Omron CJ1W-ID Series User Manual

Omron CJ1W-ID Series User Manual

Machine automation controller
Table of Contents

Advertisement

Quick Links

Machine Automation Controller
NJ-series
CPU Unit
Hardware
User's Manual
NJ501-
NJ301-1
NJ101-
NJ-P3001
CJ1W-ID/IA
CJ1W-INT01
CJ1W-IDP01
CJ1W-OC/OD/OA
CJ1W-MD
CJ1W-B7A
CPU Unit
Power Supply Unit
Basic I/O Units
W500-E1-28

Advertisement

Table of Contents
loading

Summary of Contents for Omron CJ1W-ID Series

  • Page 1 Machine Automation Controller NJ-series CPU Unit Hardware User’s Manual NJ501- NJ301-1 NJ101- NJ-P3001 CJ1W-ID/IA CJ1W-INT01 CJ1W-IDP01 CJ1W-OC/OD/OA CJ1W-MD CJ1W-B7A CPU Unit Power Supply Unit Basic I/O Units W500-E1-28...
  • Page 2 Moreover, because OMRON is constantly striving to improve its high-quality products, the infor- mation contained in this manual is subject to change without notice. 3. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON as- sumes no responsibility for errors or omissions.
  • Page 3: Introduction

    Introduction Introduction Thank you for purchasing an NJ-series CPU Unit. This manual contains information that is necessary to use the NJ-series CPU Unit. Please read this manual and make sure you understand the functionality and performance of the NJ-series CPU Unit before you attempt to use it in a control system.
  • Page 4: Relevant Manuals

    Introduction to NJ-series Controllers  Setting devices and hardware Using motion control   Using EtherCAT  Using EtherNet/IP  Using robot control for OMRON robots  Software settings Using motion control  Using EtherCAT  Using EtherNet/IP  Using OPC UA ...
  • Page 5 Using OPC UA  Using the database connection service   Using the GEM Services  Using robot control for OMRON robots  Using robot control by NJ Robotics  function Using numerical control  Learning about error management and ...
  • Page 6: Manual Structure

    Manual Structure Manual Structure Page Structure The following page structure is used in this manual. Level 1 heading 4 Installation and Wiring Level 2 heading Mounting Units Level 3 heading Level 2 heading Gives the current headings. Level 3 heading 4-3-1 Connecting Controller Components The Units that make up an NJ-series Controller can be connected simply by pressing the Units together...
  • Page 7 Manual Structure Special Information Special information in this manual is classified as follows: Precautions for Safe Use Precautions on what to do and what not to do to ensure safe usage of the product. Precautions for Correct Use Precautions on what to do and what not to do to ensure proper operation and performance. Additional Information Additional information to read as required.
  • Page 8 Manual Structure NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 9: Sections In This Manual

    Sections in this Manual Sections in this Manual Introduction to NJ-series Controllers System Configuration Configuration Units Installation and Wiring Troubleshooting Inspection and Maintenance Appendices Index NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 10: Table Of Contents

    CONTENTS CONTENTS Introduction ....................... 1 Relevant Manuals ...................... 2 Manual Structure ....................... 4 Sections in this Manual .................... 7 Terms and Conditions Agreement ................. 12 Safety Precautions ....................14 Precautions for Safe Use..................20 Precautions for Correct Use................... 30 Regulations and Standards..................34 Versions ........................
  • Page 11 CONTENTS 3-2-1 Models and Specifications ......................3-10 3-2-2 Purpose ............................ 3-10 3-2-3 Installing and Removing ......................3-11 Power Supply Units ....................... 3-14 3-3-1 Models and Specifications ......................3-14 3-3-2 Components and Functions...................... 3-16 3-3-3 Selecting a Power Supply Unit ....................3-17 CJ-series Basic I/O Units ......................
  • Page 12 CONTENTS Section 5 Troubleshooting Overview of Troubleshooting ....................5-2 Section 6 Inspection and Maintenance Periodic Maintenance and Inspection ................... 6-2 6-1-1 Periodic Inspection........................6-2 6-1-2 Unit Replacement Precautions....................6-3 Replacing the Battery......................6-4 6-2-1 Battery Replacement........................6-4 6-2-2 Operation without a Battery......................6-7 Appendices A-1 Specifications ..........................A-2 A-2 Specifications of Basic I/O Units ...................A-3...
  • Page 13 CONTENTS NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 14: Terms And Conditions Agreement

    Omron’s exclusive warranty is that the Products will be free from defects in materials and workman- ship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
  • Page 15 Disclaimers Performance Data Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual perfor- mance is subject to the Omron’s Warranty and Limitations of Liability.
  • Page 16: Safety Precautions

    Safety Precautions Safety Precautions Definition of Precautionary Information The following notation is used in this manual to provide precautions required to ensure safe usage of an NJ-series Controller. The safety precautions that are provided are extremely important to safety. Always read and heed the information provided in all safety precautions.
  • Page 17 Safety Precautions Symbols The circle and slash symbol indicates operations that you must not do. The specific operation is shown in the circle and explained in text. This example indicates prohibiting disassembly. The triangle symbol indicates precautions (including warnings). The specific operation is shown in the triangle and explained in text. This example indicates a precaution for electric shock.
  • Page 18 Safety Precautions Warnings WARNING During Power Supply Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock. Do not attempt to take any Unit apart. In particular, high-voltage parts are present in the Power Supply Unit while power is supplied or immediately after power is turned OFF.
  • Page 19 Safety Precautions Unintended outputs may occur when an error occurs in variable memory or in memory used for CJ-series Units. As a countermeasure for such prob- lems, external safety measures must be provided to ensure safe operation of the system. Provide measures in the communications system and user program to ensure safety in the overall system even if errors or malfunctions occur in data link communications or remote I/O communications.
  • Page 20 Safety Precautions Cautions Caution Application Do not touch any Unit when power is being supplied or immediately after the power supply is turned OFF. Doing so may result in burn injury. Wiring Be sure that all terminal screws and cable connector screws are tightened to the torque specified in the relevant manuals.
  • Page 21 Safety Precautions Precaution on Error Message That Says an Instruction May Cause Unintended Operation Instructions may results in unexpected operation and affect the system if you clear the selection of the Detect an error when an in-out variable is passed to specific instruction argument Check Box in the Program Check Area.
  • Page 22: Precautions For Safe Use

    Precautions for Safe Use Precautions for Safe Use Disassembly and Dropping • Do not attempt to disassemble, repair, or modify any Units. Doing so may result in malfunction or fire. • Do not drop any Unit or subject it to abnormal vibration or shock. Doing so may result in Unit malfunc- tion or burning.
  • Page 23 Precautions for Safe Use Task Design • If the following variables are specified for a condition expression when the execution condition is a condition expression for a variable, event tasks may not be executed when conditions are met or event tasks may be executed when conditions are not met. •...
  • Page 24 Precautions for Safe Use Turning ON the Power Supply • It takes up to approximately 10 to 20 s to enter RUN mode after the power is turned ON. The outputs during this time behave according to the slave or Unit specifications. Use the RUN output on the Power Supply Unit, for example, to implement fail-safe circuits so that external devices do not oper- ate incorrectly.
  • Page 25 Precautions for Safe Use Operation • Confirm that no adverse effect will occur in the system before you attempt any of the following. • Changing the operating mode of the CPU Unit (including changing the setting of the Startup Mode) •...
  • Page 26 Precautions for Safe Use Battery Backup • The user program and initial values for the variables are stored in non-volatile memory in the CPU Unit. The present values of variables with the Retain attribute and the values of the Holding, DM, and EM Areas in the memory used for CJ-series Units are backed up by a Battery.
  • Page 27 Precautions for Safe Use EtherNet/IP Communications • Make sure that the communications distance, number of nodes connected, and method of connec- tion for EtherNet/IP are within specifications. Do not connect EtherNet/IP communications to EtherCAT or other networks. An overload may cause the network to fail or malfunction.
  • Page 28 Precautions for Safe Use • You cannot use standard Ethernet hubs or repeater hubs with EtherCAT communications. If you use one of these, a major fault level error or other error may occur. • Confirm that all of the slaves are connected before you set the transmission delay time by the actual measurement.
  • Page 29 Precautions for Safe Use Motion Control • Confirm the axis number carefully before you perform an MC Test Run. • The motor is stopped if communications are interrupted between the Sysmac Studio and the CPU Unit during an MC Test Run. Connect the communications cable between the computer and CPU Unit securely and confirm that the system will not be adversely affected before you perform an MC Test Run.
  • Page 30 Precautions for Safe Use Restoring Data • You cannot back up, restore, or compare some or all of the settings for certain slaves and Units. Also, you cannot back up, restore, or compare data for disabled slaves or Units. After you restore data, suf- ficiently confirm that operation is correct before you start actual operation.
  • Page 31 Precautions for Safe Use Disposal • Dispose of the product and Batteries according to local ordinances as they apply. • The following information must be displayed for all products that contain primary lithium batteries with a perchlorate content of 6 ppb or higher when shipped to or transported through the State of California, USA. Perchlorate Material - special handling may apply.
  • Page 32: Precautions For Correct Use

    Precautions for Correct Use Precautions for Correct Use Storage and Installation • Follow the instructions in this manual to correctly perform installation. • Do not operate or store the Controller in the following locations. Operation may stop or malfunctions may occur. •...
  • Page 33 Precautions for Correct Use Wiring • Do not allow foreign matter to enter the openings in the Unit. Doing so may result in Unit burning, electric shock, or failure. • Do not allow wire clippings, shavings, or other foreign material to enter any Unit. Otherwise, Unit burning, failure, or malfunction may occur.
  • Page 34 Precautions for Correct Use Replacing Slaves and Units • If you replace a slave or Unit, refer to the operation manual for the slave or Unit for information on the data required for individual slaves or Units and redo the necessary settings. Task Settings •...
  • Page 35 If there is a corrupted file in the SD Memory Card, the file is automatically deleted by the restoration function when the power supply is turned ON. • If you use an OMRON SD Memory Card, the end of the life of the SD Memory Card can be detected in the following ways.
  • Page 36: Regulations And Standards

    Concepts  EMC Directive OMRON devices that comply with EU Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards.* Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
  • Page 37 The NJ-series Controllers comply with the following shipbuilding standards. Applicability to the ship- building standards is based on certain usage conditions. It may not be possible to use the product in some locations. Contact your OMRON representative before attempting to use a Controller on a ship.
  • Page 38: Versions

    Versions Versions Hardware revisions and unit versions are used to manage the hardware and software in NJ-series Units and EtherCAT slaves. The hardware revision or unit version is updated each time there is a change in hardware or software specifications. Even when two Units or EtherCAT slaves have the same model number, they will have functional or performance differences if they have different hardware revisions or unit versions.
  • Page 39 Versions Checking Unit Versions with the Sysmac Studio You can use the Sysmac Studio to check unit versions. The procedure is different for Units and for Eth- erCAT slaves.  Checking the Unit Version of a Unit You can use the Production Information while the Sysmac Studio is online to check the unit version of a Unit.
  • Page 40 Versions  Checking the Unit Version of an EtherCAT Slave You can use the Production Information while the Sysmac Studio is online to check the unit version of an EtherCAT slave. Use the following procedure to check the unit version. Double-click EtherCAT under Configurations and Setup in the Multiview Explorer.
  • Page 41: Related Manuals

    Related Manuals Related Manuals The followings are the manuals related to this manual. Use these manuals for reference. Manual name Cat. No. Model numbers Application Description NJ-series CPU Unit W500 NJ501- Learning the basic specifi- An introduction to the entire NJ-series system is Hardware User’s Manual NJ301-...
  • Page 42 NJ-series Robot O037 NJ501-R Using the NJ-series Robot Describes the settings and operation of the CPU Integrated CPU Unit Integrated CPU Unit. Unit and programming concepts for OMRON robot User’s Manual control. Sysmac Studio W595 SYSMAC- Learning about the Describes the operating procedures of the Robot Integrated SE2...
  • Page 43: Terminology

    Terminology Terminology Term Description absolute encoder home offset This data is used to restore in the CPU Unit the actual position of a Servo Drive with an absolute encoder. The offset is the difference between the command position after homing and the absolute data that is read from the absolute encoder. array specification One of the variable specifications.
  • Page 44 ST programming that is included within a ladder diagram program. instruction The smallest unit of the processing elements that are provided by OMRON for use in POU algorithms. There are ladder diagram instructions (program inputs and out- puts), function instructions, function block instructions, and ST statements.
  • Page 45 Terminology Term Description local variable A variable that can be accessed only from inside the POU in which it is defined. “Local variable” is used as opposed to “global variable.” Local variables include internal variables, input variables, output variables, in-out variables, and external variables.
  • Page 46 Terminology Term Description project unit version A unit version to be set for the project. It is set for the project in the Select Device Area of the Project Properties Dialog Box on the Sysmac Studio. Range Specification One of the variable specifications. You can specify a range for a variable in advance.
  • Page 47 Terminology Term Description variable memory A memory area that contains the present values of variables that do not have AT specifications. It can be accessed only with variables without an AT attribute. NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 48: Revision History

