Figure 152: Ied And Reb Switch Ip Address Configuration; Figure 153: Dip Switches For Setting Ip Address - GE P642 Technical Manual

Micom p40 agile transformer protection ied
Table of Contents

Advertisement

P64x
V01018

Figure 152: IED and REB switch IP address configuration

Note:
IP1 and IP2 are different but use the same subnet mask.
The labels "Switch Manager", "RSTP Configurator", "PRP Configurator", and "IED Configurator" refer to tools in the
Settings Application Software. You will need a computer loaded with the software to configure the elements of the
IP addresses with these labels. "SW2" refers to a dual in line (DIL) switch on the REB that needs to be set for some
protocols.
Procedures for setting the NIC IP address and the switch IP address are different. Procedures also vary according
to the chosen protocol. For some protocols, configuration needs to be carried out with the REB before installation
in its intended product. This is because access to the DIP switches shown in the figure, is required.
V01022

Figure 153: DIP switches for setting IP address

P64x-TM-EN-1.3
IED (IP1)
REB (IP2)
Set by Switch Manager for SHP and DHP
Set by RSTP Configurator for RSTP
Set by PRP /HSR Configurator for PRP or HSR
1
Example address
decimal 85
2
4
8
16
32
64
Unused
ON
SW2 Top view
Set by IED Configurator
AAA.BBB.CCC.DDD
WWW.XXX.YYY.ZZZ
Set by Hardware Dip Switch SW 2 for SHP, DHP, or RSTP
Set by PRP/HSR Configurator for PRP or HSR
Fixed at 254 for SHP, DHP, or RSTP
Set by PRP /HSR Configurator for PRP or HSR
1 + 4 + 16 + 64 = 85
Chapter 16 - Communications
327