Memory Switch Set 2 (3000-series, High-speed Type)
(Sequence No. 422 (Hex 01A6))
This sequence sets memory switches.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Offset
+0
Number of send data words
(4 digits Hex)
+1
w (1 digit BCD)
x (1 digit BCD)
y (1 digit BCD)
z (1 digit BCD)
+2
v (1 digit BCD)
Note Settings marked with asterisks are required for this protocol.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Additional Information
Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not
turned ON.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
+0
Number of send data words
+1
W
X
Y
+2
(Undefined)
Contents (data format)
A Standard System Protocol
Z
V
0003 (fixed)
0:
Work automatic detection is not performed
1:
Work automatic detection is performed
Diameter detection method (1 scan)
2:
Work automatic detection is performed
Diameter detection method (8 scan)
3:
Work automatic detection is performed
Position detection method (1 scan)
For expansion
0 (fixed)
For expansion
0 (fixed)
For expansion
0 (fixed)
*0: Error data exclusion function is not used
1: Error data exclusion function is used
Data
R-101