Terminal Cover; Cimr-A 2A0004 To 0081, 4A0002 To 0044 (Ip20/Nema Type 1 Enclosure) - YASKAWA A1000 Series Technical Manual

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

3.5

Terminal Cover

Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is
complete.

◆ CIMR-A 2A0004 to 0081, 4A0002 to 0044 (IP20/NEMA Type 1 Enclosure)

Removing the Terminal Cover
1.
Loosen the terminal cover screw.
Figure 3.10
Figure 3.6 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
2.
Push in on the hook located on the bottom of the terminal cover, and gently pull forward. This should remove the
terminal cover.
Figure 3.11
Figure 3.7 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
Reattaching the Terminal Cover
Power lines and signal wiring should pass through the opening provided.
page 71
and
Wiring the Control Circuit Terminal on page 74
After all wiring to the drive and other devices is complete, reattach the terminal cover.
Figure 3.12
Figure 3.8 Reattaching the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
YEG
YEG
for details on wiring.
Connect ground wiring first,
followed by the main circuit,
and then wire the control circuit.
Power lines and signal wiring
exit through the opening provided.
3.5 Terminal Cover
Refer to Wiring the Main Circuit Terminal on
YEG
3
59