9 Troubleshooting and Maintenance
Event name
Transmission Error (CRC Error)
Meaning
A CRC error occurred.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Noise
CRC calculation method does not
match the device.
Attached
Attached information 1: Port number where error was detected
information
Precautions/
You can check the number of transmission errors (i.e., CRC errors) in the *_P1_MbsCRCErrCnt and
Remarks
*_P2_MbsCRCErrCnt device variables.
9-52
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Implement noise countermeasures.
Correct the CRC calculation method
in the user application to match the
Modbus specifications.
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event code
846D 0000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
Set the CRC calculation method in
the user application to match the
Modbus specifications.
After serial com-
munications start
System

Hide quick links: