
to TRUE(Yes) but
Control) is TRUE
the RTS (RS) sig-
but
nal from the
*_P1(orP2)_SigC
remote device
SSta(CS signal)
was not input to
is FALSE.
the CTS (CS) sig-
nal of the Local
Unit.
Remedy
Correct the communica-
tions sequence.
Alternatively, adjust
*_P1(orP2)_PmrSgwSendT
imeoutCfg (Serial Gateway
Send Start Timeout Moni-
toring Time), as required.
Change
*_P1(orP2)_SgwDsblCmd
(Serial Gateway Prohibit
Switch (Protocol Macros))
to FALSE.
Perform either of the follow-
ing:
Loop the RTS (RS)-CTS
(CS) signals of the Local
Unit.
Disable CTS control.
Input the RTS (RS) signal
from the Remote Unit to the
CTS (CS) signal of the
Local Unit and use CTS
control.
9-5