    Revision History Revision History A manual revision code appears as a suffix to the catalog number on the front and back covers of the manual. W500-E1-28 Cat. No. Revision code Revision code Date Revised content July 2011 Original production March 2012 •...
  • Page 49 Revision History Revision code Date Revised content July 2018 • Added information on the hardware revision. • Made changes accompanying release of unit version 1.19 of the CPU Unit. • Made changes accompanying the transfer of explanation for event codes and errors to the NJ/NX-series Troubleshooting Manual.
  • Page 50 Revision History NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 51: Introduction To Nj-Series Controllers

    Introduction to NJ-series Controllers This section describes the features, basic system configuration, specifications, and overall operating procedure of an NJ-series Controller. 1-1 The NJ-series Controllers ........1-2 1-1-1 Features .
  • Page 52: The Nj-Series Controllers

    They provide the safety, reliability, and maintainability that are required of industrial controllers. The NJ-series Controllers provide the functionality of previous OMRON PLCs, and they also provide the functionality that is required for motion control. Synchronized control of I/O devices on high-speed EtherCAT can be applied to safety devices, vision systems, motion equipment, discrete I/O, and more.
  • Page 53  Programming Languages Based on the IEC 61131-3 International Standard The NJ-series Controllers support language specifications that are based on IEC 61131-3. To these, OMRON has added our own improvements. Motion control instructions that are based on PLCo- ® standards and an instruction set (POUs) that follows IEC rules are provided.
  • Page 54: Introduction To The System Configurations

    1 Introduction to NJ-series Controllers  A Wealth of Security Features The many security features of the NJ-series Controllers include operation authority settings and restriction of program execution with IDs.  Complete Controller Monitoring The CPU Unit monitors events in all parts of the Controller, including mounted Units and EtherCAT slaves.
  • Page 55 1 Introduction to NJ-series Controllers CJ-series Unit Support Software Configuration Peripheral USB port Sysmac Studio NJ-series Controller CJ-series Units Power Supply Unit CPU Unit EtherNet/IP EtherCAT Network Configuration Built-in EtherNet/IP port EtherCAT Built-in EtherCAT port Servo Drive/encoder Slave Terminal General-purpose slaves input slaves Additional Information You can connect the Sysmac Studio directly to the Communications Coupler Unit to set up the...
  • Page 56 1 Introduction to NJ-series Controllers Refer to the NJ/NX-series CPU Unit Software User’s Manual (Cat. No. W501) for details on the net- work configuration.  Support Software You can use the following Support Software to set up, monitor, and debug an NJ-series Controller. Sysmac Studio The Sysmac Studio is the main Support Software that you use for an NJ-series Controller.
  • Page 57: Specifications

    1 Introduction to NJ-series Controllers Specifications This section gives the main specifications of the NJ-series Controllers. NJ501- NJ301- NJ101- Item 12 11 10 90 5 4 3 LD instruction 1.2 ns (1.9 ns or less) 2.0 ns (3.0 ns or less) 3.3 ns (5.0 ns or less) Instruction Process-...
  • Page 58 1 Introduction to NJ-series Controllers NJ501- NJ301- NJ101- Item 5 4 3 12 11 10 90 Supported services Sysmac Studio connection Periph- eral USB Physical layer USB 2.0-compliant B-type connector port Transmission distance 5 m max. Number of ports Physical layer 10BASE-T/100BASE-TX Frame length 1,514 bytes max.
  • Page 59 1 Introduction to NJ-series Controllers NJ501- NJ301- NJ101- Item 5 4 3 12 11 10 90 Micro Embedded Device Server Pro- file Support profile/Model PLCopen Information Model Default Endpoint/Port opc.tcp://192.168.250.1:4840/ Maximum number of ses- sions (Client) Maximum number of Moni- 2,000 tored Items per server 0, 50, 100, 250, 500, 1,000, 2,000,...
  • Page 60 1 Introduction to NJ-series Controllers NJ501- NJ301- NJ101- Item 5 4 3 12 11 10 90 Communications standard IEC 61158 Type12 EtherCAT master specifications Class B (Feature Pack Motion Control compliant) Physical layer 100BASE-TX Modulation Baseband Baud rate 100 Mbps (100Base-TX) Duplex mode Auto Topology...
  • Page 61 1 Introduction to NJ-series Controllers *11 Data will be refreshed at the set interval, regardless of the number of nodes. *12 “pps” means packets per second, i.e., the number of communications packets that can be sent or received in one second. *13 As the EtherNet/IP port implements the IGMP client, unnecessary multi-cast packets can be filtered by using an Ethernet switch that supports IGMP Snoop- ing.
  • Page 62: Overall Operating Procedure For The Nj-Series Controller

    1 Introduction to NJ-series Controllers Overall Operating Procedure for the NJ-series Controller This section gives the overall operating procedure of the NJ-series Controllers and then describes it in more detail. 1-3-1 Overall Procedure The overall procedure to use an NJ-series Controller is given below. Step 1.
  • Page 63: Procedure Details

    1 Introduction to NJ-series Controllers 1-3-2 Procedure Details Step 1. Software Design Step Description Reference • External I/O devices and unit configuration Step 1-1 Section 3 Configuration • Refresh periods for external devices Units (page 3-1) Designing I/O and • Program contents Processing •...
  • Page 64 1 Introduction to NJ-series Controllers The following Controller Configurations and Setup and the Programming and Task Settings can be performed in either order. Step 2-1 Slave and Unit Configurations 1. Creating the slave configuration and 1) Creating the Slave EtherCAT Slave Set- NJ/NX-series CPU Unit Unit configuration either offline or and Unit Configura-...
  • Page 65 1 Introduction to NJ-series Controllers Step 2-3 Programming • Registering the variables used by more 1) Registering Vari- Global Variable Table Sysmac Studio Version 1 than one POU in the global variable ables Editor Operation Manual (Cat. No. table with Sysmac Studio W504) Local Variable Table •...
  • Page 66 1 Introduction to NJ-series Controllers Step 4. Wiring Step Description Reference • Connecting the built-in EtherCAT port 1. Connecting 4-4 Wiring (page 4-27) • Connecting the built-in EtherNet/IP port Ethernet Cable • Wiring I/O to EtherCAT slaves 2. Wiring I/O Operation manuals for Eth- •...
  • Page 67: System Configuration

    System Configuration This section describes the basic system configuration and devices used for NJ-series Controllers. 2-1 Basic System Configuration ........2-2 2-1-1 EtherCAT Network Configuration .
  • Page 68: Basic System Configuration

    2 System Configuration Basic System Configuration System Configuration An NJ-series Controller supports the following two types of configurations. (1) Basic Configurations The basic configurations include the CPU Unit and the Configuration Units that are controlled directly by the CPU Unit. There are two basic configurations. •...
  • Page 69 2 System Configuration CJ-series Unit Configuration CJ-series Configuration Units CPU Rack (I/O Control Unit) (Basic I/O Units, Special I/O Units, and CPU Bus Units) NJ-series Power Supply Unit NJ-series CPU Unit End Cover SD Memory Card Expansion Rack CJ-series Configuration Units (Basic I/O Units, Special NJ-series Power Supply Unit (I/O Interface Unit)
  • Page 70: Ethercat Network Configuration

    2 System Configuration 2-1-1 EtherCAT Network Configuration The EtherCAT network configuration consists of an NJ-series CPU Unit, an NJ-series Power Supply Unit, a CJ-series End Cover, and the EtherCAT slaves. You use the built-in EtherCAT master port on the NJ-series CPU Unit to connect EtherCAT slaves. For information on the system configuration of an EtherCAT network, refer to the NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (Cat.
  • Page 71: Cj-Series Unit Configuration

    2 System Configuration 2-1-2 CJ-series Unit Configuration The CJ-series Unit configuration consists of the CJ-series Units that are connected. It includes the CJ- series Units on the CPU Rack and Expansion Racks. CPU Rack The CPU Rack consists of an NJ-series CPU Unit, an NJ-series Power Supply Unit, CJ-series Configuration Units, and a CJ-series End Cover.
  • Page 72 2 System Configuration  Units NJ-series CPU Units Current consump- I/O capacity/Maxi- Data- con- tion Num- con- mum number of Pro- Memory base trol ber of trol eri- Configuration gram capacity con- Ser- Model motio Units (Maximum capa for vari- nec- vice con-...
  • Page 73 2 System Configuration Note A CJ-series Power Supply Unit cannot be used to supply power to an NJ-system CPU Rack or Expansion Rack. If you connect a CJ-series Power Supply Unit to a CPU Rack, an Incorrect Power Supply Unit Connected error will occur, and the CPU Unit will not operate.
  • Page 74 2 System Configuration Others Name Model Specifications DIN Track PFP-50N Track length: 50 cm, height: 7.3 mm PFP-100N Track length: 1 m, height: 7.3 mm PFP-100N2 Track length: 1 m, height: 16 mm PFP-M Stopper to prevent Units from moving on the track. Two each are provided with the CPU Unit and with an I/O Interface Unit.
  • Page 75 2 System Configuration Expansion Racks CJ-series Expansion Racks can be connected to the CPU Rack to expand the number of Units in the System beyond the CPU Rack. Up to 10 I/O Units can be mounted to each Expansion Rack and a total of 3 Expansion Racks can be connected.
  • Page 76 2 System Configuration  Maximum Number of Expansion Racks Expansion pattern Maximum number of Racks Remarks NJ-series CPU Rack plus 3 Racks The total length of I/O Connecting Cable CJ-series Expansion Racks between the CPU Rack and an Expansion Rack, and between all Expansion Racks, must be no more than 12 m.
  • Page 77 2 System Configuration End Cover Current con- sumption Model Specifications Weight 5 VDC 24 VDC CJ1W-TER01 The End Cover must be connected to the right end of the Included with the CPU Unit or CJ-series Expansion Rack. An End Cover Missing error Expansion Unit.
  • Page 78 2 System Configuration  Models of Configuration Units The Configuration Units with which the NJ-series CPU Unit can exchange data are classified into three groups. The number of Units that can be mounted depends on the type of Unit. Unit identifica- Number of Units Description...
  • Page 79 *2 The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 4-4-4 Wiring CJ-series Basic I/O Units with Connectors.), or use an OMRON Connector-Terminal Block Conversion Unit or I/O Relay Terminal (Refer to 4-4-5 Connecting to Connector-Terminal Block Conver- sion Units or I/O Relay Terminals.).
  • Page 80 *2 The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 4-4-4 Wiring CJ-series Basic I/O Units with Connectors.), or use an OMRON Connector-Terminal Block Conversion Unit or I/O Relay Terminal (Refer to 4-4-5 Connecting to Connector-Terminal Block Conver- sion Units or I/O Relay Terminals.).
  • Page 81 * The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 4-4-4 Wiring CJ-series Basic I/O Units with Connectors.), or use an OMRON Connector-Terminal Block Conversion Unit or I/O Relay Terminal (Refer to 4-4-5 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals.).
  • Page 82 2 System Configuration CJ-series Special I/O Units Num- Current con- sumption (A) Number of Words Type Name Specifications Model Unit No. words allocated in Weight moun allocated DM Area table Units Special I/O Analog Input 4 inputs, fully univer- CJ1W-AD04U 0 to 95 10 words 100 words...
  • Page 83 2 System Configuration Num- Current con- sumption (A) Number of Words Type Name Specifications Model Unit No. words allocated in Weight moun allocated DM Area table Units Special I/O CompoNet CompoNet remote I/O 0 to 94 20 words None 0.40 130 g max.
  • Page 84 2 System Configuration CJ-series CPU Bus Units Current con- Maximum Number of sumption (A) number of Type Name Specifications Model Unit No. words allo- Weight cated Units 5 VDC 24 VDC CPU Bus Serial Commu- Two RS-232C ports CJ1W-SCU22 0 to F 25 words 16 Units 160 g max.
  • Page 85: Connecting To The Sysmac Studio

    2 System Configuration Connecting to the Sysmac Studio Connect the NJ-series CPU Unit and the Sysmac Studio through USB or EtherNet/IP. Refer to 3-7-2 Connection for information on how to make the connection between the NJ-series CPU Unit and the Sysmac Studio. 2-19 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 86: Network Configuration

