A Standard System Protocol
Single Run Measurement Start (4000-series) (Sequence No. 434
(Hex 01B2))
When the sample measurement condition is from 1 to 999, this sequence performs a single run mea-
surement and requests the measurement results.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Offset
+0
Number of receive data words
(4 digits Hex)
+1
Decision result
(ASCII 2 characters)
+2
Measurement value (decimal
portion) (4 digits BCD)
+3
Measurement value (integer por-
tion) (3 digits BCD)
+4
Measurement value (Sign) (BIN)
+5 to +7
Deviation value
R-110
+0
Number of receive data words
+1
Decision result
Decimal portion
+2
+3
(Undefined)
+4
Sign
+5
Decimal portion
+6
(Undefined)
+7
Sign
Contents (data format)
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Measurement value
Integer portion
(Undefined)
Integer portion
Deviation value
(Undefined)
With no reference setting: 0005
With reference setting: 0008
With no limit setting: 0000
With limit setting: 2B4E ("+N"), 4F4B ("OK"), 2D4E ("–N")
0000 to 9999
000 to 999
If +: 0
If –: F
Same as measurement value
*The deviation will be stored in this area only when reference
setting is made.
Data
Example –123.4567
+2
4 5 6 7
+3
0 1 2 3
+4
F 0 0 0