B5: Pid Control - YASKAWA A1000 Series Technical Manual

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

5.2 b: Application
Figure 5.21
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function

◆ b5: PID Control

The drive has a built in PID (Proportional + Integral + Derivative) controller that can be used for closed loop control of
system variables such as pressure, temperature, and so on. The difference between the target and the feedback value
(deviation) is fed into the PID controller. The PID controller adjusts the drive output frequency in order to minimize the
deviation, providing accurate control of system variables.
P Control
The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly.
With P control, only an offset between the target and feedback remains.
I Control
The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that
typically remains when pure P control is used. The integral time (I time) constant determines how fast the offset is
eliminated.
D Control
D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant, then
adds this value to the PID input. This way the D portion of a PID controller provides a braking action to the controller
response and can reduce the tendency to oscillate and overshoot.
Be aware that D control tends to amplify noise on the deviation signal, which can result in control instability. D control
should therefore only be used when necessary.
PID Operation
To better demonstrate how PID works, the diagram below shows how the PID output changes when the PID input
(deviation) jumps from 0 to a constant level.
Figure 5.22
Using PID Control
Applications for PID control are listed in the table below.
Application
Machinery speed is fed back and adjusted to meet the target value. Synchronous control is performed using speed data from
Speed Control
other machinery as the target value
Pressure
Maintains constant pressure using pressure feedback.
Fluid Control
Keeps flow at a constant level by feeding back flow data.
Temperature Control
Maintains a constant temperature by controlling a fan with a thermostat.
152
ON
ON
b4-01
b4-02
Figure 5.21 Timer Operation
PID input
D control
PID Output
Figure 5.22 PID Operation
Description
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
ON
ON
b4-01
b4-02
Time
PID output
common_TMonly
I control
P control
Time
On (Closed)
Off (Open)
On (Closed)
common_TMonly
Off (Open)
Sensors Used
Tachometer
Pressure sensor
Flow rate sensor
Thermocoupler, Thermistor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents