YASKAWA A1000 Series Technical Manual page 420

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

B.3 Parameter Table
No.(Addr.)
Name
F1-36
PG Option Card Disconnect
(3B5H)
Detection 2
F1-37
PG 2 Signal Selection
(3BDH)
<10> Default setting is determined by the control mode (A1-02).
F2: Analog Input Card (AI-A3)
No.(Addr.)
Name
F2-01
Analog Input Option Card
(38FH)
Operation Selection
F2-02
(368H)
Analog Input Option Card Gain
F2-03
(369H)
Analog Input Option Card Bias
F3: Digital Input Card (DI-A3)
No.(Addr.)
Name
F3-01
Digital Input Option Card Input
(390H)
Selection
F3-03
Digital Input Option DI-A3 Data
(3B9H)
Length Selection
F4: Analog Monitor Card (AO-A3)
No.(Addr.)
Name
F4-01
Terminal V1 Monitor Selection
(391H)
F4-02
(392H)
Terminal V1 Monitor Gain
F4-03
Terminal V2 Monitor Selection
(393H)
F4-04
(394H)
Terminal V2 Monitor Gain
F4-05
(395H)
Terminal V1 Monitor Bias
F4-06
(396H)
Terminal V2 Monitor Bias
420
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: A pulse detection
1: AB pulse detection
All Modes
0: Option card input terminals V1, V2, and V3 replace drive input terminals A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together to create the frequency
reference.
All Modes
Sets the gain for the input signal to the analog card.
All Modes
Sets the bias for the input signal to the analog card.
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
All Modes
0: 8 bit
1: 12 bit
2: 16 bit
All Modes
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of
the desired U -
monitor. Some U parameters are available only in certain control modes.
All Modes
Sets the gain for voltage output via terminal V1.
All Modes
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
the desired U -
monitor. Some U parameters are available only in certain control modes.
All Modes
Sets the gain for voltage output via terminal V2.
All Modes
Sets the amount of bias added to the voltage output via terminal V1.
All Modes
Sets the amount of bias added to the voltage output via terminal V2.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
Description
Description
Setting
common_
Default: 1
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Setting
common_
TMonly
Default: 0
Min: 0
Max: 1
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Setting
common_
TMonly
Default: 0
Min: 0
Max: 7
common_
TMonly
Default: 2
Min: 0
Max: 2
Setting
common_
Default: 102
TMonly
Min: 000
Max: 999
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
Default: 103
TMonly
Min: 000
Max: 999
Default: 50.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Page
208
208
Page
209
209
209
Page
209
210
Page
210
210
210
210
210
210

Hide quick links:

Advertisement

Table of Contents
loading