Device variable for CJ-series Unit
Port 1
*_P1_PmrAbtSta
*_P1_PmrTracingSta
*_P1_PmrSeqEndSta
*_P1_PmrSeqAbtSta
*_P1_PmrSeqWaitSta
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Type
Port 2
*_P2_PmrAbtSta
BOOL
*_P2_PmrTracingSta
BOOL
*_P2_PmrSeqEndSta
BOOL
*_P2_PmrSeqAbtSta
BOOL
*_P2_PmrSeqWaitSta
BOOL
4 Using Protocol Macros
R/W
Name
R
Abort Flag
R
Tracing Flag
R
Sequence End
Completion
Flag
R
Sequence
Abort Comple-
tion Flag
R
Sequence Wait
Flag
Function
This flag is changed to
TRUE when processing is
ended by using the Abort
Switch from the user pro-
gram. When the Abort
Switch is turned ON at the
end of a sequence, the
sequence may end with
either End or Abort status.
This flag is changed to
TRUE while time series
data for send and receive
messages is traced with
an instruction from the
CX-Protocol.
This flag is changed to
TRUE when a sequence is
completed for the next
process or for an error
process with an End com-
mand.
Note When a sequence
ends normally, set-
ting
End
(Abort
when the sequence
ends
abnormally)
enables this flag to
be used to deter-
mine whether or not
the sequence execu-
tion ended normally.
TRUE: Sequence ended
FALSE: Sequence not
ended
This flag is changed to
TRUE when a sequence is
ended for the next process
or for an error processing
with an Abort command.
TRUE: Sequence aborted
FALSE: Sequence not
aborted
This flag is changed to
TRUE when a sequence is
waiting due to the Wait
command.
Waiting is released when
the Wait Release Switch
changes from FALSE to
TRUE in the user pro-
gram, and the sequence
will move to the next step.