Omron CJ1W-SCU32 Operation Manual page 325

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

Event name
Command Format Error
Meaning
An illegal function code or address was specified in a received Modbus-RTU command.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An illegal function code, address, or
data was specified in a received Mod-
bus-RTU command.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
Event name
Transmission Error
Meaning
A transmission error occurred.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
One of the following errors occurred.
• Tfs (Send Finished Monitoring
Time) Exceeded
• Tfr (Receive Finished Monitoring
Time) Exceeded
• Tr (Receive Wait Monitoring Time)
Exceeded
• FCS Check Error
• Command Error
• Timeout Error
• Overrun Error
• Framing Error
• Parity Error
Attached
Attached information 1: Port number where error was detected
information
Precautions/
In Protocol Macro Mode, this error does not occur if communications recover within the specified number of retries.
Remarks
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Check the format of the Modbus-RTU
command and correct the Modbus-
RTU command at the device that sent
the Modbus-RTU command.
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
See which error occurs from the Sys-
mac Studio or an NS-series PT and
take suitable measures.
9 Troubleshooting and Maintenance
Event code
64A70000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Check the format of the Modbus-RTU
command to create a Modbus-RTU
command.
Event code
84680000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Refer to the measures for the errors
listed as causes to prevent the errors
from occurring.
During Modbus-
RTU Slave Mode
System
After serial com-
munications start
System
9
9-47