Omron CJ1W-SCU32 Operation Manual page 94

Machine automation controller, cj / nj-series, serial communications units, cpu unit
Table of Contents

Advertisement

2 Initial Settings and Allocations of Device Variable for CJ-series Unit
Serial Gateway Mode
Device variable for CJ-series Unit
Port 1
*_P1_SendDelayCfg
*_P1_SendDelaySetCfg
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you set this set-
ting, set to bits 00 to 14
of
*_P1_SendDelayCfg.
*_P1_HlkCTSCtlCfg
*_P1_PmrSgwTimeoutCfg
*_P1_PmrSgwResp
TimeoutCfg
*_P1_PmrSgwSend
TimeoutCfg
* When CTS control is enabled, the request to send signal (RTS) turns ON and the transmission starts after the clear to send
signal (CTS) turns ON. When CTS control is disabled, the request to send signal (RTS) turns ON and the transmission
starts without checking whether the clear to send signal (CTS) is ON.
2-20
Port 2
*_P2_SendDelayCfg
*_P2_SendDelaySetCfg
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you set this set-
ting, set to bits 00 to 14
of
*_P2_SendDelayCfg.
*_P2_HlkCTSCtlCfg
*_P2_PmrSgwTimeoutCfg
*_P2_PmrSgwResp
TimeoutCfg
*_P2_PmrSgwSend
TimeoutCfg
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Type
R/W
Name
WORD
RW
Send Delay
Settings
BOOL
RW
Send Delay
Time
Bit
RW
Send Delay
string
Time (User-
specified)
BOOL
RW
CTS Control (*) FALSE: No
WORD
RW
Serial Gateway
Timeout Moni-
toring Time
Setting
USINT
RW
Serial Gateway
Response Tim-
eout Monitor-
ing Time
USINT
RW
Serial Gateway
Send Start Tim-
eout Monitor-
ing Time
Function
Bits serve the functions
described below.
Bit 15: Send delay time
Bits 00 to 14: Send delay
Time (user-specified)
FALSE: Default (0 ms)
TRUE: User settings
0 to 300 s (0 to 300,000
ms)
(0000 to 7530 hex; 0 to
30,000 decimal) [Unit: 10
ms]
TRUE: Yes
Bits serve the functions
described below.
08 to 15: Serial Gateway
response timeout monitor-
ing time
00 to 07: Serial Gateway
send start timeout moni-
toring time
0: 5 s (default)
Data range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]
0: 5 s (default)
Range: 1 to 255
0.1 to 25.5 s [Unit: 100
ms]