Omron CJ1W-CTL41-E Operation Manual
Omron CJ1W-CTL41-E Operation Manual

Omron CJ1W-CTL41-E Operation Manual

Machine automation controller, 4-channel counter unit, nj-series cpu unit
Hide thumbs Also See for CJ1W-CTL41-E:
Table of Contents

Advertisement

Quick Links

ZX-T Series
Machine Automation Controller
CJ-series
4-Channel Counter Unit
Operation Manual
for NJ-series CPU Unit
CJ1W-CTL41-E
4-Channel Counter Unit
W512-E2-01

Advertisement

Table of Contents
loading

Summary of Contents for Omron CJ1W-CTL41-E

  • Page 1 ZX-T Series Machine Automation Controller CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit CJ1W-CTL41-E 4-Channel Counter Unit W512-E2-01...
  • Page 3: Introduction

    Thank you for purchasing a CJ-series CJ1W-CTL41-E 4-Channel Counter Unit. This manual contains information that is necessary to use the CJ-series CJ1W-CTL41-E 4-Channel Counter Unit for an NJ-series CPU Unit. Please read this manual and make sure you understand the functionality and performance of the NJ-series CPU Unit before you attempt to use it in a control sys- tem.
  • Page 4: Relevant Manuals

    Introduction Relevant Manuals There are three manuals that provide basic information on the NJ-series CPU Units: the NJ-series CPU Unit Hardware User’s Manual, the NJ-series CPU Unit Software User’s Manual and the NJ-series Instructions Reference Manual. Most operations are performed from the Sysmac Studio Automation Software. Refer to the Sysmac Stu- dio Version 1 Operation Manual (Cat.
  • Page 5: Manual Configuration

    Introduction Manual Configuration NJ-series CPU Unit Hardware User’s Manual (Cat. No. W500) Section Description Section 1 This section provides an introduction to the NJ-series Controllers and their features, Introduction and gives the NJ-series Controller specifications. Section 2 This section describes the system configuration used for NJ-series Controllers. System Configuration Section 3 This section describes the parts and functions of the configuration devices in the NJ-...
  • Page 6 Introduction Sysmac Studio Version 1 Operation Manual (Cat. No. W504) Section Description Section 1 This section provides an overview and lists the specifications of the Sysmac Studio Introduction and describes its features and components. Section 2 This section describes how to install and uninstall the Sysmac Studio. Installation and Uninstallation Section 3 This section describes the basic concepts for designing an NJ-series System with the...
  • Page 7 CJ-series 4-Channel Counter Unit Operation Manual (Cat. No. W02E) Section Description Section 1 This section gives specifications of the CJ1W-CTL41-E and a brief description of the Introduction functions and features of the Unit and the areas of application. Section 2...
  • Page 8: Manual Structure

    Introduction Manual Structure Page Structure The following page structure is used in this manual. Level 1 heading 4 Installation and Wiring Level 2 heading Mounting Units Level 3 heading Level 2 heading Gives the current Level 3 heading headings. 4-3-1 Connecting Controller Components The Units that make up an NJ-series Controller can be connected simply by pressing the Units together and locking the sliders by moving them toward the back of the Units.
  • Page 9 In this manual, “download” refers to transferring data from the Sysmac Studio to the physical Controller and “upload” refers to transferring data from the physical Controller to the Sysmac Studio. The terms “Counter Unit”, “4-Channel Counter Unit” and “CJ1W-CTL41-E” maybe be interchanged in this manual when referring to the CJ1W-CTL41-E 4-Channel Counter Unit.
  • Page 10: Sections In This Manual

    Introduction Sections in this Manual Introduction Components, Installation and Wiring Operation and Configuration Exchanging Data with CPU Error Processing Maintenance and Inspection Appendices Index CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 11 Introduction CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 12: Table Of Contents

    CONTENTS CONTENTS Introduction ......................1 Relevant Manuals ..................... 2 Manual Configuration ....................3 Manual Structure ...................... 6 Sections in this Manual ................... 8 CONTENTS ......................10 Read and Understand this Manual ............... 14 Safety Precautions ....................17 Precautions for Safe Use ..................22 Precautions for Correct Use ..................
  • Page 13: Contents

    CONTENTS 2-3-2 Connector Wiring Methods ......................2-8 2-3-3 Important Wiring Considerations ....................2-9 2-3-4 Internal Circuitry ........................2-10 2-3-5 Counter Input Configuration ..................... 2-10 Section 3 Operation and Configuration Overview ..........................3-2 3-1-1 Summary ........................... 3-2 3-1-2 List of Functions/Allocation Areas by Purpose ................3-2 Counter Types .........................
  • Page 14 CONTENTS Maintenance and Inspection ....................5-10 5-4-1 Cleaning ........................... 5-10 5-4-2 Routine Inspections ........................5-10 Appendices A-1 Differences of NJ Series from CJ Series ................A-2 A-1-1 Functional Difference .........................A-2 A-1-2 Differences in Access Methods from a User Program ...............A-3 A-2 Using Terminal Block Units with Screw-terminals ............A-14 A-3 Application Restrictions ......................A-16 Index CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 15 CONTENTS CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 16: Read And Understand This Manual

    WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS...
  • Page 17 Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products.
  • Page 18 Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
  • Page 19: Safety Precautions

    Safety Precautions Definition of Precautionary Information The following notation is used in this manual to provide precautions required to ensure safe usage of an NJ-series Controller. The safety precautions that are provided are extremely important to safety. Always read and heed the information provided in all safety precautions. The following notation is used.
  • Page 20 Symbols The circle and slash symbol indicates operations that you must not do. The specific operation is shown in the circle and explained in text. This example indicates prohibiting disassembly. The triangle symbol indicates precautions (including warnings). The specific operation is shown in the triangle and explained in text. This example indicates a precaution for electric shock.
  • Page 21 WARNING During Power Supply Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock. Do not attempt to take any Unit apart. In particular, high-voltage parts are present in the Power Supply Unit while power is supplied or immediately after power is turned OFF.
  • Page 22 WARNING Fail-safe Measures Unintended outputs may occur when an error occurs in variable memory or in memory used for CJ-series Units. As a countermeasure for such prob- lems, external safety measures must be provided to ensure safe operation of the system. Provide measures in the communications system and user program to ensure safety in the overall system even if errors or malfunctions occur in data link communications or remote I/O communications.
  • Page 23 Caution Application Do not touch any Unit when power is being supplied or immediately after the power supply is turned OFF. Doing so may result in burn injury. Wiring Be sure that all terminal screws and cable connector screws are tightened to the torque specified in the relevant manuals.
  • Page 24: Precautions For Safe Use

