Ip Address And Subnet Mask (Ip 1 To Ip 4, Sub 1 To Sub 4); Dtail; Rated Primary Side Current Value (Sct5A) - Omron ZN-CTX21 User Manual

Portable power monitor
Hide thumbs Also See for ZN-CTX21:
Table of Contents

Advertisement

(26)

IP Address and Subnet Mask (IP 1 to IP 4, SUB 1 to SUB 4)

Specifies the 4 segments of the IP address (IP 1 to IP 4) and the 4 segments of the subnet
mask (SUB 1 to SUB 4).
Setting range (Numeric input):
IP 1, IP 2, IP 3, IP 4: 0 to 255
SUB 1, SUB 2, SUB 3, SUB 4: 0 to 255
Initial value: IP 1.IP 2.IP 3.IP 4 = 192.168.0.20
SUB 1.SUB 2.SUB 3.SUB 4 = 255.255.255.0
Note
・The unit resets itself and restarts when the MODE key is pressed to change the operation
mode, after the IP address and subnet mask values have been changed and applied with
the SET/REC/STOP key.
・The IP address and subnet mask settings are not possible when ETC is set to "OFF" and
IP is also set to "OFF".
(27)

DTAIL

Sets if a rated primary side current value, zero-out low current value and measurement
range are specified.
The range of selection (Options):
OFF / DISP
Initial value: OFF
Setting Value
OFF
DISP
Note
・The DTAIL setting is not possible when ETC is set to "OFF".
・The DTAIL setting returns to "OFF" when the unit is reset.
(28)

Rated Primary Side Current Value (SCT5A)

Specifies the rated primary side current value. However, this setting is only effective when
the dedicated CT type (CT) is set to "5A".
The range of selection (Numeric input):
5 to 9999
Initial value: 5
A rated primary side current value, zero-out low current value and
measurement range cannot be specified.
The RATE item is displayed when the ▽ key is pressed after the
setting is applied with the SET/REC/STOP key.
A rated primary side current value, zero-out low current value and
measurement range can be specified.
The SCT5A item is displayed when the ▽ key is pressed after the
setting is applied with the SET/REC/STOP key.
4-18
4. Setting the Unit (Unit Operation)
Operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Equo series

Table of Contents