    8 9 10 11 12 13 14 15 CRT1 CRT1-OD16 OD16 CRT1 CRT1-OD16 OD16 CRT1 CRT1-OD16 OD16 REMOTE TERMINAL REMOTE TERMINAL REMOTE TERMINAL General-purpose components or OMRON components DeviceNet CompoNet slaves DeviceNet slaves 2-20 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 87 2 System Configuration Connection Connection method Sysmac Studio Use USB or the built-in EtherNet/IP port. Between Control- NJ-series Controller or CJ-series Use the built-in EtherNet/IP port or a port on an Eth- lers erNet/IP Unit. Devices Servo Drives, general-purpose Use the built-in EtherCAT port. slaves and Vision Systems Ethernet communications devices Use the built-in EtherNet/IP port or a port on an Eth-...
  • Page 88 2 System Configuration 2-22 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 89: Configuration Units

    Configuration Units This section describes the configuration devices in the CJ-series Unit configuration. 3-1 CPU Units ........... . 3-2 3-1-1 Models and Specifications .
  • Page 90: Cpu Units

    3 Configuration Units CPU Units 3-1-1 Models and Specifications Robot I/O capac- Data- Robot con- ity/Maximum base Pro- Memory Num- con- trol by Nume number of Con- con- Type of gram capacity ber of trol for rical Model figuration Units nec- Ser- Unit...
  • Page 91: Components And Functions

    3 Configuration Units 3-1-2 Components and Functions (10) (11) (12) (13) (14) (15) NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 92 3 Configuration Units Number Name Function Slider Holds the Units together. SD Memory Card connector Connects the SD Memory Card to the CPU Unit. CPU Unit operation indicators Shows the operation status of the CPU Unit. Refer to CPU Unit Operation Status Indicators on page 3-5. SD Memory Card power supply Turns OFF the power supply so that you can remove the SD Memory switch...
  • Page 93 3 Configuration Units CPU Unit Operation Status Indicators You can check the CPU Unit status with the indicators at the top of the front panel of the CPU Unit. The following table describes these indicators. Indicator Color Status Meaning Green The CPU Unit is in normal operation in RUN mode.
  • Page 94 3 Configuration Units Indicator Color Status Meaning SD PWR Green Power is being supplied to the SD Memory Card and the SD Memory Card can be used. Flashing Not lit The power supply for the SD Memory Card is stopped, an SD Memory Card is not mounted, or the file format of the mounted SD Memory Card is not supported.
  • Page 95 3 Configuration Units Built-in EtherNet/IP Port (Port 1) Indicators Indicator Color Status Contents NET RUN Green Normal startup status. Flashing Ethernet communications are in progress. • Tag data link connection establishment in progress. • IP address acquisition with BOOTP in progress. Not lit You cannot perform Ethernet communications.
  • Page 96 3 Configuration Units Built-in EtherCAT Port (Port 2) Indicators Indicator Color Status Description NET RUN Green EtherCAT communications are in progress. • Inputs and outputs for I/O data are in operation. Flashing EtherCAT communications are being established. This indicator shows either of the following conditions. •...
  • Page 97 Shows the lot number and the serial number of the CPU Unit. serial number DDMYY: Lot number, : For use by OMRON, xxxx: Serial number M is 1 to 9 for January to September, X for October, Y for November, and Z for December.
  • Page 98: Sd Memory Cards

    3 Configuration Units SD Memory Cards 3-2-1 Models and Specifications Refer to Specifications of Supported SD Memory Cards, Folders, and Files in the NJ/NX-series CPU Unit Software User’s Manual (Cat. No. W501) for details. 3-2-2 Purpose You can use the SD Memory Card for the following applications. •...
  • Page 99: Installing And Removing

    • The service life may be extremely short if a non-OMRON SD Memory Card is used. Also, operation may be affected due to deterioration in writing performance. • If you use an OMRON SD Memory Card, the end of the life of the SD Memory Card can be detected in the following ways.
  • Page 100 3 Configuration Units Installing the SD Memory Card Pull the left side of the SD Memory Card cover forward and remove from the Unit. Insert the SD Memory Card with the label facing to the left. (Insert the SD Memory Card with the label facing the triangle on the CPU Unit.) Model number label Push the SD Memory Card securely into the compartment.
  • Page 101 3 Configuration Units Press the SD Memory Card after the SD BUSY indicator is no longer lit. The SD Memory Card will be ejected from the compartment. Pull out the SD Memory Card. Close the Memory Card cover when an SD Memory Card is not being used. 3-13 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 102: Power Supply Units

    3 Configuration Units Power Supply Units 3-3-1 Models and Specifications NJ-series Power Supply Units Use an NJ-series Power Supply Unit to supply power to an NJ-series CPU Rack or Expansion Rack. Precautions for Correct Use Precautions for Correct Use • Do not use the Power Supply Units in the system beyond the rated supply capacity range given in the following specifications.
  • Page 103 3 Configuration Units Item Specifications Shock resistance 147 m/s 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s ) (according to IEC 60068-2-27) Ambient operating 0 to 55°C temperature Ambient operating 10% to 90% (with no condensation) humidity Atmosphere Must be free from corrosive gases.
  • Page 104: Components And Functions

    3 Configuration Units 3-3-2 Components and Functions NJ-PA3001 POWER Indicator (PWR LED) AC input Connector RUN output NJ-PD3001 POWER Indicator (PWR LED) (DC input) Connector (DC input) RUN output AC Input Supply 100 to 240 VAC (allowable: 85 to 264 VAC). The NJ-PA3001 has a wide input range, so it does not have voltage switching terminals.
  • Page 105: Selecting A Power Supply Unit

    3 Configuration Units RUN Output (NJ-PA3001/-PD3001) The internal contacts for the RUN output turn ON when the CPU Unit is in RUN status. The following operation occurs. Status Operation In operation (RUN mode). The CPU Unit is starting (until entering the operating status that is specified in the Startup Mode setting).
  • Page 106 3 Configuration Units 2 Be sure to include the power required by the I/O Interface Unit when calculating current/power consump- tion in an Expansion Rack. Output current Output Model 5-VDC CPU 5-VDC Expan- capacity 24 VDC sion Rack Rack NJ-PA3001 6.0 A 6.0 A 1.0 A...
  • Page 107 3 Configuration Units Additional Information Rack Current Consumption and Width Display The width, current consumption, and power consumption for each Rack are displayed on the right side of the CPU/Expansion Racks Tab Page in the Controller Configurations and Setup of the Sysmac Studio.
  • Page 108 3 Configuration Units Calculating Power Consumption The ambient operating temperature at the control panel where an NJ-series Controller is mounted must be no higher than 55°C. This section describes how to calculate the power consumption of a CPU Rack or Expansion Rack for use in the thermal design of the control panel.
  • Page 109 3 Configuration Units Calculation Examples These examples show how to calculate the power consumption (W) for the following system. CPU Rack Power Supply Unit CJ1W-MAD42 × 2 NJ501-1500 Special I/O Units CPU Unit CJ1W-ID261 × 2 CJ1W-OD261 × 2 Basic I/O Units Units Model Quantity...
  • Page 110: Cj-Series Basic I/O Units

    3 Configuration Units CJ-series Basic I/O Units 3-4-1 Models and Specifications  Basic Input Units Type of Unit Name Specifications Model Page Basic Input DC Input Units Terminal block, 12 to 24 VDC 8 inputs CJ1W-ID201 Units Terminal block, 24 VDC 16 inputs CJ1W-ID211 CJ1W-ID212...
  • Page 111: Part Names And Functions

    3 Configuration Units  Basic Mixed I/O Units Type of Name Specifications Model Page Unit Mixed I/O 24-VDC Sinking Fujitsu connector 16 inputs CJ1W-MD231 A-41 Units Inputs/Transis- output Inputs: 24 VDC 16 outputs tor Output Units Outputs: 12 to 24 VDC, 0.5 A MIL connector CJ1W-MD233 A-43...
  • Page 112 3 Configuration Units  Thirty-two-point Units with 40-pin Fujitsu Connector or MIL Connector Model number Indicator Switch ID 2 3 1 ID 2 3 2 I/O indicators Changes the 16 I/O displayed on the I/O indicators. I/O wiring MIL connector connector Fujitsu connector (40-pin ×...
  • Page 113 3 Configuration Units Quick-response Inputs When you want to receive pulses that are shorter than the task period, use the CJ1W-IDP01 Quick- response Input Unit. The quick-response inputs can receive pulses with a pulse width (ON time) of 0.05 ms for the CJ1W- IDP01 Quick-response Input Unit.
  • Page 114: B7A Interface Ports

    3 Configuration Units B7A Interface Ports 3-5-1 Overview The B7A is a 1:1 transmission path that does not require a master. A total of 16 signals are transmitted using a two-conductor or three-conductor VCTF cable (maximum length: 500 m). The CJ1W-B7A B7A Interface Unit is a CJ-series Basic I/O Unit that exchanges up to 64 points of I/O data mainly with B7A Link Terminals using a B7A transmission path.
  • Page 115: B7A Communications Specifications

    , 2 conductors (power supply on both sides (separate power supplies)) *1 We recommend OMRON S8-series Power Supply Units for the external power supplies. *2 The capacity of the external supply current does not include the capacity required by the B7A Link Terminal.
  • Page 116: Common Specifications

    3 Configuration Units 3-5-5 Common Specifications Item Specifications Applicable Controllers NJ Series Unit classification CJ-series Basic I/O Unit Transmission delay Standard (19.2 ms typical) or high-speed (3 ms typical), switchable (Switchable by using the setting switch on the front panel. Settings are read when power is turned ON or Unit is restarted.) Factory setting: Standard (19.2 ms typical) Note A transmission error will occur if B7A Link Terminals with different transmis-...
  • Page 117: Parts And Names

    3 Configuration Units 3-5-7 Parts and Names B7A14 ERR1 Indicators ERR2 ERR3 ERR4 Transmission 19ms delay switch Connection terminals (Screwless connectors) Indicators  CJ1W-B7A14 B 7A 14 R U N E R R 1 E R R 2 E R R 3 E R R 4 Indicator Name...
  • Page 118 3 Configuration Units Indicator Name Color Status Condition ERR3 Port 3 A transmission error has occurred at transmis- port 3 of the B7A Unit. sion error Not lit The Unit is operating normally. ERR4 Port 4 A transmission error has occurred at transmis- port 4 of the B7A Unit.
  • Page 119: Transmission Error Processing

    3 Configuration Units 3-5-8 Transmission Error Processing B7A Interface Input Ports The B7A Interface Unit detects transmission errors at the input ports. When a transmission error is detected at an input port, the corresponding indicator and Transmission Error Flag turn ON. ...
  • Page 120: Cj-Series I/O Control Units And I/O Interface Units

    3 Configuration Units CJ-series I/O Control Units and I/O Interface Units An I/O Control Unit and I/O Interface Units are used to connect Expansion Racks to the NJ-series CPU Rack to expand the system. 3-6-1 Models and Specifications  I/O Control Unit Model Specifications CJ1W-IC101...
  • Page 121: Sysmac Studio

    3 Configuration Units Sysmac Studio The Sysmac Studio is a Support Software package that provides an integrated development environ- ment to design, program, debug, and maintain SYSMAC NJ-series Controllers. 3-7-1 Model Numbers The model numbers of the Sysmac Studio Standard Edition are given in the following table. The model numbers are different for the media and licenses.
  • Page 122: Connection

    3 Configuration Units 3-7-2 Connection With an NJ-series CPU Unit, you can connect the Sysmac Studio online in the following ways. Configuration  Connecting by USB • Direct Connection • Connection to CPU Unit on EtherNet/IP with USB Sysmac Studio Sysmac Studio EtherNet/IP The connection device does not...
  • Page 123 3 Configuration Units Additional Information The Sysmac Studio cannot connect online to an NJ-series CPU Unit in the following type of con- figuration. • If the built-in EtherNet/IP port is not used, you cannot connect to an NJ-series CPU Unit on an EtherNet/IP network.
  • Page 124 3 Configuration Units 3-36 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 125: Installation And Wiring

    Installation and Wiring This section describes how to install and wire the CPU Unit and Configuration Units. 4-1 Processing at Power ON and Power OFF ......4-2 4-1-1 Power ON Operation .
  • Page 126: Processing At Power On And Power Off

