Single Run Measurement Start (3000-series) (Sequence No. 410
(Hex 019A))
When the sample measurement condition is from 1 to 999, this sequence performs a single run mea-
surement and requests the measurement results.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data stor
age words
Offset
+0
Number of receive data words
(4 digit Hex)
+1
Program number
(1 digit BCD)
+2
Decision result
(ASCII 2 characters)
+3
Measurement value (decimal
portion) (4 digits BCD)
+4
Measurement value (integer por-
tion) (3 digits BCD)
+5
Measurement value (Sign) (BIN)
+6 to +8
Deviation value
Zero Run Measurement Start (3000-series) (Sequence No. 411 (Hex
019B))
If the sample measurement condition is zero, a zero run measurement is started.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Number of receive data words
+0
+1
(Undefined)
+2
Decision result
Decimal portion
+3
(Undefined)
+4
+5
Sign
Decimal portion
+6
+7
(Undefined)
Sign
+8
Contents (data format)
A Standard System Protocol
Program number
Measurement value
Integer portion
(Undefined)
Deviation value
Integer portion
(Undefined)
With no reference setting: 0006
With reference setting: 0009
0 to 9
With no limit setting: 0000
With limit setting: 2B4E ("+N"), 4F4B ("OK"),
2D4E ("–N")
0000 to 9999
000 to 999
If +: 0
If –: F
Same as measurement value
*The deviation will be stored in this area only when reference
setting is made.
Data
Example –123.4567
+3
4 5 6 7
+4
0 1 2 3
+5
F 0 0 0
R-95