YASKAWA A1000 Series Technical Manual page 243

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

H6-03: Pulse Train Input Gain
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
No.
H6-03
H6-04: Pulse Train Input Bias
Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
No.
H6-04
H6-05: Pulse Train Input Filter Time
Sets the pulse train input filter time constant in seconds.
No.
H6-05
H6-06: Pulse Train Monitor Selection
Selects the monitor to output as a pulse train signal via terminal MP. Indicate which monitor to output entering the three
digits in U -
.
Refer to U: Monitor Parameters on page 291
selected by H6-06 appear in the table below.
No.
H6-06
<1> Set "000" when the terminal is not used, or when using the terminal in the through mode.
H6-07: Pulse Train Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the specified monitor item is at 100%. Set H6-
06 to 102 and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
No.
H6-07
H6-08: Pulse Train Input Minimum Frequency
Sets the minimum output frequency that can be detected by the pulse train input. Decreasing this setting reduces the time
the drive needs to react to changes in the input signal.
• If the pulse input frequency falls below this level, the pulse input value will be 0.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
H6-08
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Name
Pulse Train Input Gain
Name
Pulse Train Input Bias
Name
Pulse Train Input Filter Time
Name
Pulse Train Monitor Selection
Name
Pulse Train Monitor Scaling
Name
Pulse Train Input Minimum Frequency
5.7 H: Terminal Functions
Setting Range
0.0 to 1000.0%
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 2.00 s
for a complete list of monitors. Monitors that can be
Setting Range
000
, 031, 101, 102, 105, 116, 501,
<1>
502, 702 to 711, 801 to 809
Setting Range
0 to 32000 Hz
Setting Range
0.1 to 1000.0 Hz
Default
100.0%
Default
0.0%
Default
0.10 s
Default
102
Default
1440 Hz
5
Default
0.5 Hz
243