    4 Installation and Wiring Processing at Power ON and Power WARNING • Do not touch the terminal section while power is ON. Electrical shock may occur. • Do not disassemble any of the Units. Particularly the Power Supply Units con- tain parts with high voltages when power is ON or immediately after power is turned OFF.
  • Page 127 4 Installation and Wiring Additional Information The CPU Unit internally performs initialization when the power to the Controller is turned ON. The following processing is performed for initialization. Process Description Self diagnosis at startup Operation is monitored for the following errors: Power Supply Error, CPU Unit Reset, CPU Unit Watchdog Timer Error, and Incorrect Power Supply Unit Connected.
  • Page 128: Power Off Operation

    4 Installation and Wiring 4-1-2 Power OFF Operation WARNING The NJ-series Controller continues normal operation for a specific period of time even when a momentary power interruption occurs. The Controller may therefore receive incorrect signals from external devices that are affected by the momentary power interruption.
  • Page 129 4 Installation and Wiring Power interruption Power interruption System stops. confirmed. detected. (CPU Unit stops.) Voltage recovery Voltage drop disabled. AC: 85 V max. DC: 19.2 V max. Executing user program Processing after power interruption is confirmed System reset Power interruption Power interruption detection delay time: detection time...
  • Page 130: Resetting The Controller From The Sysmac Studio

    4 Installation and Wiring Processing after Power Interruption Is Confirmed After a power interruption is confirmed, the CPU Unit performs the following processing and then stops. Item Description I/O refresh Load outputs are turned OFF. Tag data links stop. SD Memory Card Any writing is interrupted, files are closed, and the Card is access in progress unmounted.
  • Page 131: Fail-Safe Circuits

    4 Installation and Wiring Fail-safe Circuits WARNING Provide safety measures in external circuits, including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the CPU Unit, other Units, or slaves or due to other external factors affecting opera- tion.
  • Page 132: Order Of Powering Up The Controller And Controlled System

    4 Installation and Wiring 4-2-1 Order of Powering Up the Controller and Controlled System Outputs from Units, such as DC Output Units, may malfunction momentarily when the power to the Controller is turned ON. This may cause problems in the system if the Controller power supply is turned ON after the controlled system's power supply.
  • Page 133 4 Installation and Wiring Interlock Circuits When the Controller controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown in the following example to prevent both the forward and reverse outputs from turning ON at the same time if required by the application. Interlock circuit ON_MC1 Motor clockwise...
  • Page 134: Mounting Units

    4 Installation and Wiring Mounting Units Precautions for Correct Use Precautions for Correct Use • Follow the instructions in this manual to correctly perform installation. • Do not operate or store the Controller in the following locations. Doing so may cause operation to stop or incorrect operation.
  • Page 135 4 Installation and Wiring Control panel NJ-series Controller Louver  Accessibility for Operation and Maintenance • To ensure safe access for operation and maintenance, separate the Controller as much as possi- ble from high-voltage equipment and power machinery. • It will be easy to operate the Controller if it is mounted at a height of 1.0 to 1.6 m above the floor. ...
  • Page 136 4 Installation and Wiring Mounting with the DIN Track on the Bottom Mounting with the DIN Track on the Top DIN Track DIN Track Mounting with the DIN Track Installed Vertically Mounting with the Rack Upside down Installation Method in Control Panels An NJ-series Controller must be mounted inside a control panel on DIN Track.
  • Page 137 4 Installation and Wiring • Wiring Ducts Whenever possible, route I/O wiring through wiring ducts or raceways. Install mounting bracket so that it is easy to fish wire from the I/O Units through the duct. It is handy to have the duct at the same height as the Racks.
  • Page 138 4 Installation and Wiring  Routing Wiring Ducts Install the wiring ducts at least 20 mm away from the tops of the Racks and any other objects (e.g., ceiling, wiring ducts, structural supports, devices, etc.) to provide enough space for air circulation and replacement of Units.
  • Page 139: Connecting Controller Components

    4 Installation and Wiring 4-3-2 Connecting Controller Components The Units that make up an NJ-series Controller can be connected simply by pressing the Units together and locking the sliders by moving them toward the back of the Units. The End Cover is connected in the same way to the Unit on the far right side of the Controller.
  • Page 140 4 Installation and Wiring Attach the End Cover to the Unit on the far right side of the Rack. CPU Rack (I/O Control Unit) *1 Power Supply CPU Unit End Cover Unit Configuration Units (10 max.) (included with CPU Unit) *1: Connect the I/O Control Unit directly to the CPU Unit to enable connecting Expansion Racks.
  • Page 141: Din Track Installation

    4 Installation and Wiring 4-3-3 DIN Track Installation Use the following procedure to install an NJ-series Controller on DIN Track. Release the pins on the backs of the NJ-series Units. Release DIN Track mounting pins Fit the back of the Controller onto the DIN Track by inserting the top of the track and then press- ing in at the bottom of the Controller, as shown below.
  • Page 142 4 Installation and Wiring Install a DIN Track End Plate on each end of the Controller. To install an End Plate, hook the bot- tom on the bottom of the track, rotate the Plate to hook the top of the Plate on the top of the track, and then tighten the screw to lock the Plate in place.
  • Page 143 4 Installation and Wiring DIN Track and Accessories Use the DIN Track and DIN Track End Plates shown below. Secure each DIN Track inside a control panel with at least three screws. • DIN Track Model numbers: PFP-50N (50 cm), PFP-100N (100 cm), PFP-100N2 (100 cm) Secure the DIN Track to the control panel using M4 screws separated by 210 mm (6 holes) or less and using at least 3 screws.
  • Page 144: Connecting Cj-Series Expansion Racks

    4 Installation and Wiring 4-3-4 Connecting CJ-series Expansion Racks CS/CJ-series I/O Connecting Cables are used to connect the NJ-series CPU Rack and CJ-series Expansion Racks.  CS/CJ-series I/O Connecting Cables • These connectors are equipped with easy-lock connectors. • Use them to connect the CPU Rack to an Expansion Rack or to connect two Expansion Racks. Model number Cable length CS1W-CN313...
  • Page 145 4 Installation and Wiring I/O Control Unit CPU Rack Easy-lock connector I/O Interface Unit I/O Connecting Cable Expansion Rack I/O Interface Unit Easy-lock connector Expansion Rack • The top and bottom of the connector are different. Be sure the connector is facing the correct direction before connecting it.
  • Page 146: Assembled Appearance And Dimensions

    4 Installation and Wiring Precautions for Correct Use Precautions for Correct Use • When using an I/O Connecting Cable with a locking connector, be sure that the connector is firmly locked in place before using it. • Always turn OFF the power supply to the Controller before connecting a cable. •...
  • Page 147 4 Installation and Wiring Dimensions Power Supply Unit Model Unit width (mm) NJ-PA3001 NJ-PD3001 CPU Unit Model Unit width (mm) NJ501-1500 NJ501-1400 NJ501-1300 NJ501-R500 NJ501-R400 NJ501-R300 NJ501-4500 NJ501-4400 NJ501-4300 NJ501-4310 NJ501-1520 NJ501-1420 NJ501-1320 NJ501-4320 NJ301-1200 NJ301-1100 NJ101-1000 NJ101-9000 NJ101-1020 NJ101-9020 End Cover Model Unit width (mm)
  • Page 148 4 Installation and Wiring 31-mm-wide Units Name Model Unit width (mm) I/O Interface Unit CJ1W-II101 8-point and 16-point Basic I/O Units CJ1W-ID201 CJ1W-ID211/212 CJ1W-IA111/201 CJ1W-OD20 CJ1W-OD211/212/213 CJ1W-OC201/211 CJ1W-OA201 32-point Basic I/O Units CJ1W-MD231/232/233 64-point Basic I/O Units CJ1W-ID261 CJ1W-OD261 CJ1W-MD261 CJ1W-ID262 CJ1W-OD262/263 CJ1W-MD263/563...
  • Page 149 4 Installation and Wiring  Design Example for Width W Power Supply Unit CPU Unit Configuration Units Power Supply Unit: NJ-PA3001 (70 mm) CPU Unit: NJ501-1500 (90 mm) Basic I/O Units: CJ1W-ID231 (20 mm) × 2 Special I/O Units: CJ1W-AD081-V1 (31 mm) × 4 CPU Bus Unit: CJ1W-EIP21 (31 mm) ×...
  • Page 150 4 Installation and Wiring Installation Height With a height of 90.0 mm, the CPU Unit is the highest component in an NJ-series CPU Rack. It is also higher than any Units on an Expansion Rack. When a cable is connected (such as a connecting cable to Support Software), however, even greater height is required.
  • Page 151: Wiring

    4 Installation and Wiring Wiring WARNING • Do not input a voltage or current that exceeds the specified range into a Unit or slave. If a voltage or current that is outside the specified range is input, the Unit or slave may fail or a fire may occur. CAUTION •...
  • Page 152 4 Installation and Wiring  AC Power Source • Supply 100 to 240 VAC. • Keep voltage fluctuations within the specified range: Supply voltage Allowable voltage fluctuations 100 to 240 VAC 85 to 264 VAC • If one power supply phase of the equipment is grounded, connect the grounded phase side to the L2/N terminal.
  • Page 153 4 Installation and Wiring  Crimp Terminals The terminals on the Power Supply Unit are M4, self-raising terminals with screws. Precautions for Safe Use • Use crimp terminals for wiring. • Do not connect bare stranded wires directly to terminals. •...
  • Page 154 4 Installation and Wiring  DC Power Source Supply 24 VDC. Keep voltage fluctuations within the specified range. Model Allowable voltage fluctuation range ± NJ-PD3001 19.2 to 28.8 VDC (24 VDC 20%)  Power Supply Capacity The maximum power consumption is 50 W (NJ-PD3001) per Rack. When you select the power supply, consider that surge current will flow when the power is turned Refer to 3-3-1 Models and Specifications for information on surge current specifications.
  • Page 155 4 Installation and Wiring Grounding LG (Noise-filter neutral terminal) GR (Ground terminal) Termi- Grounding Symbol Function type name Functional Functional grounding is done to protect device and system func- Grounding tions, including prevention of noise from external sources, or pre- vention of noise from devices or equipment that could have harmful effects on other devices or equipment.
  • Page 156: Wiring The Built-In Ethercat Port

    4 Installation and Wiring • Ground to 100 Ω or less, and if possible use a separate ground from those of other devices. (Refer to figure (a) in the diagram below.) • If using an independent ground is not possible, then use a common ground as shown in figure (b). Connect to the ground pole of the other device.
  • Page 157: Wiring Cj-Series Basic I/O Units With Terminal Blocks

    4 Installation and Wiring 4-4-3 Wiring CJ-series Basic I/O Units with Terminal Blocks Precautions for Wiring I/O Units  I/O Unit Specifications Double-check the specifications for the I/O Units. Be particularly careful of the following to prevent failure, damage, and fires. •...
  • Page 158: Wiring Cj-Series Basic I/O Units With Connectors

    Depending on the connector, the following methods are used to connect these Units to external I/O devices. • Use an OMRON Connecting Cable (equipped with a special connector) to connect to a Terminal Block or Relay Terminal. • Use a special connector and make your own cable.
  • Page 159 Connecting to a Connector-Terminal Block Conversion Unit or I/O Relay Terminal For details on using OMRON Connecting Cables equipped with special connectors to connect Basic I/O Units with connectors to OMRON Connector-Terminal Block Conversion Units or I/O Relay Termi- nals, refer to A-2-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals.
  • Page 160 4 Installation and Wiring Applicable Cable-side Connectors Connection Pins OMRON set Fujitsu parts Crimped C500-CE405 Socket: FCN-363J040 Connector cover: FCN-360C040-J2 Contacts: FCN-363J-AU C500-CE242 Socket: FCN-363J024 Connector cover: FCN-360C024-J2 Contacts: FCN-363J-AU Pressure-welded C500-CE403 FCN-367J040-AU/F C500-CE243 FCN-367J024-AU/F CJ-series 32- and 64-point Basic I/O Units with MIL Connectors...
  • Page 161 4 Installation and Wiring Cover the Unit while wiring to prevent wire clippings from entering the Unit. If there is a dustproof label on the top of the Unit, do not remote it before you wire the Unit. (Remove the label or other covering after wiring has been completed to allow air circulation needed for cooling.) After wiring Before wiring...
  • Page 162 4 Installation and Wiring Assemble the connector (purchased separately). Small screws (3) Connector cover Small screws (2) Socket Connector lock screws Cable bracket Nuts (3) Nuts (2) Insert the wired connector. ID261 10 11 12 13 14 15 10 11 12 13 14 15 Connector Basic I/O Unit...
  • Page 163: Connecting To Connector-Terminal Block Conversion Units Or I/O Relay Terminals

    Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals OMRON Connecting Cable can be used to connect Basic I/O Units with Connectors to OMRON Con- nector-Terminal Block Conversion Units or to OMRON I/O Relay Terminals. For details, refer to A-2-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals.
  • Page 164: Connecting I/O Devices