    Precautions for Safe Use Disassembly and Dropping • Do not attempt to disassemble, repair, or modify any Units. Doing so may result in malfunction or fire. • Do not drop any Unit or subject it to abnormal vibration or shock. Doing so may result in Unit malfunc- tion or burning.
  • Page 25 • Do not apply voltages or connect loads to the Output Units or slaves in excess of the maximum rat- ings. • Surge current occurs when the power supply is turned ON. When selecting fuses or breakers for external circuits, consider the above precaution and allow sufficient margin in shut-off performance. Refer to the relevant manuals for surge current specifications.
  • Page 26 The Power Supply Unit may continue to supply power to the rest of the Controller for a few seconds after the power supply turns OFF. The PWR indicator is lit during this time. Confirm that the PWR indicator is not lit before you perform any of the above. Operation •...
  • Page 27 • You cannot upload or download information for forced refreshing with the Sysmac Studio. After downloading data that contains forced refreshing, change to RUN mode and then use the Sys- mac Studio to perform the operation for forced refreshing. Depending on the difference in the forced status, the control system may operate unexpectedly. •...
  • Page 28 • EtherCAT communications are not always established immediately after the power supply is turned ON. Use the system-defined variables in the user program to confirm that communications are estab- lished before attempting control operations. • If frames sent to EtherCAT slaves are lost due to noise or other causes, slave I/O data is not commu- nicated, and the intended operation is sometimes not achieved.
  • Page 29 Unit Replacement • We recommend replacing the Battery with the power turned OFF to prevent the CPU Unit’s sensitive internal components from being damaged by static electricity and to prevent malfunctions. The Bat- tery can be replaced without turning OFF the power supply. To do so, always touch a grounded piece of metal to discharge static electricity from your body before you start the procedure.
  • Page 30: Precautions For Correct Use

    Precautions for Correct Use Storage, Mounting, and Wiring • Do not operate or store the Controller in the following locations. Operation may stop or malfunctions may occur. • Locations subject to direct sunlight • Locations subject to temperatures or humidity outside the range specified in the specifications •...
  • Page 31 Error Processing • In applications that use the results of instructions that read the error status, consider the affect on the system when errors are detected and program error processing accordingly. For example, even the detection of a minor error, such as Battery replacement during operation, can affect the system depending on how the user program is written.
  • Page 32 SD Memory Cards • Insert the SD Memory Card all the way. • Do not turn OFF the power supply to the Controller during SD Memory Card access. The files may be corrupted. If there is a corrupted file in the SD Memory Card, the file is automatically deleted by the restoration function when the power supply is turned ON.
  • Page 33 Concepts  EMC Directive OMRON devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards.* Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
  • Page 34 The NJ-series Controllers comply with the following shipbuilding standards. Applicability to the ship- building standards is based on certain usage conditions. It may not be possible to use the product in some locations. Contact your OMRON representative before attempting to use a Controller on a ship.
  • Page 35: Unit Versions

    □ DDMYY: Lot number, : For use by OMRON, xxxx: Serial number “M” gives the month (1 to 9: January to September, X: October, Y: November, Z: December) MAC address Gives the MAC address of the built-in port on the Unit.
  • Page 36 Right-click any open space in the Unit Editor and select Production Information. The Production Information Dialog Box is displayed. Simple Display Detailed Display In this example, “Ver.1.0” is displayed next to the unit model. The following items are displayed. CPU Unit CJ-series Units Unit model Unit model...
  • Page 37: Related Manuals

    Studio. tions of the Sysmac Studio. CJ-series 4-Channel W512) CJ1W-CTL41-E Learning about the func- The functions and usage of the CJ-series 4- Counter Unit Operation tions and usage of CJ- Channel Counter Unit for using it in an NJ-series...
  • Page 38: Revision History

    Revision History A manual revision code appears as a suffix to the catalog number on the front and back covers of the manual. W512-E2-01 Cat. No. Revision code Revision code Date Revised content September 2011 Original production CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 39: Introduction

    Introduction This section gives specifications of the CJ1W-CTL41-E and a brief description of the functions and features of the Unit and the areas of application. 1-1 Features and Functions ......... 1-2 1-2 Basic Configuration .
  • Page 40: Features And Functions

     CJ1W-CTL41-E Counters The CJ1W-CTL41-E 4-Channel Counter Unit is equipped with 4 Counters and counts over a maxi- mum binary range of 32-bits. Accepting input pulse frequencies of up to 100 kHz allows precise con- trol of fast motions. The Unit’s bi-directional counting ability allows movement detecting in either direction.
  • Page 41 1 Introduction In Range Mode, a configurable number of up to 4 Ranges can be applied to individual Counters. Every Range can control up to a maximum of 32 Software Outputs. An Output is turned ON when the Counter is in the corresponding Range. In Comparison Mode a configurable number of up to 8 Comparison Values can be applied to individ- ual Counters.
  • Page 42: Basic Configuration

    1 Introduction Basic Configuration  Mounting Restrictions The CJ1W-CTL41-E 4-Channel Counter Unit is a Special I/O Unit that belongs to the CJ Series. The CJ1W-CT41-E 4-Channel Counter Unit can be mounted in an NJ-series CPU rack or NJ-series Expansion Rack.
  • Page 43 Indirectly connecting the wires by connecting them to screwless terminals on an XW2G-40G7-E Input Terminal Block Unit. This Input Terminal Block Unit allows connection of Line Driver or 24 V Encoder signals. The XW2G-40G7-E is connected to the Unit via standard available OMRON I/O-cables (XW2Z-xxxK).
  • Page 44: Specifications And Characteristics

