Setting Measurement Target Circuit (TYPE) and Dedicated CT Type (CT)

Set the measurement target circuit (TYPE) and dedicated CT type (CT) in the same way as
the previous setting.
Refer to the FUN mode description for the measurement target circuit and dedicated CT
type details.
Reference: 4.2.4 (13) Measurement Target Circuit (TYPE), 4.2.4 (14) Dedicated CT Type
(CT)
(4)

Setting Voltage of Measurement Target (VOLT) (Example: 100.0V)

Display
(Upper/Lower)
CT
200A
("FUN" Blinking)
▽or △ Key
VOLT
220.0
SET/REC/STOP Key
VOLT
220.0
↑Blinking
▽or △ Key
VOLT
100.0
↑Blinking
SET/REC/STOP Key
VOLT
100.0
(5)

Setting Power Factor (PF) and Frequency (FREQ)

Set the power factor (PF) and frequency (FREQ) in the same way as the previous setting.
Refer to the FUN mode description for the power factor and frequency details.
Reference: 4.2.4 (16) Power Factor (PF), 4.2.4 (17) Frequency
Press the ▽or △ key until "VOLT" appears at the upper row on
the display.
Press the SET/REC/STOP key. The lower row indication starts
blinking.
Press the ▽or △ key to display "100.0" at the lower row.
Note A long press of the ▽ or △ key can rapidly change the
values in Decremental or incremental steps.
Press the SET/REC/STOP key to apply "100.0" for the
measurement target voltage. The blinking at the lower row stops.
Next, proceed to the power factor (PF) and frequency (FREQ)
settings.
3-8