Cause and Countermeasure by Command End Code
Main response code
Sub response code
(hex)
Value
Details
Value
00
Normal end
00
04
02
Destination
05
error
06
10
Command
01
format error
02
11
Parameter
0C
error
26
Command
05
error
07
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
(hex)
Check point
Details
Normal end
---
Destination
*_P1(orP2)_Timeout
busy
Err (Timeout Error)
Response
*_P1(orP2)_Timeout
timeout at
Err (Timeout Error)
command
source side
Instruction control
data
Error log read
Serial gate-
*_P1(orP2)_Timeout
way
Err (Timeout Error)
response
timeout
Transmis-
*_P1(orP2)_FCSErr
sion line
(FCS Check Error) or
error
*_P1(orP2)_ParityErr
(Parity Error)
Command
Command data
packet too
long
Insufficient
Command data
command
length
Parameter
Parameters in com-
error
mand data
Service exe-
---
cuting
No right to
Serial Gateway pro-
execute ser-
hibited or not
vice
9 Troubleshooting and Maintenance
Possible cause
---
The Serial Gateway
Retry the command or correct the com-
function cannot be
munications sequence.
executed by interrupt-
ing the macro
between protocol
macro steps.
When the message
If *_P1(orP2)_TimeoutErr is TRUE,
frame is damaged by
assume that the command source gener-
noise.
ated a response timeout.
• Check the noise condition by an inter-
node test.
• Increase the number of resends at the
command source.
• Perform communications retry if
required.
Response monitor-
Set a longer parameter value for
ing time is short.
response monitoring time.
Discarding of send
Take the correct action after checking the
and receive frame
error log.
Serial Gateway
If *_P1(orP2)_TimeoutErr is set to TRUE,
Response Timeout
assume that the Serial Gateway gener-
occurred.
ated a response timeout and take the
appropriate actions.
• Conversion to
Use shielded twisted-pair cables.
CompoWay/F com-
Lay power lines separately by using
mand: BCC error or
ducts.
parity error
Increase the number of resends at the
• Conversion to Mod-
command source.
bus-RTU com-
Perform communications retry as
mand: CRC error or
required.
parity error
• Conversion to Mod-
bus-ASCII com-
mand: CRC error or
checksum error
Command length is
Set the command data correctly by refer-
long.
ring to the command format.
Command length is
Set the command data correctly by refer-
short.
ring to the command format.
Parameter is not set
Set the parameters again, this time cor-
correctly.
rectly, after you check the command
data.
Service executing
Add retry processing on the command
(The serial communi-
source for response code 2605 hex.
cations port received
a sixth command
when five commands
are still waiting for
processing.)
*_P1(orP2)_PmrSgw
While the Serial Gateway is prohibited,
ProhSta (Serial Gate-
set *_P1(orP2)_SgwDsblCmd (Serial
way Prohibited Flag
Gateway Prohibit Switch (Protocol Mac-
(Protocol Macros)) is
ros)) from TRUE to FALSE.
set to TRUE.
Remedy
---
9
9-9