    1 Introduction Specifications and Characteristics 1-3-1 General Specifications Item CJ1W-CTL41-E Unit type Special I/O Unit General Specifications Conform to general specifications for NJ-series 0 to 55 C Operating Temperature -20 to 70 C Storage Temperature Humidity 10% to 90% without condensation...
  • Page 45: Input Specifications

    1 Introduction Item CJ1W-CTL41-E Reset Signals Every Counter can be reset to zero by (a combination of) the following sources: • Software Counter Reset Bit • Z-Input Refer to section 3-6 Reset Signals. Extra Functions Hysteresis: To prevent Outputs from being switched On and Off by very small fluctua- tions in the Counter Value around Range Limits, for every Counter an Hysteresis-value [1, 255] can be defined (the Unit must in Range Mode).
  • Page 46 1 Introduction Counter Inputs A, B and Z 24V input signals (via Input Terminal Block) RS-422 Line Driver signals Counter inputs A and B Counter inputs A and B Input pulses with a duty factor of 50% Input pulses with a duty factor of 50% Relationship between A and B phases with phase Relationship between A and B phases with phase differential inputs...
  • Page 47 1 Introduction Additional Information As a general guideline it can be stated that if you want the timing requirements for the Counter Inputs to satisfy the above mentioned specifications, you must pay attention to the type of output driver of the encoder being used, the length of the encoder cable and the frequency of the count pulses generated.
  • Page 48: Quick Start Up Reference Guide

    1 Introduction Quick Start Up Reference Guide  Operation and Configuration Each individual Counter of the Counter Unit can be configured as Circular or Linear Counter (refer to section 1-5 Operating Procedure Guidelines for quick start up information). The diagram below shows the functions the Unit has available to operate and configure the Unit (refer to Section 3, Operation and Configuration).
  • Page 49  Specifying indirect addresses for Circular/Linear Counters and Allocating them to user-defined variables CJ1W-CTL41-E 4-Channel Counter Units are set with the Special Unit Setup Editing of Sysmac Stu- dio. When the contents of the Special Unit setup are transferred to the CPU unit, they are reflected in the device variables for CJ-series Unit (for setting).
  • Page 50: Operating Procedure Guidelines

    1 Introduction Operating Procedure Guidelines The operating procedures for the Counter Units are described here. There is no restriction regarding the sequence of "Programs and software settings" and "Hardware set- ting and rack assembly." These tasks may be carried out concurrently or in the reverse order. Use Sysmac Studio to create and set programs.
  • Page 51 1 Introduction Details of Hardware Setting and Rack Assembly  Set the Unit number Set the Machine Number. Refer to 2-1-3 Machine Number Switch for further details. Machine Number Switch: MACH × × Set between 00 - 92  Mounting and wiring to the Rack Install and wire the Unit.
  • Page 52: Application Areas

    Counter Values. Application areas include: • Packaging and Sorting plants • Dosing or proportioning plants • Process Industry Typical applications in which the CJ1W-CTL41-E can be used: • (CAM)-Positioning • Position Monitoring • Length Measurement • Flow Control •...
  • Page 53: Components, Installation And Wiring

    This section provides details of the components, switch settings and other information required to install and operate CJ1W-CTL41-E 4-Channel Counter Units. 2-1 Components and Switch Settings ....... . 2-2 2-1-1 Components .
  • Page 54: Components And Switch Settings

    2 Components, Installation and Wiring Components and Switch Settings 2-1-1 Components  Front and Side View 83.6 CTL41 Indicators Machine Number Switch Units in mm 2-1-2 Indicators CTL41 The indicators on the front display show the operating status of the Unit. The following table shows the meaning of the indicators.
  • Page 55: Machine Number Switch

    2 Components, Installation and Wiring Indicator Color State Description CPU Unit has operational failure. (For a list of all the errors that can occur at the CPU Unit see 5-1 Error Indica- tors) CPU Unit has no operational failure. Yellow Counter 1 is counting, i.e.
  • Page 56 2 Components, Installation and Wiring • One Counter Unit occupies allocation areas of four unit numbers. Be sure that no unit num- bers are duplicated. To avoid duplication, when you set a High-speed Counter Unit to the unit number "n", set the next Special I/O Unit to the unit number "n + 4". •...
  • Page 57: Installation

    • Be sure to turn OFF the power supply to the CPU before installing or removing Units or con- necting or disconnecting connectors. Use the following procedure to install CJ1W-CTL41-E Counter Units. Connect the Units before mount- ing them to DIN-rail.
  • Page 58 2 Components, Installation and Wiring Attach an End Plate to the Unit on the right end of the Rack. Precautions for Safe Use The Units may not function properly if the sliders are not locked into place. Always connect the End Plate to the right most Unit.
  • Page 59: Wiring

    • RS-422 Line Driver, either directly connected to the connector on the front of the Unit or through a separate Input Terminal Block, e.g. the OMRON XW2G-40G7-E or XW2D-40G6. • 24 VDC signals from NPN or PNP Drivers, only through the separate OMRON XW2G-40G7- E Input Terminal Block.
  • Page 60: Cj-Series 4-Channel Counter Unit Operation Manual For Nj-Series Cpu Unit (W512)

    • Be sure that all the connectors are wired correctly and properly connected to the Counter Unit, to prevent the Unit from malfunctioning. To wire the CJ1W-CTL41-E in order to connect the external signals three methods are available: Directly connecting the wires and cables to an external connector. Recommended connectors are 40-pin MIL-C-83503 (or DIN 41651 or IEC 60603-1) compatible 40-pole connectors.
  • Page 61: Important Wiring Considerations

    • XW2Z-500K (5 m) The next figure shows how to use the Terminal Block Unit in a typical configuration together with the CJ1W-CTL41-E Counter: Refer to section A-2 Using Terminal Block Units with Screw-terminals for information on the number- ing of the screw-terminals. You need this information in case you want to connect the external sig- nals via Terminal Block Units to the Counter Unit.
  • Page 62: Internal Circuitry

