9 Troubleshooting and Maintenance
Event name
System Setup Error
Meaning
There is an error in the system settings for the Serial Communications Unit.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There is an error in the system set-
tings for the Serial Communications
Unit.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
Event name
DTR Check Error
Meaning
An error was found during the DTR check.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Loopback test jig failure.
Noise
The communications circuits in the
Serial Communications Unit are
faulty.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
None
Remarks
9-38
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Check the system settings for the
Serial Communications Unit and cor-
rect any problems.
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Correct any mistakes in wiring the
loopback test jig.
Implement noise countermeasures.
Replace the Unit.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event code
34A4 0000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Operation will be performed using the default setting for
the baud rate if there is an error in the baud rate setting.
Communications are not possible if there is an error in
other system settings.
Name
---
Prevention
Make the correct system settings for
the Serial Communications Unit.
Event code
0475 0000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Check the wiring of the loopback test
jig.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
None
At power ON or
Controller reset
System
During loopback
test
System