Entering Motor Data - Siemens Sinamics G120P Instruction Manual

Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Entering motor data

In the next step, the converter is adjusted to the motor. The motor data can be found on the motor
rating plate. Please set the values according to the rating plate.
• Press OK to edit the motor voltage stored under P304
• The preset motor voltage of 400 volts is displayed
• Keep the value and confirm by pressing OK
1
2
3
4
5
6
Operator Panels BOP-2 and IOP-2:
34
OK
OK
2
4
6
P304 = MOT VOLT = motor voltage
P100 = EUR USA = standard IEC or NEMA
P305 = MOT CURR = motor rated current
P307 = MOT POW = motor rated power
P311 = MOT RPM = motor rated speed
P308 = MOT COS PHI = Rated Motor power factor
The line frequency has been set already
in the beginning of quick commissioning
(see page 31).
Quick commissioning
1
3
5
If you want to adjust any flash-
ing value digit by digit (using the
UP and DOWN button might take
too long) continuously press the
OK button for longer than two
seconds. After releasing the but-
ton, you can change each single
digit by using the buttons OK
(move to next digit), ESC (move
to previous digit), UP (increase
value) and DOWN (decrease
value).
NOTE