    2 Components, Installation and Wiring • Use a separate stabilized Power Supply for the Counter Unit and another Power Supply for other Units. 2-3-4 Internal Circuitry  Counter Input Circuitry The figure below shows the internal input circuitry for all three digital input signals for each of the four Counter channels.
  • Page 63 2 Components, Installation and Wiring  Line Driver (RS422) CJ1W-CTL41-E Counter Unit Terminals: Black: Phase A+ (Phase A, LD+) Black/red: Phase A- (Phase A, LD-) Encoder White: Phase B+ (Phase B, LD+) White/red: Phase B- (Phase B, LD-) Orange: Phase Z+...
  • Page 64 2 Components, Installation and Wiring 2-12 CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 65: Operation And Configuration

    Operation and Configuration This section describes how to configure the CJ1W-CTL41-E 4-Channel Counter Unit and how to operate the Unit according to the specific requirements of your application. 3-1 Overview ........... . . 3-2 3-1-1 Summary .
  • Page 66: Overview

    3-1-1 Summary You can make the Unit settings after you complete registration of the CJ1W-CTL41-E 4-Channel Coun- ter Unit to the Unit Configuration and registration of device variables for CJ-series Unit. Unit settings are made with Special Unit Setup Editing of Sysmac Studio. Alternatively, set device vari- ables for CJ-series Unit (for setting) (refer to section 4-1 Overview) in the user program.
  • Page 67: 3-2-1 Circular Counter

    3 Operation and Configuration Counter Operations Name of Explanation of functions used device variable Name of device variable Purpose (reference) for CJ-series Unit for CJ-series Unit (for setting) (for input/output) When used for Linear 3-2-2 Linear Counter • Ranges/Compari- • Output Control Mode/AND/OR Counter operation son Values active Counter Output Patterns...
  • Page 68: Counter Types

    3 Operation and Configuration Counter Types Every individual counter of the Counter Unit can be set independently to one of the following counter Types (for an overview of the differences between Circular and Linear Counters refer to section 1-4 Quick Start Up Reference Guide): •...
  • Page 69: Linear Counter

    3 Operation and Configuration 1 ≤ Upper Count Limit ≤ 4,294,967,295 00000001 ≤ Upper Count Limit ≤ FFFFFFFF (=00000000 ) Rollover Down Counting Counting Counter Value  Configuring Upper Count Limit The Upper Count Limit can be configured between 1 and 4,294,967,295. By default the Upper Count Limit is equal to the maximum possible count limit of 4,294,967,295.
  • Page 70 3 Operation and Configuration −2,147,483,648 ≤ Lowercount Limit ≤ −1 1 Uppercount Limit +2,147,483,647 Up Counting Counter Value Down Counting Underflow Overflow If the Counter Value goes above the Upper Count Limit or below the Lower Count Limit an Overflow and Underflow flag will be set respectively in the device variable for CJ-series Units.
  • Page 71 3 Operation and Configuration Name of device variable Type Name Function for CJ-series Unit *_Ch1_CtOvf BOOL Counter Overflow Counter Overflow 0: Upper Count Limit of Linear Counter is not *_Ch2_CtOvf reached *_Ch3_CtOvf 1: Upper Count of Limit of Linear Counter is *_Ch4_CtOvf reached.
  • Page 72: Input Signal Types

    3 Operation and Configuration Input Signal Types The type of input you require for your application is selected by means of the device variable for CJ- series Units (for setting). For every Counter the Signal Type can be selected individually. Name of device variable Type Name...
  • Page 73: Up & Down Pulse

    3 Operation and Configuration  Multiplication x2 To increase the resolution of the incremental encoder the Counter can be configured for Multiplica- tion by 2. If the Counter is up-counting (signal A leads to signal B) pulses are taken into account by the Counter on the rising- and falling edges of signal A.
  • Page 74 3 Operation and Configuration Counter Incremental encoder Input A or other pulse Count pulse generator Input B Sensor or Input Z switch Direction control Count pulse Direction control: High = Increment Low = Decrement Additional Information For Counter Reset options refer to section 3-6 Reset Signals. 3-10 CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 75: Controlling A Counter

    3 Operation and Configuration Controlling a Counter Each Counter Input contains a gate through which the counting function can be enabled or disabled. When disabled, the gate will block incoming counter signals. The Gate of a Counter can be enabled and disabled with the following device variables for CJ-series Units (for setting).
  • Page 76 3 Operation and Configuration  Reset Function To reset a Counter, through a signal pulse on the corresponding Z-input, the Z-input Reset Enable bit must be set to 1. A Counter can also be reset by using the device variable for CJ-series Units. Setting this bit to ‘1’...
  • Page 77: Output Control

    3 Operation and Configuration Output Control  Output Control Mode The 32 Soft (internal) outputs of the Counter Unit can be controlled automatically in two ways: • Range Mode: In Range Mode you can define up to a maximum of 4 Ranges per Counter. The Outputs are controlled according to the Counter Value being within Range Limits.
  • Page 78: Range Mode

    3 Operation and Configuration Name of device variable Type Name Function for CJ-series Unit *_OutStaDat DWORD Output Status The current statuses of the internal outputs (total of 32) are all displayed. 0: FALSE 1: TRUE Bit 00: Internal output 00 Bit 01: Internal output 01 Bit 31: Internal output 31 *_OutSta0 to *_OutSta31...
  • Page 79 3 Operation and Configuration In the above example the Counter Value is within Range 1 and 3 and consequently the Outputs 0, 1 and 3 are changed to TRUE.  Example Range Mode with Circular Counter Range 2 Maximum Count Limit 4,294,967,295 (=00000000 ) (= FFFFFFFF...
  • Page 80 3 Operation and Configuration Range 0 Counter 1 Upper Range Limit Output Pattern Lower Range Limit Output Pattern Range 3 Upper Range Limit Output Pattern Lower Range Limit Range 0 Counter 2 Upper Range Limit Output Pattern Lower Range Limit Output Pattern Range 3 Upper Range Limit...
  • Page 81 3 Operation and Configuration The Counter Type (Circular or Linear) determines the range in which the Upper and Lower Limits can be set. For Circular Counters this range is 0 to 4,294,967,295 and for Linear Counters this range is -2,147,483,648 to 2,147,483,647. For Linear Counters the Upper Range Limit must be greater than the Lower Range Limit.
  • Page 82 3 Operation and Configuration 3.2-kHz pulse Counter Value Range Data 0 Upper Range Limit Lower Range Limit Range Data 1 Upper Range Limit Lower Range Limit Range Data 2 Upper Range Limit Lower Range Limit Comparison stops for 1.5 ms Counter Value matches During this period, the output set under the output Lower Limit (falls within...
  • Page 83 3 Operation and Configuration  Enabling and Disabling of Ranges Each range condition can be enabled/disabled separately. When a pair of range conditions is set to disabled (the default setting), that output pattern is ignored when the unit output pattern is calcu- lated.
  • Page 84: Comparison Mode

