Omron CJ1W-SCU32 Operation Manual page 441

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

Offset
+0
Number of send data words
(4 digits Hex)
+1
Segment number (1 digit BCD)
+2
Measurement interval number
(1 digit BCD)
+3
Lower limit value (Decimal por-
tion) (4 digits BCD)
+4
Lower limit value (integer por-
tion) (3 digits BCD)
+5
Lower limit value (Sign)
(ASCII 1 character)
+6 to +8
Upper limit value
+9 to +11 Reference value
+12
Analog output scale number
(1 digit BCD)
+13 to
Unused
+15
+16
Data output conditions
(1 digit BCD)
+17
Data output timer value
(3 digits BCD)
+18
Number of seconds for latch
timer (2 digits BCD)
+19
Yes/No for segment setting
(1 digit BCD)
+20
Yes/No for measurement inter-
val number setting (1 digit BCD)
+21
Yes/No for upper/lower limit
value setting (1 digit BCD)
+22
Yes/No for reference setting
(1 digit BCD)
+23
Yes/No for data output condition
setting (1 digit BCD)
+24
Yes/No for latch timer setting
(1 digit BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Contents (data format)
A Standard System Protocol
0019 (0025 decimal) (fixed)
1 to 5
1 to 7
0000 to 9999
000 to 999
If +: 20 (' ')
If –: 2D ('–')
Same as lower limit value
Same as lower limit value
0 to 3
0 to 6
000 to 999
00 to 99
Set: 1(SG)
Don't set: 0
Set: 1(M)
Don't set: 0
Set: 1(LL, LH)
Don't set: 0
Set: 1(REF, SCL)
Don't set: 0
Set: 1(PR, PRT)
Don't set: 0
Set: 1(RLT)
Don't set: 0
Data
Example –123.4567
+3
4 5 6 7
+4
0 1 2 3
+5
2 D 0 0