b5-16: PID Sleep Delay Time
Sets the delay time to activate or deactivate the PID Sleep function.
No.
b5-16
b5-17: PID Accel/Decel Time
■
The PID acceleration/deceleration time is applied on the PID setpoint value.
As the normal acceleration times C1-
and can cause hunting or overshoot and undershoot when the setpoint changes quickly. Using the PID acceleration/
deceleration time instead helps to avoid such problems.
The PID acceleration/deceleration time can be canceled using a digital input programmed for "PID SFS cancel" (H1-
= 34).
No.
b5-17
■
b5-18: PID Setpoint Selection
Enables or disables parameter b5-19 for PID setpoint.
No.
b5-18
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint.
Setting 1: Enabled
Parameter b5-19 is used as PID setpoint.
b5-19: PID Setpoint Value
■
Used as the PID setpoint if parameter b5-18 = 1.
No.
b5-19
■
b5-20: PID Setpoint Scaling
Determines the units that the PID setpoint (b5-19) is set in and displayed. Also determines the units for monitors U5-01
and U5-04.
No.
b5-20
Setting 0: Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined
Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID
monitors U1-01 and U1-04.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Name
PID Sleep Delay Time
are applied after the PID output, they reduce the responsiveness of the system
Name
PID Accel/Decel Time
Parameter Name
PID Setpoint Selection
Name
PID Setpoint Value
Parameter Name
PID Setpoint Scaling
5.2 b: Application
Setting Range
Default
0.0 to 25.5 s
Setting Range
Default
0.0 to 6000.0 s
Setting Range
Default
0 or 1
Setting Range
Default
0.00 to 100.00%
Setting Range
Default
0 to 3
0.0 s
0.0 s
0
0.00%
1
5