    3 Operation and Configuration Additional Information The Counter Output Patterns of Counters which are configured to use no (i.e. zero) Ranges, are ignored in the AND-calculation of the Unit Output Pattern. Like this, Counters that you do not want to use, do not influence the AND-calculation of the Unit Output Pattern. If both the Counters are configured to use no Ranges, the output patterns for both outputs will be all OFF.
  • Page 85 3 Operation and Configuration In this example 7 Comparison Values are specified. On reaching a Comparison Value an Output can be Set or Reset depending on the crossing direction. If the CV is crossed in the positive counting direction (+CV crossing) or negative counting direction (-CV crossing), one or multiple Outputs can be Set (S) or Reset (R).
  • Page 86 3 Operation and Configuration Counter 1 +Set Pattern CV0 +Reset Pattern CV0 Comparison Value 0 -Set Pattern CV0 -Reset Pattern CV0 +Set Pattern CV7 +Reset Pattern CV7 Comparison Value 7 -Set Pattern CV7 -Reset Pattern CV7 Counter 2 +Set Pattern CV0 +Reset Pattern CV0 Comparison Value 0 -Set Pattern CV0...
  • Page 87 3 Operation and Configuration • Comparison Value (can be set between 2,147,483,648 and 2,147,483,647 for a Linear Counter and between 0 and 4,294,967,295 for a Circular Counter) • Output Set Pattern for the positive counting direction (+Set Pattern CV‘n’), specifying which Outputs must be Set on reaching that CV in the positive counting direction (0 = No Change, 1 = Set Output) •...
  • Page 88 3 Operation and Configuration Additional Information Precautions When Setting Comparison Data • Comparison Stoppage When Comparison Value Reached When the Counter Value reaches a comparison value, comparison stops for 1.5 ms. The other Counters, however, do not stop comparisons. Set the Comparison Data considering the time when the comparison is stopped. For example, for the Comparison table shown in the following diagram, approximately 4.8 counts occur during 1.5 ms when a 3.2 kHz pulse is input.
  • Page 89 3 Operation and Configuration Name of device variable Type Name Function for CJ-series Unit *_Ch1_RngCmpDatSta WORD Ranges/Comparison The current status of the comparison condi- Values active tions is shown. *_Ch2_RngCmpDatSta Bits 00 to 31 correspond to comparison con- *_Ch3_RngCmpDatSta ditions 0 to 31. *_Ch4_RngCmpDatSta Each bit shows 1 when the conditions are met and 0 when they are not.
  • Page 90 3 Operation and Configuration  Updating Unit Output Pattern with Preset or Reset Action Besides by crossing CV’s the Unit Output Pattern can also be updated by a Preset or a Reset action. To trigger a Preset or Reset action refer to section 3-4 Controlling a Counter and section 3-6 Reset Signals.
  • Page 91: Reset Signals

    3 Operation and Configuration Reset Signals For every Counter a reset of the Counter Value to zero can be triggered by the following Sources: • Software Reset Bit • Z-signal In order for a Digital Input or the Z-Signal to trigger a reset, the Reset Enable Bit must be set to 1. CIO Reset Bit Reset Trigger Rising Z-Signal...
  • Page 92 3 Operation and Configuration Name of device variable Type Name Function for CJ-series Unit *_Ch1_RstEnbl BOOL Reset Enable Reset Enable setting 0: Disable *_Ch2_RstEnbl 1: Enabled *_Ch3_RstEnbl *_Ch4_RstEnbl 3-28 CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 93: Extra Functions

    3 Operation and Configuration Extra Functions 3-7-1 Hysteresis An encoder can come to rest at a particular position and then “oscillate” around this position. This state means that the Counter Value fluctuates around a particular value. If, for example, a Range Limit is in this area of fluctuation, the corresponding Range would become active and inactive in the rhythm of these fluctuations.
  • Page 94: Initial Counter Value

    3 Operation and Configuration 3-7-2 Initial Counter Value Every Counter has device variables for CJ-series Unit for setting (double word) the initial Counter Val- ues. The settings for these variables are transferred from the CPU Unit to this unit when the Unit restarts or the Controller is reset, including when the power is turned ON.
  • Page 95: Exchanging Data With Cpu

    Exchanging Data with CPU This section provides information on exchanging data between CJ1W-CTL41-E 4- Channel Counter Units and NJ-series CPU Units. 4-1 Overview ........... . . 4-2 4-1-1 Data Flow .
  • Page 96: Overview

    4 Exchanging Data with CPU Overview 4-1-1 Data Flow The CPU Unit and the high-speed Counters exchange data via the I/O port created for the Counter Unit. The table and figure below show the data exchange method for each data type. Data exchange type AT specification How to access...
  • Page 97 4 Exchanging Data with CPU NJ-series CPU Unit CJ1W-CTL41 Unit User program I/O port Inputs General Device variables for General Unit I/O AT specification CJ-series Unit Counter 1-4 Data I/O refresh Outputs General Counter Specific Device variables for AT specification I/O Data CJ-series Unit Counter 1-4...
  • Page 98: Unit Restart

