Over Voltage; Encoder Error - Delta ASD-B2-0121-B User Manual

Asda-b2 series standard type ac servo drive for network communication application
Hide thumbs Also See for ASD-B2-0121-B:
Table of Contents

Advertisement

Chapter 5 Trial Run and Tuning Procedure
1) When display shows:

Over voltage:

The main circuit voltage has exceeded its maximum allowable value or input power is
error (Incorrect power input).
Corrective Actions:
Use voltmeter to check whether the input voltage falls within the rated input
voltage.
Use voltmeter to check whether the input voltage is within the specified limit.
2) When display shows:

Encoder error:

Check if the wiring is correct. Check if the encoder wiring (CN2) of servo motor is loose
or incorrect.
Corrective Actions:
Check if the users perform wiring recommended in the user manual.
Examine the encoder connector and cable.
Inspect whether wire is loose or not.
Check if the encoder is damaged.
3) When display shows:
Emergency stop activated:
Please check if any of digital inputs DI1~DI9 signal is set to "Emergency Stop" (EMGS).
Corrective Actions:
If it does not need to use "Emergency Stop (EMGS)" as input signal, the users only
need to confirm that if all of the digital inputs DI1~DI8 are not set to "Emergency
5-4
Revision June 2010