YASKAWA A1000 Series Technical Manual page 425

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

H1-
Function
Setting
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integral Reset
31
PID Integral Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter Cancel
35
PID Input Level Selection
Forward Run Command (2-wire
40
Sequence)
Reverse Run Command (2-wire
41
Sequence)
42
Run Command (2-wire Sequence 2)
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
H1 Multi-Function Digital Input Selections
V/f
V/f w/PG
OLV/PM
AOLV/PM
Open: Motor 1 (E1-
, E2-
)
Closed: Motor 2 (E3-
, E4-
)
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2-
= 12).
All Modes
Open: PID control enabled
Closed: PID control disabled
All Modes
Used in conjunction with an input terminal set for "Accel/decel time selection 1" (H1-
drive to switch between accel/decel times 3 and 4.
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
All Modes
Closed: Samples the analog frequency reference and operates the drive at that speed.
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
All Modes
Closed: Resets the PID control integral value.
All Modes
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
All Modes
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use parameters d1-09 to
d1-16 to set reference values.
All Modes
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
All Modes
Closed: Inverts the PID input signal
All Modes
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
Description
OLV
CLV
CLV/PM
B.3 Parameter Table
Page
common_
TMonly
219
common_
TMonly
218
common_
TMonly
219
common_
TMonly
219
common_
TMonly
220
= 7), and allows the
common_
TMonly
220
common_
TMonly
220
common_
TMonly
220
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
common_
TMonly
221
425
B