    4 Exchanging Data with CPU AT specification of variables used to access these parameters/data is determined with the following. Unit data type AT specification destination Setting Method For Inputs I/O port (for Inputs, Outputs) Created automatically when the Unit is registered to the Unit Configuration.
  • Page 99: Access From User Program

    4 Exchanging Data with CPU 4-1-3 Access from User Program Various data are exchanged from the user program using the following variables. Data type Access method Refresh timing For settings Device variable for CJ-series When the Controller is reset or Units the unit restarts For Outputs...
  • Page 100 4 Exchanging Data with CPU Additional Information For details on creation of device variables for CJ-series Unit, refer to Sysmac Studio Version 1 Operation Manual (Cat. No. W504). In the explanations from here on, the device name automatically created is used as the device variable for CJ-series Unit, for example *_Ch1_Prst.
  • Page 101: Memory Allocation

    4 Exchanging Data with CPU Memory Allocation 4-2-1 Memory Mapping The data to be used when operating in Range mode or Comparison mode are allocated to any DM or EM Area (bank 0). This allocation method is called extended allocation. For details, refer to 4-2-2 Allo- cating Ranges and Comparison Data.
  • Page 102: Allocating Ranges And Comparison Data

    4 Exchanging Data with CPU Data assigned to Counters 1-4 can be allocated to any DM or EM address. When this data is over- lapped (duplicated), the Unit treats the overlap as a warning and "*_IABlkOverlapSta" (IA Blocks overlap) becomes 1. But this is not an error. In other words, by defining one range data or compari- son data and setting the same indirect address in more than one location (k1 = k2), that data can be shared by more than one Counter.
  • Page 103 4 Exchanging Data with CPU k(c) Comparison data 0 Special I/O Unit DM-Area: Comparison data 1 Comparison data 2 # of Comparison data M (0 ≤ M ≤ 8) Comparison data EM (=0) / DM (=1) Size of CV Data block: Area Number of CV's (= M) x 10 words Indirect address k(c)
  • Page 104 4 Exchanging Data with CPU D1850 Data Range 0: Data Range 0 2 x 6 words = D1856 12 words Data Range 1 D1850 Lower Range Limit D1851 D1852 Upper Range Limit D1853 D1854 Output Pattern D1855 For an overview of all addresses related to range data refer to 4-2-5 Memory Allocation for Ranges ...
  • Page 105 4 Exchanging Data with CPU Allocation to User-defined Variable With Sysmac Studio, you can specify an AT (allocation destination) for the DM/EM area that you secured for ranges or comparison data by specifying indirect addresses (see page 4-8). With user- defined variables, it is possible to specify an arbitrary variable name.
  • Page 106: Details Of Device Variables For Cj-Series Unit (For Input/Output)

    4 Exchanging Data with CPU Variable tables Variable name Array Data type CmpData [0..3] _sCJCTL41_Ex_RngLin D01850 CmpData[0].LowLmt Range data Lower limit range 0 CmpData[0].UpLmt Upper limit CmpData[0].OutPat Output pattern CmpData[1].LowLmt Range data Lower limit range 1 6 x 4 = 24 words CmpData[03].LowLmt Range data Lower limit...
  • Page 107 4 Exchanging Data with CPU Name of device variable Type Name Function for CJ-series Unit *_Ch1_Rst BOOL 0 to 1: Counter reset (Resets Counter Values to 0) Reset *_Ch2_Rst Factory value: 0 *_Ch3_Rst *_Ch4_Rst *_Ch1_RstEnbl BOOL 0: Disable (factory value) Reset Enable *_Ch2_RstEnbl 1: Enables Z phase input, Digital Input reset...
  • Page 108 4 Exchanging Data with CPU  For Inputs Name of device variable Type Name Function for CJ-series Unit General *_OutStaDat DWORD Output Status The current statuses of external and internal output (total of 32) are all displayed. 0: FALSE 1: TRUE Bit 00: Internal output 0 Bit 01: Internal output 1 Bit 31: Internal output 31...
  • Page 109 4 Exchanging Data with CPU Name of device variable Type Name Function for CJ-series Unit *_Ch1_RngCmpSta0 BOOL Ranges/Comparison 1: Met, 0: Not met Values 0 active *_Ch2_RngCmpSta0 *_Ch3_RngCmpSta0 *_Ch4_RngCmpSta0 *_Ch1_RngCmpSta1 BOOL Ranges/Comparison 1: Met, 0: Not met Values 1 active *_Ch2_RngCmpSta1 *_Ch3_RngCmpSta1 *_Ch4_RngCmpSta1...
  • Page 110: Details Of Device Variables For Cj-Series Unit (For Setting)

    4 Exchanging Data with CPU Name of device variable Type Name Function for CJ-series Unit *_Ch1_CtUdf BOOL Counter Underflow 1: The lower count limit of the Linear Counter is reached. *_Ch2_CtUdf *_Ch3_CtUdf *_Ch4_CtUdf *_Ch1_CtRun BOOL Counter Run- 1: During Counter operation/while gate open ning/Gate Open *_Ch2_CtRun 0: While Counter stopped/while gate closed...
  • Page 111 4 Exchanging Data with CPU Name of device variable Type Name Function for CJ-series Unit General *_OutCtlMdCfg WORD Output Control Bits 00 to 07: Output Control Mode Mode/AND/OR Coun- Selects the Output Control Mode. ter Output Patterns 16#00: Range Mode (factory value) 16#01: Comparison Mode Bits 08 to 15: Counter output pattern AND/OR selection...
  • Page 112 4 Exchanging Data with CPU Name of device variable Type Name Function for CJ-series Unit *_Ch1_InitLinCtCfg DINT Initial Count Value Sets the initial Counter Value after unit setting data is transferred. *_Ch2_InitLinCtCfg Used for Simple Counter or Linear Counter. *_Ch3_InitLinCtCfg Data range: 2,147,483,648 to 2,147,483,647 *_Ch4_InitLinCtCfg Unit: Pulse...
  • Page 113: Memory Allocation For Ranges