    4 Installation and Wiring 4-4-6 Connecting I/O Devices Input Devices Use the following information for reference when selecting or connecting input devices.  DC Input Units The following types of DC input devices can be connected. Contact output DC Input Unit Two-wire DC output DC Input Unit Sensor...
  • Page 165 4 Installation and Wiring  AC Input Units Contact output AC Input Unit AC Switching Proximity switch AC Input Unit main circuit Precautions for Correct Use Precautions for Correct Use When using a reed switch as the input contact for an AC Input Unit, use a switch with an allow- able current of 1 A or greater.
  • Page 166 In this example, the sensor's power supply voltage is used as the input to SensorVcc. A timer delay (100 ms for an OMRON Proximity Sensor) is added to the user program to wait for sensor operation to stabilize. After the timer times out and then the SensorOK input changes to TRUE, a sensor input to the Sensorln input causes InData to change to TRUE.
  • Page 167: Wiring The Built-In Ethercat Port

    4 Installation and Wiring Output Wiring Precautions  Output Short-circuit Protection If a load connected to the output terminals is short-circuited, output components and the printed cir- cuit boards may be damaged. To guard against this, incorporate a fuse in the external circuit. Use a fuse with a capacity of about twice the rated output.
  • Page 168: Wiring B7A Interface Units

    4 Installation and Wiring 4-4-8 Wiring B7A Interface Units Terminal Arrangement Terminal Name Function Word Appearance Port 1 power supply: V1 Connect to the + terminal of the B7A Link Terminal to Connector with be connected to port 1 (only when using a common clamps power supply).
  • Page 169 4 Installation and Wiring Preparing and Connecting Cables Use the following procedure to prepare and connect the cables. Precautions for Correct Use Precautions for Correct Use Always turn OFF the Unit's power supply and communications power supply before attaching or removing connectors.
  • Page 170 4 Installation and Wiring Precautions for Correct Use Precautions for Correct Use Always use the specified crimp tool to attach the crimp terminals. If a crimp tool is not used, the cable will not be crimped properly, which may cause the cable to become detached from the ter- minal.
  • Page 171 4 Installation and Wiring Additional Information To remove the signal lines from the connector, press down on the orange tab while pulling out the signal line, as shown in the following diagram. Small, flat- blade screwdriver Precautions for Correct Use Precautions for Correct Use To remove the connector from the Unit, fully unscrew the set screws from both sides of the con- nector, and then remove the connector.
  • Page 172 4 Installation and Wiring Connection Diagrams Precautions for Correct Use Precautions for Correct Use • Confirm that terminals are connected correctly. If connections are incorrect, the internal com- ponents of the B7A Interface Unit and B7A Link Terminal may be damaged. •...
  • Page 173 4 Installation and Wiring  High-speed Mode Note If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a common or separate power supplies are used. (Use VCTF cable of 0.75 mm or higher.) •...
  • Page 174: Control Panel Installation

    4 Installation and Wiring Control Panel Installation To ensure system reliability and safety, the system must be designed and configured according to the installation environment (temperature, humidity, vibration, shock, corrosive gases, overcurrent, noise, etc.). 4-5-1 Temperature Panels have been reduced in size due to space-saving and miniaturization in devices and systems, and the temperature inside the panel may be at least 10 to 15°C higher than outside the panel.
  • Page 175 4 Installation and Wiring  Forced Air Circulation (by Fan in Closed Panel) Controller Controller Forced Air Circulation  Room Cooling (Cooling the Entire Room Where the Control Panel Is Located) Cooler Control panel Room Cooling Low Temperatures The Controller may not start normally if the temperature is below 0°C when the power is turned ON. Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures such as installing a low-capacity space heater in the panel.
  • Page 176: Humidity

    4 Installation and Wiring 4-5-2 Humidity Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to short- circuiting. When there is a possibility of this occurring, take measures against condensation, such as leaving the Controller power ON at night or installing a heater in the control panel to keep it warmer. Control panel Moisture absorber Controller...
  • Page 177: Electrical Environment

    4 Installation and Wiring 4-5-5 Electrical Environment When installing or wiring devices, make sure that there will be no danger to people and that noise will not interfere with electrical signals. Controller Installation Location Install the Controller as far away as possible from high-voltage (600 V or higher) and power devices to ensure safe operation and maintenance.
  • Page 178 4 Installation and Wiring Wire Layout for the Power Supply System Observe the following points when wiring the power supply system. • Separate the Controller power supply from the I/O device power supply and install a noise filter near the Controller power supply feed section. •...
  • Page 179 4 Installation and Wiring • Wire the lines so that common impedance does not occur. Such wiring will increase the number of wires, so use common return circuits. Use thick wires with sufficient allowance for the return circuits, and bundle them with lines of the same signal level. •...
  • Page 180 4 Installation and Wiring • To avoid overheating the conduits when using conduits for wiring, do not place wires for a single circuit in separate conduits. Power supply Load Incorrect Power supply Load Correct Power supply Load Correct Parallel Wiring (Single Phase) •...
  • Page 181: Grounding

    4 Installation and Wiring 4-5-6 Grounding This section describes the earthing methods and precautions. Refer to 4-4-1 Power Supply Wiring on page 4-27 for details on the grounding of the Controller. Considerations for Earthing Methods Local potential fluctuations due to lightning or noise occurred by power devices will cause potential fluc- tuations between ground terminals of devices.
  • Page 182 4 Installation and Wiring Each of these earthing methods is given below.  Equipotential Bonding System Equipotential bonding is an earthing method in which steel frames and building structures, metal ducts and pipes, and metal structures in floors are connected together and make connections to the earth trunk line to achieve a uniform potential everywhere across the entire building.
  • Page 183 4 Installation and Wiring Control panel A device that could be a noise source Other device NJ-series CPU Units 10 m min. b) Connecting devices and noise sources to a common earth electrode This is an earthing method to connect the device that is connected with a communications cable, other devices, and a device that could be a noise source, to a common earth electrode.
  • Page 184 4 Installation and Wiring Precautions for Grounding  General Precautions • To prevent electrical shock, do not connect devices to ground poles (or steel frames) with non- equalized potential to which multiple devices are connected. • Use a ground pole as close to the Controller as possible and keep the ground line as short as pos- sible.
  • Page 185 4 Installation and Wiring  Grounding for AC Power Supply Units When wiring to an AC Power Supply Unit, if one power supply phase of the equipment is grounded, always connect the grounded phase to the L2/N terminal. L2/N 4-61 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 186 4 Installation and Wiring 4-62 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 187: Troubleshooting

    Troubleshooting This section describes the overview of methods for checking errors. 5-1 Overview of Troubleshooting ........5-2 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 188: Overview Of Troubleshooting

    5 Troubleshooting Overview of Troubleshooting You manage all of the errors that occur on the NJ-series Controller as events. This allows you to see what errors have occurred and find corrections for them with the same methods for the entire range of errors that is managed (i.e., CPU Unit, NX-series Slave Terminals, EtherCAT slaves, and CJ-series Units).
  • Page 189: Inspection And Maintenance

    Inspection and Maintenance This section describes the required inspections and maintenance. It also describes the service lives and replacement procedures for the Battery and Power Supply Units. 6-1 Periodic Maintenance and Inspection ......6-2 6-1-1 Periodic Inspection .
  • Page 190: Periodic Maintenance And Inspection

    6 Inspection and Maintenance Periodic Maintenance and Inspection Daily or periodic inspections are required in order to maintain the Controller's functions in peak operat- ing condition. 6-1-1 Periodic Inspection Although the major components in NJ-series Controllers have an extremely long life time, they can deteriorate under improper environmental conditions.
  • Page 191: Unit Replacement Precautions

    • If you return a faulty Unit for repair, describe the problem in as much detail as possible, enclose this description with the Unit, and return the Unit to your OMRON representative. • For poor contact, take a clean cotton cloth, soak the cloth in industrial alcohol, and carefully wipe the contacts clean.
  • Page 192: Replacing The Battery

    6 Inspection and Maintenance Replacing the Battery The Battery in the NJ-series CPU Unit must be replaced periodically as preventative maintenance. (The Battery is a backup power supply for the CPU Unit's internal clock and the variables that are retained during power interruptions.) This section describes how to replace the Battery.
  • Page 193 6 Inspection and Maintenance Low Battery Indicators If the Controller Setup has been set to detect a low-battery error, the ERROR indicator on the front of the CPU Unit will flash when the battery is nearly discharged. If the ERROR indicator flashes, connect the Sysmac Studio, and then check the CPU Unit's Battery connection if the Sysmac Studio shows a Low Battery Voltage, Battery-backup Memory Check Error, or Real-Time Clock Stopped event.
  • Page 194 6 Inspection and Maintenance Replacement Procedure Use the following procedure to replace the battery when the previous battery has become completely discharged. Precautions for Safe Use We recommend replacing the battery with the power OFF to prevent the CPU Unit's sensitive internal components from being damaged by static electricity.
  • Page 195: Operation Without A Battery

    6 Inspection and Maintenance Additional Information The Low Battery Voltage event is cleared automatically the next time the Controller is turned ON after replacing the Battery. 6-2-2 Operation without a Battery NJ-series CPU Units do not support a battery-free operation function such as CJ-series CPU Units. If a Battery is not connected or the Battery voltage is too low, the following operation occurs.
  • Page 196 6 Inspection and Maintenance NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 197: Appendices

    Appendices The appendices provide the specifications of the Basic I/O Units, Unit dimensions, load short-circuit protection detection, line disconnection detection, and measures for EMC Directives. A-1 Specifications ..........A-2 A-2 Specifications of Basic I/O Units .
  • Page 198: Specifications

    EU Directives, NK, LR and KC *1 This is the value when the power ON time rate is 0% (power OFF). *2 Refer to the OMRON website (http://www.ia.omron.com/) or contact your OMRON representative for the most recent applicable standards for each model.
  • Page 199: Specifications Of Basic I/O Units

    Appendices Specifications of Basic I/O Units A-2-1 Overview of Units Basic I/O Units  Basic Input Units Type of Unit Name Input specifications Model Page Basic Input DC Input Units Terminal block, 12 to 24 VDC 8 inputs CJ1W-ID201 Units Terminal block, 24 VDC, 16 inputs CJ1W-ID211...
  • Page 200 Appendices  Basic Mixed I/O Units Type of Name I/O specifications Model Page Unit Basic I/O 24-VDC Sinking Fujitsu connector 16 inputs CJ1W-MD231 A-41 Units Inputs/Transis- output Inputs: 24 VDC 16 outputs tor Output Units Outputs: 12 to 24 VDC, 0.5 A MIL connector CJ1W-MD233 A-43...
  • Page 201: Basic I/O Units

