3.5.2
Siemens AG
1. Select Options > Parameter settings > Reset drive to factory settings.
2. Confirm with OK.
 BOP-2
1. Select Options > DRVRESET in the menu.
2. Confirm with OK.

Setting the ramp-function generator

You can set the speed limits and the ramp-up and ramp-down times here.
Parameter
Possible settings
p1080
Minimum speed in [rpm]
p1082
Maximum speed in [rpm]
p1120
Ramp-up time of the motor after switching on in [s]
p1121
Ramp-down time of the motor after switching off in [s]
The minimum speed and maximum speed of the motor are dependent upon the
speed setpoint and the rated speed of the motor. Refer to the overview below:
% of the synchronous
Hz
speed
10
5
20
10
30
15
40
20
50
25
60
30
70
35
80
40
90
45
100
50
110
55
120
60
The ramp-up and ramp-down time define the maximum motor acceleration when
the speed setpoint changes. The ramp-up and ramp-down time is the time between
motor standstill and the maximum speed, or between the maximum speed and
motor standstill.
Factory settings:
Minimum speed [p1080] - factory setting 0 [rpm]
Maximum speed [p1082] - factory setting 1500 [rpm]
Acceleration time [p1120] - factory setting 10 s
Deceleration time [p1121] - factory setting 10 s
Recommended ramp times
0.37 – 3kW
4 – 15 kW
18.5 – 30 kW
37 – 90 kW
Commissioning
Additional settings
Four-pole motor (rpm)
Two-pole motor (rpm)
150
300
300
600
450
900
600
1200
750
1500
900
1800
1050
2100
1200
2400
1350
2700
1500
3000
1650
3300
1800
3600
30 s
60s
90s
120s
3
27
CM2G5111en
2014-05-16