P1 - 52
RES1
Default: -
Applicable Control Mode: ALL
Unit: Ohm
Range: 10 ~ 750
Data Size: 16-bit
Display Format: Decimal
Settings:
This parameter is used to set the resistance of the applicable regenerative resistor.
For 750W models
For 1kW to 3kW models
P1 - 53
RES2
Default: -
Applicable Control Mode: ALL
Unit: Watt
Range: 30 ~ 3000
Data Size: 16-bit
Display Format: Decimal
Settings:
This parameter is used to set the capacity of the applicable regenerative resistor.
For 750W models
For 1kW to 3kW models
P1 - 54
PER
Default: 1600
Applicable Control Mode: PT
Unit:
Range: 0 ~ 1280000
Data Size: 32-bit
Display Format: Decimal
Settings:
In PT mode, when the error pulse numbers is less than the setting value of
parameter P1-54, TPOS (At positioning completed signal) will be activated.
Revision June 2010

Regenerative Resistor Value

Model

Regenerative Resistor Capacity

Model

Positioning Completed Width

pulse
Default
100Ω
40Ω
Related Section: Section 6.6.3
Default
60W
60W
Chapter 7 Servo Parameters
Address: 0168H, 0169H
Related Section:
Section 6.6.3
Address: 016AH, 016BH
Address: 016CH, 016DH
Related Section: Table 7.B