Omron CJ1W-SCU32 Operation Manual page 103

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

Device variable for CJ-series Unit
Port 1
*_P1_PmrAbtSta
*_P1_PmrTracingSta
*_P1_PmrSeqEndSta
*_P1_PmrSeqAbtSta
*_P1_PmrSeqWaitSta
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
2 Initial Settings and Allocations of Device Variable for CJ-series Unit
Port 2
*_P2_PmrAbtSta
BOOL
*_P2_PmrTracingSta
BOOL
*_P2_PmrSeqEndSta
BOOL
*_P2_PmrSeqAbtSta
BOOL
*_P2_PmrSeqWaitSta
BOOL
Type
R/W
Name
R
Abort Flag
R
Tracing Flag
R
Sequence End
Completion
Flag
R
Sequence
Abort Comple-
tion Flag
R
Sequence Wait
Flag
Function
This flag is changed to
TRUE when processing is
ended by using the abort
switch from the user pro-
gram.
When the abort switch is
turned ON at the end of a
sequence, the sequence
may end with either End or
Abort status.
This flag is changed to
TRUE while time series
data for send and receive
messages is traced with
an instruction from the
CX-Protocol.
This flag is changed to
TRUE when a sequence is
completed for the next
process or for an error
process with an End com-
mand.
Note When a sequence
has ended normally,
setting End (Abort
when the sequence
has ended abnor-
mally) enables this
flag
to
determine
whether or not the
sequence execution
has ended normally.
TRUE: Sequence ended
FALSE: Sequence not
ended
This flag is changed to
TRUE when a sequence is
ended for the next process
or for an error processing
with an Abort command.
TRUE: Sequence aborted
FALSE: Sequence not
aborted
This flag is changed to
TRUE when a sequence is
in the waiting state due to
the WAIT command.
Waiting is released when
the Wait Release Switch is
changed to TRUE in the
user program, and the
sequence will move to the
next step.
2-29
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu22Cj1w-scu42

Table of Contents