The example below explains MX2 parameter settings concerning LCD digital operator.
Code
Function name
Output Frequency
F001
setting
Frequency source
A001
setting
Run command
A002
source setting
Software lock
b031
mode selection
Function code
b037
display restriction
Initial-screen
b038
selection
Data R/W
B166
selection
b087
Stop key selection
Automatic
b164
return to the
initial display
C001
Intelligent Input
terminal function
C007
LCD Digital Operator User's Manual v0_90 110218.doc
Content
You could set the frequency when the
frequency instruction is done from the
operator.
Select the frequency source.
Select the run/stop command
source.
This function prevents data
changes.
Parameter mode selection
displayed in the LCD digital
operator.
Select the start display.
Restrict the data read/write by
LCD digital operator.
Enable/Disable the LCD Digital
operator STOP key.
10 minutes after the last key
operation, the display will return to
the initial parameter set by b038.
If it is set to 31(OPE) and the input is
turned on, the frequency instruction
and the run command source will be
set from the LCD digital operator.
If it is set to 51(F-TM) and the input
is turned on, the frequency
instruction and the run command
source will be set to terminal mode.
If it is set to 86(DISP) and the input is
turned on, it will show the display set
by parameter (b038).
Setting parameter
Start Freq. ~ Max. Freq.
00: Keypad Potentiometer
01: Terminal
02: Digital Operator
03: Modbus
04: Option Card
06: Pulse train input
07: EzSQ (Drive Programming)
10: Operation function result
01: Terminal
02: Digital Operator
03: Modbus
04: Option Card
00: Lock(SFT)
01: Only FQ(SFT)
02: Lock
03: Only FQ
10: RUN chg mode
00: Full display
01: Function-specific display
02: User setting
03: Data comparison display
04: Basic display
05: Monitor display
000: Last modified parameter.
001~060: Display set
by d001~d060
201: F001 – Frequency Source
00: Read/Write OK
01: Protected
00: Enabling
01: Disabling
02: Disabling only stop
00: Enable
01: Disable
31: OPE (Operator Control)
51: F-TM (Force Terminal Mode)
86: DISP (Display limitation)