    Appendices A-2-2 Basic I/O Units Basic Input Units with Terminal Blocks  CJ1W-ID201 DC Input Unit (12 to 24-VDC, 8 Points) Name 8-point DC Input Unit with Terminal Block Model CJ1W-ID201 Rated Input Voltage 12 to 24 VDC Allowable Input Voltage Range 10.2 to 26.4 VDC Input Impedance 2.4 kΩ...
  • Page 202 Appendices  CJ1W-ID211 DC Input Unit (24 VDC, 16 Points) Name 16-point DC Input Unit with Terminal Block Model CJ1W-ID211 Rated Input Voltage 24 VDC Allowable Input Voltage 20.4 to 26.4 VDC Range Input Impedance 3.3 kΩ Input Current 7 mA typical (at 24 VDC) ON Voltage/ON Current 14.4 VDC min./3 mA min.
  • Page 203 Appendices  CJ1W-ID212 DC Input Unit (24 VDC, 16 Points) Name 16-point DC Input Unit with Terminal Block Model CJ1W-ID212 Rated Input Voltage 24 VDC Allowable Input Voltage Range 20.4 to 26.4 VDC Input Impedance 3.3 kΩ Input Current 7 mA typical (at 24 VDC) ON Voltage/ON Current 14.4 VDC min./3 mA min.
  • Page 204 Appendices  CJ1W-ID231 DC Input Unit (24 VDC, 32 Points) Name 32-point DC Input Unit with Fujitsu Connector Model CJ1W-ID231 Rated Input Voltage 24 VDC Allowable Input Voltage 20.4 to 26.4 VDC Range Input Impedance 5.6 kΩ Input Current 4.1 mA typical (at 24 VDC) ON Voltage/ON Current 19.0 VDC min./3 mA min.
  • Page 205 Appendices * The ON response time will be 20 μs maximum and OFF response time will be 400 μs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. •...
  • Page 206 Appendices Allocated Signal Signal Connec- Allocated CIO word name name tor pin CIO word 24 VDC COM1 COM1 Jxx_Ch2_In15 Jxx_Ch2_In07 Jxx_Ch2_In14 Jxx_Ch2_In06 Jxx_Ch2_In13 Jxx_Ch2_In05 Jxx_Ch2_In12 Jxx_Ch2_In04 Wd m+1 Wd m+1 Jxx_Ch2_In11 Jxx_Ch2_In03 Jxx_Ch2_In10 Jxx_Ch2_In02 Jxx_Ch2_In09 Jxx_Ch2_In01 Jxx_Ch2_In08 Jxx_Ch2_In00 External connection and terminal-device variable COM0 COM0...
  • Page 207 Appendices Number of Simultaneously ON Points vs. Allocated Signal Ambient Temperature Characteristic CIO word name 5.6 kW 32 points at 48°C Input voltage: 32 points at 40°C Jxx_Ch1_In00 24 VDC Wd m Input voltage: Jxx_Ch1_In15 26.4 VDC Connector 12 points/common row A at 55°C COM0...
  • Page 208 Appendices ON Response Time 8.0 ms max. (Can be set to between 0 and 32 ms in the Unit Information settings.) OFF Response Time 8.0 ms max. (Can be set to between 0 and 32 ms in the Unit Information settings.) Number of Circuits 64 (16 points/common, 4 circuits) Number of Simulta-...
  • Page 209 Appendices  CJ1W-ID262 DC Input Unit (24 VDC, 64 Points) Name 64-point DC Input Unit with MIL Connector Model CJ1W-ID262 Rated Input Voltage 24 VDC Allowable Input Volt- 20.4 to 26.4 VDC age Range Input Impedance 5.6 kΩ Input Current 4.1 mA typical (at 24 VDC) ON Voltage/ON Cur- 19.0 VDC min./3 mA min.
  • Page 210 Appendices Allocated Allocated Allocated Signal Connec- Signal Signal Allocated Signal Connec- CIO word CIO word CIO word name tor pin name name name CIO word tor pin 24 VDC Jxx_Ch1_In00 Jxx_Ch1_In08 Jxx_Ch1_In01 Jxx_Ch1_In09 COM3 COM3 24 VDC Jxx_Ch1_In02 Jxx_Ch1_In10 Jxx_Ch4_In07 Jxx_Ch4_In15 Jxx_Ch1_In03 Jxx_Ch1_In11...
  • Page 211 Appendices  CJ1W-IA201 AC Input Unit (200 VAC, 8 Points) Name 8-point AC Input Unit with Terminal Block Model CJ1W-IA201 Rated Input Voltage 200 to 240 VAC 50/60 Hz Allowable Input Voltage Range 170 to 264 VAC Input Impedance 21 kΩ (50 Hz), 18 kΩ (60 Hz) 9 mA typical (at 200 VAC, 50 Hz), Input Current 11 mA typical (at 200 VAC, 60 Hz)
  • Page 212 Appendices  CJ1W-IA111 AC Input Unit (100 VAC, 16 points) Name 16-point AC Input Unit with Terminal Block Model CJ1W-IA111 Rated input voltage 100 to 120 VAC 50/60 Hz Allowable Input Voltage Range 85 to 132 VAC Input Impedance 14.5 kΩ (50 Hz), 12 kΩ (60 Hz) 7 mA typical (at 100 VAC, 50 Hz), Input Current 8 mA typical (at 100 VAC, 60 Hz)
  • Page 213 Appendices  CJ1W-INT01 Interrupt Input Unit (16 Points) Name 16-point Interrupt Input Unit with Terminal Block Model CJ1W-INT01 Rated Input Voltage 24 VDC Allowable Input Voltage Range 20.4 to 26.4 VDC Input Impedance 3.3 kΩ Input Current 7 mA typical (at 24 VDC) ON Voltage/ON Current 14.4 VDC min./3 mA min.
  • Page 214 Appendices  CJ1W-IDP01 Quick-response Input Unit (16 Points) Name 16-point Quick-response Input Unit with Terminal Block Model CJ1W-IDP01 Rated Input Voltage 24 VDC Allowable Input Voltage Range 20.4 to 26.4 VDC Input Impedance 3.3 kΩ Input Current 7 mA typical (at 24 VDC) ON Voltage/ON Current 14.4 VDC min./3 mA min.
  • Page 215 Appendices Basic Output Units  CJ1W-OC201 Contact Output Unit (Independent Relays, 8 Points) Name 8-point Contact Output Unit with Terminal Block (Independent Relays) Model CJ1W-OC201 Max. Switching Capacity 2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit) Min.
  • Page 216 Appendices  CJ1W-OC211 Contact Output Unit (16 Points) Name 16-point Contact Output Unit with Terminal Block Model CJ1W-OC211 Max. Switching Capacity 2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit) Min.
  • Page 217 Appendices  CJ1W-OA201 Triac Output Unit (8 Points) Name 8-point Triac Output Unit with Terminal Block Model CJ1W-OA201 Max. Switching Capacity 0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit) Max. Inrush Current 15 A (pulse width: 10 ms max.) Min. Switching Capacity 50 mA 75 VAC Leakage Current 1.5 mA (200 VAC) max.
  • Page 218 Appendices  CJ1W-OD201 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD201 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 2.0 A/point, 8.0 A/Unit Maximum Inrush Current 10 A/point, 10 ms max.
  • Page 219 Appendices  CJ1W-OD203 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD203 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.5 A/point, 4.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max.
  • Page 220 Appendices  CJ1W-OD211 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD211 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max.
  • Page 221 Appendices  CJ1W-OD213 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD213 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max.
  • Page 222 Appendices  CJ1W-OD231 Transistor Output Unit (32 Points) Name 32-point Transistor Output Unit with Fujitsu Connector (Sinking Outputs) Model CJ1W-OD231 Rated Voltage 12 to 24 VDC Operating Load Voltage 10.2 to 26.4 VDC Range Maximum Load Current 0.5 A/point, 2.0 A/common, 4.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max.
  • Page 223 Appendices Connec- Signal Signal Allocated Allocated tor pin name name CIO word CIO word Jxx_Ch1_Out00 Jxx_Ch2_Out00 Jxx_Ch1_Out01 Jxx_Ch2_Out01 Jxx_Ch1_Out02 Jxx_Ch2_Out02 12 to 12 to Jxx_Ch1_Out03 Jxx_Ch2_Out03 24 VDC 24 VDC Wd m Wd m+1 Jxx_Ch1_Out04 Jxx_Ch2_Out04 Jxx_Ch1_Out05 Jxx_Ch2_Out05 Jxx_Ch1_Out06 Jxx_Ch2_Out06 Jxx_Ch1_Out07 Jxx_Ch2_Out07 COM1...
  • Page 224 Appendices Signal Allocated name CIO word Jxx_Ch1_Out00 Wd m Jxx_Ch1_Out15 COM0 COM0 Output indicator Circuit Configuration Jxx_Ch2_Out00 Wd m+1 Jxx_Ch2_Out15 COM1 COM1 Allocated Signal Connec- Signal Allocated CIO word name tor pin name CIO word 12 to 24 VDC COM1 COM1 Jxx_Ch2_Out07 Jxx_Ch2_Out15...
  • Page 225 Appendices Internal Current Consumption 220 mA max. Fuse None External Power Supply 20.4 to 26.4 VDC, 110 mA min. Weight 70 g max. Signal name Allocated CIO word Jxx_Ch1_Out00 Wd m Jxx_Ch1_Out15 COM0 COM0 Circuit Configuration Output indicator Jxx_Ch2_Out00 Wd m+1 Jxx_Ch2_Out15 COM1 COM1...
  • Page 226 Appendices  CJ1W-OD261 Transistor Output Unit (64 Points) Name 64-point Transistor Output Unit with Fujitsu Connectors (Sinking Outputs) Model CJ1W-OD261 Rated Voltage 12 to 24 VDC Operating Load 10.2 to 26.4 VDC Voltage Range Maximum Load 0.3 A/point, 1.6 A/common, 6.4 A/Unit Current Maximum Inrush 3.0 A/point, 10 ms max.
  • Page 227 Appendices Connec- Connec- Signal Signal Signal Allocated Signal Allocated Allocated Allocated tor pin tor pin name name name CIO word name CIO word CIO word CIO word Jxx_Ch3_Out00 Jxx_Ch4_Out00 Jxx_Ch3_Out01 Jxx_Ch4_Out01 COM0 COM1 Jxx_Ch3_Out02 Jxx_Ch4_Out02 12 to 12 to Jxx_Ch2_Out15 Jxx_Ch1_Out15 Jxx_Ch3_Out03 Jxx_Ch4_Out03...
  • Page 228 Appendices  CJ1W-OD263 Transistor Output Unit (64 Points) Name 64-point Transistor Output Unit with MIL Connectors (Sinking Outputs) Model CJ1W-OD263 Rated Voltage 12 to 24 VDC Operating Load Voltage 10.2 to 26.4 VDC Range Maximum Load Current 0.3 A/point, 1.6 A/common, 6.4 A/Unit Maximum Inrush Current 3.0 A/point, 10 ms max.
  • Page 229 Appendices Connec- Allocated Allocated Signal Signal Signal Connec- Signal Allocated Allocated tor pin CIO word CIO word name name name tor pin name CIO word CIO word 12 to Jxx_Ch1_Out00 Jxx_Ch1_Out08 12 to Jxx_Ch1_Out09 Jxx_Ch1_Out01 COM3 COM3 Jxx_Ch1_Out10 Jxx_Ch1_Out02 Jxx_Ch4_Out15 Jxx_Ch4_Out07 Jxx_Ch1_Out11 Jxx_Ch1_Out03...
  • Page 230 Appendices  CJ1W-OD202 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD202 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 2 A/point, 8 A/Unit Leakage Current 0.1 mA max.
  • Page 231 Appendices Signal Connec- Signal name tor pin name Jxx_Ch1_Out00 Jxx_Ch1_Out01 Jxx_Ch1_Out02 Jxx_Ch1_Out03 24 VDC COM0 (+V) External connection and terminal- device variable diagram Jxx_Ch1_Out04 Jxx_Ch1_Out05 Jxx_Ch1_Out06 Jxx_Ch1_Out07 24 VDC COM1 (+V) • When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
  • Page 232 Appendices  CJ1W-OD204 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD204 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 4.0 A/Unit Leakage Current 0.1 mA max.
  • Page 233 Appendices  CJ1W-OD212 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD212 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 0.1 mA max.
  • Page 234 Appendices  CJ1W-OD232 Transistor Output Unit (32 Points) Name 32-point Transistor Output Unit with MIL Connector (Sourcing Outputs) Model CJ1W-OD232 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 2.0 A/common, 4.0 A/Unit Leakage Current 0.1 mA max.
  • Page 235 Appendices Allocated Allocated Connec- Signal Signal CIO word CIO word tor pin name name 24 VDC COM1 (+V) COM1 (+V) Jxx_Ch2_Out15 Jxx_Ch2_Out07 Jxx_Ch2_Out14 Jxx_Ch2_Out06 Jxx_Ch2_Out13 Jxx_Ch2_Out05 Jxx_Ch2_Out12 Jxx_Ch2_Out04 Jxx_Ch2_Out11 Jxx_Ch2_Out03 Jxx_Ch2_Out10 Jxx_Ch2_Out02 Jxx_Ch2_Out09 Jxx_Ch2_Out01 Jxx_Ch2_Out08 Jxx_Ch2_Out00 COM0 (+V) COM0 (+V) Jxx_Ch1_Out15 Jxx_Ch1_Out07 External connection and termi-...
  • Page 236 Appendices Signal Allocated name CIO word COM0 COM0 Jxx_Ch1_Out00 Wd m Jxx_Ch1_Out15 CN1 (OUT) Output indicator COM1 COM1 Indicator switch Jxx_Ch2_Out00 Wd m+1 Circuit Configura- Jxx_Ch2_Out15 tion COM2 COM2 Jxx_Ch3_Out00 Wd m+2 Jxx_Ch3_Out15 CN2 (OUT) COM3 COM3 Jxx_Ch4_Out00 Wd m+3 Jxx_Ch4_Out15 Connec- Allocated...
  • Page 237 Appendices Mixed I/O Units  CJ1W-MD231 DC Input/Transistor Output Unit (24 VDC, 16 Inputs/16 Outputs) Name 16-point DC Input/16-point Transistor Output Unit with Fujitsu Connectors (Sinking Outputs) Model CJ1W-MD231 Output section (CN1) Input section (CN2) Rated Voltage 12 to 24 VDC Rated Input Voltage 24 VDC Operating Load Volt-...
  • Page 238 Appendices CN1 (OUT) CN2 (IN) Allocated Signal Signal Connector Signal Allocated Signal Connec- Allocated Allocated CIO word name name name CIO word name tor pin CIO word CIO word Jxx_Ch1_In00 Jxx_Ch1_In08 Jxx_Ch1_In01 Jxx_Ch1_In09 Jxx_Ch1_In02 Jxx_Ch1_In10 Jxx_Ch1_In03 Jxx_Ch1_In11 COM0 (0 V) COM0 (0 V) Jxx_Ch1_In04 Jxx_Ch1_In12...
  • Page 239 Appendices  CJ1W-MD233 DC Input/Transistor Output Unit (24 VDC, 16 Inputs/16 Outputs) Name 16-point DC Input/16-point Transistor Output Unit with MIL Connectors (Sinking Outputs) Model CJ1W-MD233 Output section (CN1) Input section (CN2) 12 to 24 VDC Rated Input Volt- 24 VDC Rated Voltage Operating Load Voltage 10.2 to 26.4 VDC...
  • Page 240 Appendices CN1 (OUT) CN2 (IN) Signal Connec- Signal Allocated Allocated Allocated Signal Connec- Signal Allocated CIO word CIO word name tor pin name CIO word name tor pin name CIO word Jxx_Ch1_Out00 Jxx_Ch1_Out08 Jxx_Ch1_Out01 Jxx_Ch1_Out09 COM1 COM1 Jxx_Ch1_Out02 Jxx_Ch1_Out10 Jxx_Ch1_In15 Jxx_Ch1_In07 Jxx_Ch1_Out03 Jxx_Ch1_Out11...
  • Page 241 Appendices CN1 (OUT) CN2 (IN) Signal Allocated Allocated Signal name CIO word CIO word name 5.6 kW Jxx_Ch1_In00 Connect Jxx_Ch1_Out00 Jxx_Ch1_In15 Connect or row A Wd m or row A COM2 Jxx_Ch1_Out15 COM2 Indicator switch COM0 Output COM0 Input indicator indicator Indicator 5.6 kW...
  • Page 242 Appendices  CJ1W-MD263 DC Input/Transistor Output Unit (24 VDC 32 Inputs/32 Outputs) Name 32-point DC Input/32-point Transistor Output Unit with MIL Connectors (Sinking Outputs) Model CJ1W-MD263 Output section (CN1) Input section (CN2) Rated Voltage 12 to 24 VDC Rated Input Voltage 24 VDC Operating Load 10.2 to 26.4 VDC...
  • Page 243 Appendices CN1 (OUT) CN2 (IN) Allocated Allocated Allocated Signal Connec- Signal Signal Allocated Connec- Signal CIO word CIO word CIO word name tor pin name name CIO word tor pin name 24 VDC Jxx_Ch1_Out00 Jxx_Ch1_Out08 12 to Jxx_Ch1_Out01 Jxx_Ch1_Out09 COM3 COM3 Jxx_Ch1_Out02 Jxx_Ch1_Out10...
  • Page 244 Appendices  CJ1W-MD232 DC Input/Transistor Output Unit (24 VDC, 16 inputs/16 Outputs) Name 16-point DC Input/16-point Transistor Output Unit with MIL Connectors (Sourcing Outputs) Model CJ1W-MD232 Output section (CN1) Input section (CN2) 24 VDC Rated Input Volt- 24 VDC Rated Voltage Operating Load Voltage 20.4 to 26.4 VDC Operating Input...
  • Page 245 Appendices CN1 (OUT) CN2 (IN) Signal Signal Connec- Signal Allocated Connec- Signal Allocated Allocated Allocated name name tor pin name CIO word tor pin name CIO word CIO word CIO word Jxx_Ch1_Out00 Jxx_Ch1_Out08 COM1 COM1 Jxx_Ch1_Out01 Jxx_Ch1_Out09 Jxx_Ch1_In15 Jxx_Ch1_In07 Jxx_Ch1_Out02 Jxx_Ch1_Out10 Jxx_Ch1_In14 Jxx_Ch1_In06...
  • Page 246 Appendices  CJ1W-MD563 TTL I/O Unit (32 Inputs/32 Outputs) Name 32-point Input /32-point Output TTL I/O Unit with MIL Connectors Model CJ1W-MD563 Output section (CN1) Input section (CN2) 5 VDC±10% Rated Input Volt- 5 VDC±10% Rated Voltage Operating Load Volt- 4.5 to 5.5 VDC 1.1 kΩ...
  • Page 247 Appendices CN1 (OUT) CN2 (IN) Allocated Allocated Allocated Signal Connec- Signal Signal Connec- Allocated Signal CIO word CIO word CIO word name tor pin name name tor pin CIO word name 5 VDC Jxx_Ch1_Out00 Jxx_Ch1_Out08 5 VDC COM3 COM3 Jxx_Ch1_Out01 Jxx_Ch1_Out09 Jxx_Ch2_In15 Jxx_Ch2_In07...
  • Page 248: A-2-3 Precautions On Contact Output Units

