TROUBLESHOOTING

14.3 List of errors

Division of
Error
Error name
error
code
000
(Normal)
001
Fault
003
Division by zero
Fatal error
004
Overflow
005
Underflow
Outside position
051
command range
Error at
selection of
stepping
motor mode
Outside speed
052
command range
Peripheral device
100
stop during
operation
Remote station
101
READY OFF
Common
during operation
Drive unit
102
READY OFF
Description of the errors and remedies are shown below.
Description
Hardware error
 The position data in the parameter is out of
the setting range for the stepping motor
mode.
 The positioning address or movement
amount setting in the positioning data is out of
the setting range for the stepping motor
mode.
 The speed data in the parameter is out of the
setting range for the stepping motor mode.
 The command speed setting in the
positioning data is out of the setting range for
the stepping motor mode.
A stop command is supplied during operation
from a peripheral device.
The remote station READY signal [RX(n+7)B]
is turned OFF during operation.
The "Drive unit READY" signal is turned OFF
during operation.
The system is stopped.
 The D75P2 READY signal (RXn0) does not
turn OFF.
 Failure to start.
 The D75P2 READY signal (RXn0) does not
turn OFF.
 Failure to start.
Stopping according to the sudden stop
(stopping group 2) setting (deceleration and
stop/sudden stop) selected in detail parameter
2 (However, deceleration and stop only during
manual pulse generator operation)
Stopping according to sudden stop (stopping
group 2) setting (deceleration and stop/sudden
stop) selected in detail parameter 2
(However, deceleration and stop only during
manual pulse generator operation)
Immediate stop.
14 - 8
MELSEC-A
Action at occurrence of error