Event name
Error Log Data Error
Meaning
An error occurred in the error log data.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There is a source of noise nearby.
Non-volatile memory failure
Attached
None
information
Precautions/
None
Remarks
Event name
Protocol Data Error
Meaning
A protocol data checksum error has occurred.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The communications connector with
the CX-Protocol was disconnected or
the power supply to the Controller
was interrupted during transfer of the
protocol data from the CX-Protocol.
The Serial Communications Unit
failed.
Attached
None
information
Precautions/
None
Remarks
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Implement noise countermeasures.
If the above cause does not apply,
replace the Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Transfer the protocol data again from
the CX-Protocol.
If this error occurs after transferring
the protocol data again, replace the
Serial Communications Unit.
9 Troubleshooting and Maintenance
Event code
04740000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply.
The Unit will stop if the error was detected in the self
check when the power supply was cycled or the Controller
was reset. Operation continues if the error occurs during
operation.
Name
---
Prevention
Use the Unit away from sources of
noise.
None
Event code
14800000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
The Serial Communications Unit will not operate in Proto-
col Macro Mode. This error has no affect on operation in
Host Link mode.
Name
---
Prevention
Do not interrupt the power supply to
the Controller during transfer of proto-
col data.
None
Continuously
System
At power ON or
Controller reset
System
9
9-37