    Appendices A-2-3 Precautions on Contact Output Units Service Life Expectancy The service life expectancy of the relays (NY-24W-K-IE) in the CJ1W-OC201/211 Contact Output Units depends on the type of load, the contact current, and the ambient temperature. Use the follow- ing diagrams to calculate the relay service life based on the operating conditions, and replace the relay before the end of its service life.
  • Page 249 Appendices Current Circuit Characteristic Required element If the load is a relay or solenoid, there The capacitance of the capacitor should be approx. 1 to 0.5 μF per contact current of 1 A and method is a delay in the resetting time. resistance of the resistor should be approx.
  • Page 250: Connecting Connector-Terminal Block Conversion Units And I/O Relay Terminals

    Patterns for Combining Connector-Terminal Block Conversion Units and I/O Relay Terminals The following patterns can be used to connect Basic I/O Units with Connectors to OMRON Connector- Terminal Block Conversion Units and I/O Relay Terminals using OMRON Connecting Cables.  Connection Patterns for Connector-Terminal Block Conversion Units...
  • Page 251 Appendices  Connection Patterns for I/O Relay Terminals Pattern Configuration Connecting Cable I/O Relay Terminal I/O Relay Terminal I/O Relay Terminal Connecting Cable I/O Relay Terminal I/O Relay Terminal Connecting Cable Connecting Cable I/O Relay Terminal A-55 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 252 Appendices Combinations of Connections Combinations of OMRON Connecting Cables with Connector-Terminal Block Conversion Units and I/O Relay Terminals are shown below.  Connections to Connector-Terminal Block Conversion Units Number Connec- Number Connec- I/O capac- Connecting Connector-Terminal Block Common Unit of con-...
  • Page 253 Appendices Number Connec- Number Connec- I/O capac- Connecting Connector-Terminal Block Common Unit of con- Polarity tion pat- tion dia- Cable Conversion Unit terminal nectors tern branches gram CJ1W- 64 inputs 2 Fujitsu NPN/PNP None XW2Z-B XW2D-40G6 None A-67 ID261 connectors None XW2Z-B None...
  • Page 254 Appendices Number Connec- Number Connec- I/O capac- Connecting Connector-Terminal Block Common Unit of con- Polarity tion pat- tion dia- Cable Conversion Unit terminal nectors tern branches gram CJ1W- 32 outputs 1 MIL con- None XW2Z-K XW2D-40G6 None A-71 OD233 nector None XW2Z-K XW2B-40G5...
  • Page 255 Appendices Number Connec- Number Connec- I/O capac- Connecting Connector-Terminal Block Common Unit of con- Polarity tion pat- tion dia- Cable Conversion Unit terminal nectors tern branches gram CJ1W- 16 inputs 1 Fujitsu NPN/PNP None XW2Z-A XW2D-20G6 None A-76 MD231 connector None XW2Z-A XW2B-20G5...
  • Page 256 Appendices Number Connec- Number Connec- I/O capac- Connecting Connector-Terminal Block Common Unit of con- Polarity tion pat- tion dia- Cable Conversion Unit terminal nectors tern branches gram CJ1W- 32 inputs 1 MIL con- NPN/PNP None XW2Z-K XW2D-40G6 None A-81 MD263 nector None XW2Z-K...
  • Page 257 Appendices  Connections to I/O Relay Terminals Number of Connection Number of Connecting Connection Unit I/O capacity Polarity I/O Relay Terminal connectors pattern branches Cable diagram CJ1W-ID231 32 inputs 1 Fujitsu con- XW2Z-RIC- G7TC-ID16 A-84 nector XW2Z-RIC- G7TC-IA16 CJ1W-ID232 32 inputs 1 MIL con- XW2Z-RO--D1 G7TC-ID16...
  • Page 258 Appendices Number of Connection Number of Connecting Connection Unit I/O capacity Polarity I/O Relay Terminal connectors pattern branches Cable diagram CJ1W-OD261 64 outputs 2 Fujitsu con- XW2Z-ROC- G7TC-OC16 A-87 nectors XW2Z-ROC- G7TC-OC08 XW2Z-ROC- G70D-SOC16 A-86 XW2Z-ROC- G70D-FOM16 XW2Z-ROC- G70D-VSOC16 A-85 XW2Z-ROC-...
  • Page 259 Appendices Number of Connection Number of Connecting Connection Unit I/O capacity Polarity I/O Relay Terminal connectors pattern branches Cable diagram CJ1W-MD261 32 inputs 1 Fujitsu con- XW2Z-RIC- G7TC-ID16 A-84 nector XW2Z-RIC- G7TC-IA16 32 outputs 1 Fujitsu con- XW2Z-ROC- G7TC-OC16 A-87 nector XW2Z-ROC-...
  • Page 260 Appendices Connector-Terminal Block Conversion Unit Connection Diagrams The applicable terminals on the Connector-Terminal Block Conversion Unit and external connection diagrams are provided below for Basic I/O Unit connections to Connector-Terminal Block Conversion Units.  Inputs Programma- CJ1W-ID231 Programma- CJ1W-ID231 ble Control- ble Controller ler I/O Unit I/O Unit...
  • Page 261 Appendices 2 The COM terminals are wired inside the Connec- Programma- CJ1W-ID232 tor-Terminal Block Conversion Unit. ble Control- ler I/O Unit Connector- XW2C-20G6-IO16 (2 Units) Programma- CJ1W-ID232 Terminal ble Control- Block Con- ler I/O Unit version Unit Connector- XW2D-40G6 Connecting XW2Z-N Terminal XW2D-40G6-RM...
  • Page 262 Appendices Programma- CJ1W-ID233 Programma- CJ1W-ID233 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal XW2D-40G6-RM Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m (Wd (m+1)) (Short bar)
  • Page 263 Appendices Programma- CJ1W-ID261 Programma- CJ1W-ID261 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal XW2D-40G6-RF Block Con- Block Con- version Unit version Unit Connecting XW2Z-B Connecting XW2Z-D Cables Cables Wd m and m+1 (Wd m+2 and m+3) (Short bar)
  • Page 264 Appendices Programma- CJ1W-ID262 Programma- CJ1W-ID262 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal XW2D-40G6-RM Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m and m+1 (Wd m+2 and m+3) (Short bar)
  • Page 265 Appendices  Outputs Programma- CJ1W-OD231 Programma- CJ1W-OD231 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal XW2D-40C6 Block Con- Block Con- version Unit version Unit XW2Z-B Connecting XW2Z-L Connecting Cables Cables XW2Z-BU Wd m (Wd (m+1))
  • Page 266 Appendices Programma- CJ1W-OD232 Programma- CJ1W-OD232 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m (Wd (m+1)) (Short bar) COM0 (COM1)
  • Page 267 Appendices Programma- CJ1W-OD233 Programma- CJ1W-OD233 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m (Wd (m+1)) (Short bar) COM0 (COM1)
  • Page 268 Appendices Programma- CJ1W-OD234 Programma- CJ1W-OD234 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m (Wd (m+1)) (Short bar) COM0 (COM1)
  • Page 269 Appendices Programma- CJ1W-OD261 Programma- CJ1W-OD261 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal XW2D-40C6 Block Con- Block Con- version Unit version Unit XW2Z-B Connecting XW2Z-L Connecting Cables Cables XW2Z-BU Wd m ( CN2 ) and (m+1) (Wd (m+2)
  • Page 270 Appendices Programma- CJ1W-OD262 Programma- CJ1W-OD262 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m and (m+1) (Wd (m+2) and (m+3)) (Short bar)
  • Page 271 Appendices Programma- CJ1W-OD263 Programma- CJ1W-OD263 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-40G6 Connector- XW2C-20G6-IO16 (2 Units) Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-K Connecting XW2Z-N Cables Cables Wd m and (m+1) (Wd (m+2) and (m+3)) (Short bar)
  • Page 272 Appendices  Inputs and Outputs Programma- CJ1W-MD231 ble Control- ler I/O Unit Connector- XW2D-20G6 Terminal Block Con- version Unit Connecting XW2Z-A Cables (OUT) Wd m COM (0 V) COM (0 V) 12 to 12 to 24 VDC 24 VDC Connection diagram (IN) Wd (m+1)
  • Page 273 Appendices Programmable Con- CJ1W-MD231 troller I/O Unit Connector-Terminal XW2C-20G6-IO16 Block Conversion Unit Connecting Cables XW2Z-A (IN) Wd m (OUT) Wd (m+1) (Short (Short bar) bar) COM0 (COM1) (Short bar) Solenoid valve, etc. Black (White) Brown (Red) Blue (Black) 3-wire sensor with PNP output (photoelectric sensor or proximity sensor)
  • Page 274 Appendices Programma- CJ1W-MD232 Programma- CJ1W-MD233 ble Control- ble Control- ler I/O Unit ler I/O Unit Connector- XW2D-20G6 Connector- XW2D-20G6 Terminal Terminal Block Con- Block Con- version Unit version Unit Connecting XW2Z-X Connecting XW2Z-X Cables Cables (OUT) Wd m (OUT) Wd m 12 to 12 to COM (+V)
  • Page 275 Appendices Programmable Con- CJ1W-MD261 troller I/O Unit Connector-Terminal XW2D-40G6 Block Conversion XW2D-40G6RF Unit Connecting Cables XW2Z-B (OUT) (IN) Wd (m+3) Wd (m+1) Wd (m+2) Wd m COM1 COM0 COM3 COM2 Connection diagram COM1 COM3 COM0 COM2 12 to 12 to 24 VDC 24 VDC 24 VDC...
  • Page 276 Appendices Programmable Con- CJ1W-MD261 troller I/O Unit Connector-Terminal XW2C-20G6-IO16 (2 Units) XW2C-20G6-IO16 (2 Units) Block Conversion Unit Connecting Cables XW2Z-L XW2Z-D Wd m Wd (m+2) (OUT) (Wd (m+1)) (Wd (m+3)) (IN) (Short (Short bar) bar) COM0 (COM1) (Short bar) Solenoid valve, etc. Black (White) Brown (Red) Blue (Black)
  • Page 277 Appendices Programmable Con- CJ1W-MD263 troller I/O Unit Connector-Terminal XW2D-40G6 Block Conversion XW2D-40G6-RM Unit Connecting Cables XW2Z-K (IN) (OUT) 12 to 24 VDC 24 VDC Wd (m+2) Wd m COM2 COM0 COM2 COM0 Connection diagram Wd (m+3) Wd (m+1) COM3 COM3 COM1 COM1 12 to...
  • Page 278 Appendices Programmable Con- CJ1W-MD263 troller I/O Unit Connector-Terminal XW2C-20G6-IO16 (2 Units) Block Conversion Unit Connecting Cables XW2Z-N Wd m Wd (m+2) (OUT) (IN) (Wd (m+1)) (Wd (m+3)) (Short (Short bar) bar) COM0 (COM1) (Short bar) Solenoid valve, etc. Black (White) Brown (Red) Blue (Black) 3-wire sensor with...
  • Page 279 Appendices Programmable Con- CJ1W-MD563 troller I/O Unit Connector-Terminal XW2D-40G6 Block Conversion XW2D-40G6-RM Unit Connecting Cables XW2Z-K (IN) (OUT) 5 VDC 5 VDC Wd (m+2) Wd m COM2 COM2 COM0 COM0 Connection diagram Wd (m+3) Wd (m+1) COM3 COM3 COM1 COM1 5 VDC 5 VDC Note 1 The +V terminals and COM terminals...
  • Page 280 Appendices Connection Diagrams for I/O Relay Terminals Connection examples and internal connection diagrams for I/O Relay Terminals connected to Basic I/O Units are shown below.  Inputs G7TC I/O Relay Terminals G7TC-ID16 G7TC-IA16 G7TC G7TC Relay side Relay side Input Unit Input Unit TOP VIEW TOP VIEW...
  • Page 281 Appendices  Outputs G70D-V Relay Terminals G70D-VSOC16 G70D-VSOC16+G70D-ET Power Power supply supply G70D - VSOC16 G70D - VSOC16 G70D - ET Back Back side side Output Unit Output Unit TOP VIEW TOP VIEW Note 1 They are also isolated from the Output Unit and I/O Note 1 They are also isolated from the Output Unit and I/O Relay Terminal.
  • Page 282 Appendices G70D Relay Terminals G70D-SOC16 G70D-SOC08 Power supply G70D - SOC16 Power supply G70D - SOC08 Relay side Output Unit Relay side Output Unit TOP VIEW TOP VIEW Note Every two outputs share a common. The current supplied Note 1 All outputs are independent. They are also isolated is 3 A per common.
  • Page 283 Appendices G70R Relay Terminals G7TC I/O Relay Terminals G70R-SOC08 G7TC-OC16/OC08 Power supply G7TC Power supply G70R - SOC08 Output Unit Relay side Output Unit TOP VIEW TOP VIEW Note 1 All outputs are independent. They are also iso- Note 1 All outputs are independent. They are also iso- lated from the Output Unit and I/O Relay Terminal.
  • Page 284 Appendices G7TC I/O Relay Terminals G70A-ZOC16 Relay Terminal Socket G7TC-OC16-1 G70A-ZOC16-3+G2R-1-S (16 Units) Power Power supply supply G7TC G70A - ZOC16 - 3 + G2R - 1 - S (16 Units) Relay side Relay side Output Unit Output Unit TOP VIEW TOP VIEW Note 1 The above diagram is an example with the G2R-1- Note 1 All outputs are independent.
  • Page 285: Dimensions

