b1-08: Run command selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-
Tuning Mode). If required by the application, set b1-08 to allow the drive to run while in the Programming Mode.
No.
b1-08
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
b1-14
Setting 0: Standard phase order
Setting 1: Switched phase order
b1-15: Frequency Reference Selection 2
Refer to b1-01: Frequency Reference Selection 1 on page
No.
b1-15
b1-16: Run Command Selection 2
Refer to b1-02: Run Command Selection 1 on page
No.
b1-16
b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up will start the drive
or not.
No.
b1-17
Setting 0: Run command at power up is not issued
The Run command has to be cycled to start the drive.
Note: For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is
issued at power up, the RUN indicator LED will flash quickly.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Run Command Selection while in Programming Mode
Parameter Name
Phase Order Selection
Parameter Name
Frequency Reference Selection 2
137.
Parameter Name
Run Command Selection 2
Parameter Name
Run Command at Power Up
Setting Range
Setting Range
136.
Setting Range
Setting Range
Setting Range
5.2 b: Application
Default
0 to 2
0
Default
0 or 1
0
Default
0 to 4
0
Default
0 to 3
0
Default
0 or 1
0
5
143