    4 Exchanging Data with CPU 4-2-5 Memory Allocation for Ranges Range data are set in the user-defined variable. Refer to Allocation to User-defined Variable on page 11 for more information. Two types of structure data are prepared beforehand for range data user-defined variables: one type for Linear Counters and one type for Circular Counters.
  • Page 114: Memory Allocation For Comparison Data

    4 Exchanging Data with CPU Variable name Data type Item Function c2D[0].OutPat DWORD Range 0 Output Pattern Range 0 output pattern c2D[1] _sCJCTL41_Ex_ Range 1 Range 1 lower limit/upper limit values and output RngLin pattern c2D[2] _sCJCTL41_Ex_ Range 2 Range 2 lower limit/upper limit values and output RngLin pattern c2D[3]...
  • Page 115 4 Exchanging Data with CPU Use these structures to define user-defined variables. Data type (name) Member Data type Name _sCJCTL41_Ex_CmpLin CmpVal DINT Comparison value AddSetPat DWORD +Set pattern AddRstPat DWORD +Reset pattern Set pattern SubSetPat DWORD Reset pattern SubRstPat DWORD _sCJCTL41_Ex_CmpRing CmpVal UDINT...
  • Page 116 4 Exchanging Data with CPU Variable name Data type Item Function c1D[5] _sCJCTL41_Ex_ Comparison data 5 Comparison value, output (+/) set/reset pattern CmpLin c1D[6] _sCJCTL41_Ex_ Comparison data 6 Comparison value, output (+/) set/reset pattern CmpLin c1D[7] _sCJCTL41_Ex_ Comparison data 7 Comparison value, output (+/) set/reset pattern CmpLin Variable name...
  • Page 117 4 Exchanging Data with CPU Variable name Data type Item Function c3D[1] _sCJCTL41_Ex_ Comparison data 1 Comparison value, output (+/) set/reset pattern CmpRing c3D[2] _sCJCTL41_Ex_ Comparison data 2 Comparison value, output (+/) set/reset pattern CmpRing c3D[3] _sCJCTL41_Ex_ Comparison data Comparison value, output (+/) set/reset pattern CmpRing c3D[4] _sCJCTL41_Ex_...
  • Page 118 4 Exchanging Data with CPU 4-24 CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 119: Error Processing, Maintenance And Inspection

    Error Processing, Maintenance and Inspection This section provides details of the CJ1W-CTL41-E 4-Channel Counter Unit's error indicators and error codes and guidelines for maintenance and inspection of the Unit. 5-1 Error Indicators ..........5-2 5-1-1 Errors during initial processing .
  • Page 120: Error Indicators

    5 Error Processing, Maintenance and Inspection Error Indicators The RUN-, ERC-, and ERH indicators at the front panel of the Counter Unit, display the following errors. 5-1-1 Errors during initial processing Error Probable cause Remedy Setup error Incorrect Unit number Set correct Unit number and turn ON the power again Cyclic initial error...
  • Page 121: Error Codes

    5 Error Processing, Maintenance and Inspection Error Codes  Reporting errors Errors occurring in the Counter Unit are divided into the following 4 types. • Allocated DM area setting error • Overflow/underflow error • Preset error • System error There is an error code for each error. These error codes are made up of error code 1 and error code If an error occurs, the state becomes as follows.
  • Page 122: Dm-Configuration Errors

    5 Error Processing, Maintenance and Inspection 5-2-1 DM-configuration errors An allocated DM area setting error is detected during the initialization processing when the Controller is reset or the Unit is restarted. When an allocated DM area setting error is detected, the error information is stored into memory and the Counter Unit stops operation.
  • Page 123: Overflow/Underflow Errors

    5 Error Processing, Maintenance and Inspection  Clearing DM-configuration Errors DM-configuration errors can be cleared by correcting the faulty settings in device variables for CJ- series Unit (for setting) and consecutively transferring the new configuration data again to the Unit. To transfer the configuration data you can choose from one out of two possibilities: •...
  • Page 124 5 Error Processing, Maintenance and Inspection  Clearing Preset Error A Preset error can be cleared by resetting or by presetting the Counter that generated a Preset error, with a valid Preset Value. To reset a Counter refer to 3-6 Reset Signals. To preset a Counter refer to 3-4 Controlling a Counter.
  • Page 125: Event Log

    5 Error Processing, Maintenance and Inspection Event Log 5-3-1 Overview of the Event Logs The Event Log allows the user to access all of the events that occur on the NJ-series Controller includ- ing errors and information. You can use the Sysmac Studio or an NS-series PT to confirm current Con- troller events and the logs of events that have occurred.
  • Page 126: Error Table

    5 Error Processing, Maintenance and Inspection 5-3-3 Error Descriptions This section describes the information that is given for individual errors. Controller Error Descriptions The items that are used to describe individual errors (events) are described in the following copy of an error table.
  • Page 127: Error Descriptions

    5 Error Processing, Maintenance and Inspection Error Descriptions Event name Global Error Event code 68040000 hex Meaning One or more error has occurred. Errors codes are stored in the error list. Source Function Module Source details CJ-series Unit Detection Depends on the timing nature of the error.
  • Page 128: Maintenance And Inspection

    5 Error Processing, Maintenance and Inspection Maintenance and Inspection This section describes the routine cleaning and inspection recommended as regular maintenance. 5-4-1 Cleaning Clean the Counter Unit regularly as described below in order to keep it in its optimal operating condi- tion.
  • Page 129 5 Error Processing, Maintenance and Inspection  Inspection Procedure Check the items in the following table and correct any items that are not according to the criteria. Item Criteria Equipment Environmental Ambient temperature 0C to 55C Thermometer conditions Ambient humidity 10% to 90% Hygrometer Dust/dirt accumulation...
  • Page 130 5 Error Processing, Maintenance and Inspection 5-12 CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512)
  • Page 131 Appendix A-1 Differences of NJ Series from CJ Series ......A-2 A-1-1 Functional Difference ..........A-2 A-1-2 Differences in Access Methods from a User Program .
  • Page 132: Differences Of Nj Series From Cj Series

