Setting Motor Data; Setting Connection Macros - Siemens SINAMICS V20 Compact Operating Instructions

Up to 30 kw
Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Overview of connection and application macros
Connection macros (Page 18)
Cn000
No chosen connection macro
Cn001
BOP as the only control source
Cn002
Control from terminals
(PNP/NPN)
Cn003
Fixed speeds
Cn004
Fixed speeds in binary mode
Cn005
Analog input and fixed frequency Cn011
3.2.2

Setting motor data

Parameter
Description
P0100
50/60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
P0304[0] ●
Rated motor voltage [V]
P0305[0] ●
Rated motor current [A]
P0307[0] ●
Rated motor power [kW/hp]
P0308[0] ●
Rated motor power factor (cosφ)
Note: "●" indicates that the value of this parameter must be entered according to the rating plate of the motor. If P0100 = 1
(60 Hz [hp]), P0308[0] is invisible which indicates that this parameter is unnecessary for configuration.
3.2.3

Setting connection macros

Functionality
This menu selects which macro is required for standard wiring arrangements. The default one is "Cn000" for connection
macro 0.
Connection macros
Cn001 - BOP as the only control source
18
Cn006
External push button control AP000
Cn007
External push buttons with
analog control
Cn008
PID control with analog
reference
Cn009
PID control with the fixed
value reference
Cn010
USS control
MODBUS RTU control
Parameter
P0309[0] ●
P0310[0] ●
P0311[0] ●
P1900
Cn002 - Control from terminals (PNP/NPN)
External control - Potentiometer with setpoint
Both NPN and PNP can be realized with the same parame-
ters. You can change the connection of the digital input com-
mon terminal to 24 V or 0 V to decide the mode.
Application macros (Page 21)
Factory default setting
AP010
Simple pump applications
AP020
Simple fan applications
AP021
Compressor applications
AP030
Conveyor applications
Description
Rated motor efficiency [%]
Rated motor frequency [Hz]
Rated motor speed [RPM]
Select motor data identification
= 0: Disabled
= 2: Identification of all parameters in standstill
A5E37281078-003, 05/2016
SINAMICS V20 Inverter