    Appendices Dimensions A-3-1 NJ-series CPU Units NJ501-, NJ301- and NJ101- Unit: mm A-89 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 286: A-3-2 Nj-Series Power Supply Units

    Appendices A-3-2 NJ-series Power Supply Units NJ-PA3001 Unit: mm NJ-PD3001 Unit: mm A-90 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 287: A-3-3 Cj-Series Basic I/O Units

    Appendices A-3-3 CJ-series Basic I/O Units 8/16-point Units with 18-terminal Terminal Blocks Unit: mm ID211 10 11 12 13 14 15 DC24V 32-point Units (Input Units and Output Units) Unit: mm Units with Fujitsu-compatible Connector (40-pin × 1) (112.5) 66.5 ID231 1 2 3 4 5 6 7...
  • Page 288 Appendices 32-point Units (24-VDC Input/Transistor Output Units) Units with Fujitsu-compatible Connector (24-pin × 2) Unit: mm (112.5) 66.5 Units with MIL Connector (20-pin × 2) 83.6 A-92 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 289 Appendices 64-point Units (Input Units, Output Units, 24-VDC Input/Transistor Output Units, TTL I/O Units) Units with Fujitsu-compatible Connector (40-pin × 2) Unit: mm (112.5) 66.5 Units with MIL Connector (40-pin × 2) 83.6 A-93 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 290: A-3-4 B7A Interface Unit

    Appendices A-3-4 B7A Interface Unit CJ1W-B7A Unit: mm 79.5 A-3-5 CJ-series I/O Control Unit and I/O Interface Unit Unit: mm CJ1W-IC101 CJ1W-II101 I/O Control Unit I/O Interface Unit (140) (140) II101 IC101 IC101 69.3 69.3 A-3-6 SD Memory Card Unit: mm 32±0.1 2.1±0.15 24±0.1...
  • Page 291: Load Short-Circuit Protection And Line Disconnection Detection For Cj-Series Basic I/O Units

    Appendices Load Short-circuit Protection and Line Disconnection Detection for CJ- series Basic I/O Units A-4-1 Load Short-circuit Protection and Line Disconnection Detection for CJ1W-OD202 This section describes the load short-circuit protection and line disconnection detection of the CJ1W- OD202 Output Units. As shown below, normally when the output bit (OUT) turns ON, the transistor will turn ON and then out- put current (Iout) will flow.
  • Page 292 Appendices Figure 3 Operation for Disconnected Line with Output Current below the Line Disconnection Detection Current A: Load not connected or load line broken. B: Current to load at or below line disconnection detection current. C: Rise of current to load too slow and error detected before the disconnection detection current was reached.
  • Page 293 Appendices  Programming Example In this example, CJ1W-OD202 is mounted in slot 0 of rack 0. This example shows how to change output Jxx_Ch0_Out00 to FALSE immediately if the Alarm Out- put Bit _CJB_IOUnitInfo[0,0,0] changes to TRUE and how to keep the output FALSE until the cause is removed and the bit is reset with RstOD202.
  • Page 294: A-4-2 Load Short-Circuit Protection For Cj1W-Od204/Od212/Od232/Md232

    Appendices A-4-2 Load Short-circuit Protection for CJ1W- OD204/OD212/OD232/MD232 As shown below, normally when the output bit turns ON (OUT), the transistor will turn ON and then out- put current (Iout) will flow. If the output current (Iout) exceeds the detection current (Ilim) when an over- load or short-circuit occurs, the output current (Iout) will be limited as shown in Figure 2.
  • Page 295 Appendices  Restrictions If a short-circuit occurs in an external load, immediately turn OFF the corresponding output and remove the cause. An alarm output bit that corresponds to the external load output number is turned ON. There is an alarm output bit for every common. When an alarm output bit turns ON, use a self-holding bit for the alarm in the user program and turn OFF the corresponding output.
  • Page 296: Emc Directive Measures For Relay Outputs

    Appendices EMC Directive Measures for Relay Outputs The NJ-series Controllers conform to the Common Emission Standards (EN 61131-2) of the EMC Directives. However, noise generated by relay output switching may not satisfy these Standards when the Controller is incorporated into a system. In such a case, a noise filter must be connected to the load side or other appropriate countermeasures must be provided external to the Controller.
  • Page 297 Appendices Current Circuit Characteristic Required element The varistor method prevents the Varistor method imposition of high voltage between the contacts by using the constant voltage characteristic of the varis- tor. There is a delay in the resetting time. Power supply If the supply voltage is 24 or 48 V, insert the varistor in parallel with the load.
  • Page 298: System-Defined Variables Related To Hardware

    Appendices System-defined Variables Related to Hardware System-defined variables are assigned specific functions by the system. They are registered in the global variable table, or the local variable table for each POU, in advance. The variable names cannot be changed. Some of the variables start with an underbar and some start with ”P_”.
  • Page 299: Version Information

    Appendices Version Information Refer to Version Information for NJ-series Controllers in the NJ/NX-series CPU Unit Software User’s Manual (Cat. No. W501) for the relationship between the unit versions of CPU Unit and the Sysmac Studio versions, and for the functions that are supported by each unit version. A-7-1 Relationship between Hardware Revisions of CPU Units and Sysmac Studio Versions...
  • Page 300 Appendices Performance Sysmac Stu- Function Unit version value dio version Motion Number of Maximum number of con- 15 axes 1.06 or later 1.07 or higher Control controlled axes *2*3*4 8 axes (NJ301- Other than the above combi- trolled axes 1200) nation (NJ301-) 4 axes (NJ301-...
  • Page 301 Index Index-1 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 302 Index Index current consumptions ........2-6, 2-10, 2-13 B7A communications specifications ......3-27 B7A interface ports ............3-26 Daisy chain ............4-57, 4-59 B7A Interface Units ............3-26 dimensions ............4-23, A-89 wiring ..............4-44 DIN Track ............2-8, 4-17, 4-19 Basic I/O Unit DIP switches ............3-4, 3-8 Information ..
  • Page 303 Index LG ................4-31 SD BUSY indicator ............3-6 LG terminal ............3-16, 4-31 SD Memory Card connector ......... 3-4 line disconnection detection ........A-95 SD Memory Card Power Supply Switch ....... 3-4 LINK/ACT indicator ..........3-7, 3-8 SD Memory Cards ..........2-7, 3-10 load short-circuit protection .........
  • Page 304 Index Index-4 NJ-series CPU Unit Hardware User’s Manual (W500)
  • Page 306 The Netherlands Hoffman Estates, IL 60169 U.S.A. Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 © OMRON Corporation 2011-2021 All Rights Reserved. OMRON (CHINA) CO., LTD. OMRON ASIA PACIFIC PTE. LTD. In the interest of product improvement, Room 2211, Bank of China Tower, No.

Table of Contents