    Differences of NJ Series from CJ Series You can use the CJ1W-CTL41-E 4-Channel Counter Unit with the NJ-series Units. If this Unit is used with the NJ Series, some functions become unavailable compared to when it is used with the CJ Series.
  • Page 133: Differences In Access Methods From A User Program

    Appendix Item Function in CJ series Function in NJ series IORD Instruction, You can read or write the following data. The IORD/IOWR instruction cannot be used. IOWR Instruction • Allocated DM data Therefore, you cannot read or write the data on the left.
  • Page 134 Appendix • After correcting the Unit number setting, cycle the power to the Controller. • One Counter Unit occupies allocation areas of four Unit numbers. Be sure that no Unit num- bers are duplicated. To avoid duplication, when you set a High-speed Counter Unit to the Unit number "n", set the next Special I/O Unit to the Unit number "n + 4".
  • Page 135 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description General n+10 *_Ch2_Enbl Open Gate *_Ch2_Dsbl Close Gate *_Ch2_Prst Preset *_Ch2_Rst Reset Undefined Capture *_Ch2_RstEnbl Reset Enable 06 to 15 Undefined n+11, 00 to 15 *_Ch2_PrstLinCtVal (Linear Counter) Preset Value n+12...
  • Page 136 Appendix  Allocated CIO Area words for inputs CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description General n+13, 00 to 15 *_OutStaDat Output Status n+14 • 32 outputs status (corre- spond to n+13, n+14) n+13 *_OutSta0 Digital Output 00 Status...
  • Page 137 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description n+21 *_Ch1_CtOvf Counter Overflow *_Ch1_CtUdf Counter Underflow *_Ch1_CtRun Counter Running/Gate Open *_Ch1_CntDir Counter Direction *_Ch1_PrstSta Preset Activated *_Ch1_RstSta Reset Activated Undefined Capture Activated *_Ch1_ZSig Z-signal Activated 08 to 15 Undefined Counter 2...
  • Page 138 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description n+26 *_Ch3_RngCmpSta0 Range 0/Comparison 0 Value active *_Ch3_RngCmpSta3 Range 3/Comparison 3 Value active *_Ch3_RngCmpSta4 Comparison 4 Value active *_ Ch3_RngCmpSta7 Comparison 7 Value active n+27, 00 to 15 *_Ch3_LinCtVal (Linear Counter) Counter Value...
  • Page 139 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description n+33 *_Ch4_CtOvf Counter Overflow *_Ch4_CtUdf Counter Underflow *_Ch4_CtRun Counter Running/Gate Open *_Ch4_CntDir Counter Direction *_Ch4_PrstSta Preset Activated *_Ch4_RstSta Reset Activated Undefined Capture Activated *_Ch4_ZSig Z-signal Activated 08 to 15 Undefined 00 to 15...
  • Page 140 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description m+15, 00 to 15 *_Ch1_LowCtLmtCfg Lower Count Limit Linear m+16 m+17, 00 to 15 *_Ch1_InitLinCtCfg, *_Ch1_InitRingCtCfg Initial Count Value m+18 m+19, 00 to 15 *_Ch1_RngCmpEnblCfg Range/Comparison Enable m+20 Data...
  • Page 141 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description m+48, 00 to 15 *_Ch2_MemAdrCfg Memory Address m+49 Counter 3 m+50 00 to 15 *_Ch3_CtTypCfg Counter Type m+51 00 to 03 *_Ch3_SigTypCfg Signal Type 04 to 15 m+52 00 to 03 *_Ch3_ZOvfUdfCfg...
  • Page 142 Appendix CJ-series I/O NJ-series device variables for CJ-series Unit memory address Word Variable name Description m+75, 00 to 15 *_Ch4_LowCtLmtCfg Lower Count Limit Linear m+76 m+77, 00 to 15 *_Ch4_InitLinCtCfg, *_Ch1_InitRingCtCfg Initial Count Value m+78 m+79, 00 to 15 *_Ch4_RngCmpEnblCfg Range/Comparison Enable m+80 Data...
  • Page 143 Appendix CJ-series I/O memory address NJ-series device variables for CJ-series Unit Word Variable name Description k+6 to k+11 00 to 15 aaaa[1] Range 1 k+12 to k+17 00 to 15 aaaa[2] Range 2 k+18 to k+23 00 to 15 aaaa[3] Range 3 Comparison Data Comparison data is set in the user-defined variable.
  • Page 144: Using Terminal Block Units With Screw-Terminals

    This section describes the signal layout of the screw terminals on the Connector Terminal Converter Unit (XW2B-40G4, XW2B-40G5, XW2G-40G7-E, or XW2D-40G6). The Unit is used to connect external signals such as power supply signals, digital I/O signals, and Counter input signals to a CJ1W-CTL41-E Counter Unit.
  • Page 145 Appendix  Connections High-speed Counter Unit XW2B-40G4 XW2B-40G5 Screw terminal block terminal arrangement Additional Information The top row of the Terminal Block Unit (numbered 1 to 39) corresponds to the pins numbered A1 to A20 of the associated connector (CN1) on the Counter Unit. The bottom row of the Terminal Block Unit (numbered 2 to 40) corresponds to the pins numbered B1 to B20 of the associated connector (CN1) on the Unit.
  • Page 146: A-3 Application Restrictions

    Appendix A-3 Application Restrictions The following restrictions apply when using CJ1W-CTL41-E 4-Channel Counter Units. Restriction Reference The Open Gate, Close Gate, Preset Counter or Reset in device variables for CJ- 4-2 Memory Allocation series Unit (for output) may not be executed if the CPU Unit is ON for only one task period.
  • Page 147 Index CJ-series 4-Channel Counter Unit Operation Manual for NJ-series CPU Unit (W512) Index-1...
  • Page 148 Index Index Symbols +CV crossing ....... 3-21 Gate ........3-11 +Reset Pattern .
  • Page 149 Index Operating Procedure ......1-12 Underflow Error ......5-5 Output Control Mode .
  • Page 150 Buyer indemnifies Omron against all related costs or expenses. rights of another party. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-...
  • Page 151 OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON EUROpE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 • www.industrial.omron.eu Cat.

Table of Contents