INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
[Shielding wire processing example]
Wrap with insulating tape.
(10) Do not pull the cable when removing the cable from the D75P2 or drive unit. Hold
and pull the connector connected to the D75P2 or drive unit. If the cable
connected to the D75P2 or drive unit is pulled, a malfunction may be caused. As
well, the D75P2, drive unit or cable may be broken.
(11) Disconnect the external device connection connector when the system is
stopped.
If the external device connection connector is disconnected during operation of
the system, the system will be stopped.
(12) Do not tie the D75P2 cable with the main circuit cable, power cable, or a load
cable for other than the programmable controller or do not route the D75P2 cable
near them. Separate these by 100 mm as a measure. Otherwise noise, surge or
induction may cause a malfunction.
(13) When routing the D75P2 cable near a power cable at a distance smaller than
100 mm, use a shielded cable for a countermeasure against noise. Connect the
shielding wire of the shielded cable securely to the panel of the D75P2.
Ground a 2mm
in the shortest path.
(Ground to the panel of the D75P2 securely.)
Strip the sheath of the shielded cable.
Remove the shielding wires from the
shielded cable and solder them to the
grounding cable.
4 - 17
MELSEC-A
or a thicker grounding wire
2